Individual design depending on the item: power cores without or with one or two individually screened control core pairs twisted together in short lay lengths
PVC outer sheath, black (RAL 9005)
Classification ETIM 5
ETIM 5.0 Class-ID: EC000104
ETIM 5.0 Class-Description: Control cable
Classification ETIM 6
ETIM 6.0 Class-ID: EC000104
ETIM 6.0 Class-Description: Control cable
Core identification code
Power cores: black with marking U/L1/C/L+; V/L2; W/L3/D /L-; GN/YE protective conductor
Single-paired versions: black; white Double-paired versions: black with white numbers 5; 6; 7; 8 0,34mm² pairs: WH/BN/GN/YE
Conductor stranding
Fine wire according to VDE 0295 Class 5/ IEC 60228 Class 5
Minimum bending radius
Occasional flexing: 15 x outer diameter
Fixed installation: 6 x outer diameter
Nominal voltage
Power cores and control cores: IEC U0/U: 600/1000 V
UL & CSA: 1000 V
Test voltage
Core/Core: 4 kV
Core/Screen: 4 kV
Protective conductor
G = with GN-YE protective conductor
Temperature range
Occasional flexing: -5°C to +70°C (UL: +80°C) Fixed installation: -40°C to +80°C
Product Datasheet
Electrica Online Product DatasheetPrepared from the current product description, catalog data and structured technical attributes.