View larger
00466373 ÖLFLEX HEAT 180 MS 4G6 LAPP ÖLFLEX HEAT 180 MS 4G6
00466373
00466373
ÖLFLEX HEAT 180 MS 4G6
LAPP
500 m.
Cables > Power cable less 1 kV, for moving application
ÖLFLEX HEAT Temperature measurement cables
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Lapp 00466373 ÖLFLEX HEAT 180 MS 4G6 ÖLFLEX® HEAT 180 MS is a high-temperature silicone control cable designed to withstand extreme thermal conditions in heavy industrial manufacturing. Heat-resistant cables of this classification are typically deployed around furnaces, foundries, and heating equipment. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- CPR: Article number choice under www.lappkabel.com/cpr: CPR: Article number choice under www.lappkabel.com/cpr
- From 6 cores: black with white numbers: From 6 cores: black with white numbers
- Occasional flexing: 15 x outer diameter: Occasional flexing: 15 x outer diameter
- Fixed installation: 4 x outer diameter: Fixed installation: 4 x outer diameter
- U0/U: 300/500 V Working voltage UL: 600 V: U0/U: 300/500 V Working voltage UL: 600 V
- According to VDE: -60 °C to +180 °C: According to VDE: -60 °C to +180 °C
- UL/cUL: up to +150°C (adequate ventilation required): UL/cUL: up to +150°C (adequate ventilation required)
- ETIM 5.0 Class-ID: EC001578: ETIM 5.0 Class-ID: EC001578
- ETIM 5.0 Class-Description: Flexible cable: ETIM 5.0 Class-Description: Flexible cable
- ETIM 6.0 Class-ID: EC001578: ETIM 6.0 Class-ID: EC001578
- ETIM 6.0 Class-Description: Flexible cable: ETIM 6.0 Class-Description: Flexible cable
More info
▲ÖLFLEX® HEAT 180 MS - silcione power and control cable, UL/cUL-AWM approved for machine and plant construstion in North America, suitable for +180°C
- MS = Multi-Standard
For use in the USA and Canada - UL AWM Style 4476 (150 °C/600 V)
- CPR: Article number choice under www.lappkabel.com/cpr
Benefits
- Certified for the USA and Canada for export-oriented machine, appliance and apparatus manufacturers
- Thicker cable design meets the requirements of the FT-1 flame test and also approved for the external interconnection of apparatuses and appliances
- Flexibility simplifies installation where space is limited
- Possesses insulating properties after combustion due to remaining SiO2 ash on the conductor
Application range
- Areas with high ambient temperatures where insulating and sheath materials of conventional cables will embrittle after a short while
- Typical fields of application
- Steel, ceramic and iron works
- Bakery equipment and industrial furnaces
- Electric motor industry
- Sauna/solarium construction
- Thermal and heating elements
- Lighting technology
- Ventilator engineering
- Air-conditioning technology
- Galvanisation technology
Product features
- Halogen-free (IEC 60754-1), no corrosive gases (IEC 60754-2)
- Flame-retardant acc. to IEC 60332-1-2, Cable Flame Test, CSA FT 1
- Good hydrolysis and UV-resistance
- Resistant to a multitude of oils, alcohols, vegetable and animal fats and chemical substances
- Adequate ventilation must be ensured, since the mechanical properties of silicone cables decrease from +100°C in the absence of air
Norm references / Approvals
- UL AWM 4476 and cUL AWM II A/B
Construction B, External wiring - UL File No. E63634
Product Make-up
- Fine-wire, tinned-copper conductor
- Silicone-based core insulation
- Cores twisted together
- Silicone-based outer sheath,
colour black
Classification ETIM 5
- ETIM 5.0 Class-ID: EC001578
- ETIM 5.0 Class-Description: Flexible cable
Classification ETIM 6
- ETIM 6.0 Class-ID: EC001578
- ETIM 6.0 Class-Description: Flexible cable
Core identification code
- Colours according to VDE 0293-308, refer to Appendix T9
- From 6 cores: black with white numbers
Conductor stranding
- Fine wire according to VDE 0295,
class 5/IEC 60228 class 5 - (Refer to Appendix T16 for the matching US conductor sizes in AWG standard)
Minimum bending radius
- Occasional flexing: 15 x outer diameter
- Fixed installation: 4 x outer diameter
Nominal voltage
- U0/U: 300/500 V
Working voltage UL: 600 V
Test voltage
- 2000 V
Protective conductor
- G = with GN-YE protective conductor
- X = without protective conductor
Temperature range
- According to VDE: -60 °C to +180 °C
- UL/cUL: up to +150°C
(adequate ventilation required)