View larger
1024437 ÖLFLEX HEAT 125 C MC 7G2.5 LAPP ÖLFLEX HEAT 125 C MC 7G2.5
1024437
1024437
ÖLFLEX HEAT 125 C MC 7G2.5
LAPP
100 m.
Cables > Power cable less 1 kV, for moving application
ÖLFLEX HEAT Temperature measurement cables
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Created as a Lapp 1024437 ÖLFLEX HEAT 125 C MC 7G2.5 control cable, this shielded heat-resistant wire supports high thermal conditions. Such cables serve machinery operating near furnaces, heating elements, and elevated temperature zones.
Please note that pricing, availability and lead time are confirmed per enquiry through an RFQ.
- CPR: Article number choice under www.lappkabel.com/cpr
- Outer sheath: electron beam cross-linked polyolefin copolymer, black
- Occasional flexing: 15 x outer diameter
- Fixed installation: 5 x outer diameter
- Occasional flexing: -35 °C to +120 °C
- Fixed installation: -55°C to +125°C Temporary (3.000h): up to +145°C
- ETIM 5.0 Class-ID: EC000104
- ETIM 5.0 Class-Description: Control cable
- ETIM 6.0 Class-ID: EC000104
- ETIM 6.0 Class-Description: Control cable
More info
▲ÖLFLEX® HEAT 125 C MC - halogen free shielded control cable with DNV GL certificate, special fire performance, IEC 60332-3, suitable for +125°C
- CPR: Article number choice under www.lappkabel.com/cpr
- Improved characteristics in the event of a fire
- DNV GL approved
Benefits
- For safety in areas with high density of people
- Reduction of flame propagation, density and toxicity of smoke gases in event of fire
- Minimises damage to buildings and equipment caused by the formation of toxic acid fumes in fires
- Certified for maritime applications
- Copper braiding screens the cable against
electromagnetic interference
Application range
- For outdoor applications
- For the wiring and connection of lighting, heating appliances, control cabinets, and distributors in mechanical and plant engineering
- For use in traffic regulation systems and outdoors
- Coil winding, electromagnets, pumps, electrical systems
- Heat treatment plants, pressure die casting, heating and cooling technology
Product features
- Fire behaviour:
- Halogen-free (IEC 60754-1)
- No corrosive gases (IEC 60754-2)
- Low smoke density (IEC 61034-2)
- Flame-retardant (IEC 60332-1-2,
NF C 32-070 (C1) and
NF-F 16-101 (Class C))
- Low toxicity (EN 50305) - No flame-propagation according to IEC 60332-3-22, IEC 60332-3-24 and IEC 60332-3-25 (Flame spread on vertical cable bundle)
- Oil-resistant acc. IEC 60227-1 (ST9) and EN 50264-1 (EM104)
- UV-resistant according to ISO 4892-2
- Ozone-resistant according to EN 50396
Norm references / Approvals
- DNV GL approved
- Based on EN 50525-3-21 and EN 50525-3-41
Product Make-up
- Fine-wire, tinned-copper conductor
- Electron beam cross-linked polyolefin copolymer insulation
- Cores twisted in layers
- Tinned-copper braiding
- Outer sheath: electron beam cross-linked polyolefin copolymer, black
Classification ETIM 5
- ETIM 5.0 Class-ID: EC000104
- ETIM 5.0 Class-Description: Control cable
Classification ETIM 6
- ETIM 6.0 Class-ID: EC000104
- ETIM 6.0 Class-Description: Control cable
Core identification code
- Colour-coded according to VDE 0293-308, refer to Appendix T9
or black with white numbers - refer to article table
Specific insulation resistance
- >2 TOhm x cm
Conductor stranding
- Fine wire according to VDE 0295,
class 5/IEC 60228 class 5
Minimum bending radius
- Occasional flexing: 15 x outer diameter
- Fixed installation: 5 x outer diameter
Nominal voltage
- Up to 1.0mm² U0/U 300/500 V
From 1.5mm² U0/U 450/750 V - 0.6/1kV from 1.5 mm² in the case of fixed and protected installation
Test voltage
- C/C 4000 V, C/S 2500 V
Protective conductor
- G = with GN-YE protective conductor
- X = without protective conductor
Temperature range
- Occasional flexing: -35 °C to +120 °C
- Fixed installation: -55°C to +125°C
Temporary (3.000h): up to +145°C