View larger
1119412 ÖLFLEX CLASSIC 110 12G2,5 LAPP ÖLFLEX CLASSIC 110 12G2,5
1119412
1119412
ÖLFLEX CLASSIC 110 12G2,5
LAPP
1 m.
Cables > Power cable less 1 kV, for moving application
ÖLFLEX PVC, numbered cores
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A high-capacity wiring solution, the Lapp 1119412 control cable manages multiple signal and power paths across complex industrial automation setups. Engineers specify these multi-core cables for machine tool connections and centralized control panel wiring. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- CPR: Article number choice under www.lappkabel.com/cpr
- VDE reg. no. 7030 for the following sizes: up to 2.5 mm²: 2 - 65 coresfrom 4 mm²: 2 - 7 coresfrom 25 mm²: 2 - 5 cores
- Occasional flexing: 10 x outer diameter In power chains: 15 x outer diameter
- Fixed installation: 4 x outer diameter
- U0/U: 300/500 V
- Occasional flexing: -15°C to +70°C In power chains: -5°C to +70°C
- Fixed installation: -40°C to +80°C
- ETIM 5.0 Class-ID: EC000104
- ETIM 5.0 Class-Description: Control cable
- ETIM 6.0 Class-ID: EC000104
- ETIM 6.0 Class-Description: Control cable
More info
▲ÖLFLEX® CLASSIC 110 - PVC control cable, VDE registered, oil resistant and flexible for various applications, 300/500V, also for YSLY or YY
- CPR: Article number choice under www.lappkabel.com/cpr
- VDE certificate of conformity with
factory surveillance
Benefits
- Wide choice of standardized lengths and individual cuts
- Very broad range, items with up to 100 conductors
Application range
- For fixed installation as well as occasional flexing at free, non-continuously recurring movement without tensile load
- Dry or damp rooms that are subject to medium mechanical loads
- Suitable for torsional applications which are typical for the loop in wind turbine generators (WTG)
- In power chains for a travelling distance up to 5 m and 0,2 ... 1 million bending cycles, for following dimensions: 0,5 to 2.5mm² and 2 to 7 conductors
Product features
- Flame-retardant according IEC 60332-1-2
- Good chemical resistance, see catalogue appendix T1
- Oil-resistant according to DIN EN 50290-2-22 (TM54)
Norm references / Approvals
- VDE reg. no. 7030 for the following sizes:up to 2.5 mm²: 2 - 65 coresfrom 4 mm²: 2 - 7 coresfrom 25 mm²: 2 - 5 cores
Product Make-up
- Fine-wire strand made of bare copper wires
- PVC insulation LAPP P8/1
- Cores twisted in layers
- PVC outer sheath, grey (similar RAL 7001)
Classification ETIM 5
- ETIM 5.0 Class-ID: EC000104
- ETIM 5.0 Class-Description: Control cable
Classification ETIM 6
- ETIM 6.0 Class-ID: EC000104
- ETIM 6.0 Class-Description: Control cable
Core identification code
- Black with white numbers acc. to VDE 0293-334
Conductor stranding
- Fine wire according to DIN EN 60228 (VDE 0295), class 5 / IEC 60228 class 5
Torsion movement in WTG
- TW-0 & TW-1, refer to Appendix T0
Minimum bending radius
- Occasional flexing: 10 x outer diameter
In power chains: 15 x outer diameter - Fixed installation: 4 x outer diameter
Nominal voltage
- U0/U: 300/500 V
Test voltage
- 4000 V
Protective conductor
- G = with GN-YE protective conductor
- X = without protective conductor
Temperature range
- Occasional flexing: -15°C to +70°C
In power chains: -5°C to +70°C - Fixed installation: -40°C to +80°C