View larger
0035160 UNITRONIC LiYY (TP) 2x2x0,25 LAPP UNITRONIC LiYY (TP) 2x2x0,25
0035160
0035160
UNITRONIC LiYY (TP) 2x2x0,25
LAPP
1 m.
Cables > Data and communication cable
flexible data cable transfer from special cable
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A Lapp 0035160 UNITRONIC LiYY (TP) 2x2x0,25 control cable is utilized for low-frequency data transmission, instrumentation, and industrial control applications. Twisted pair construction helps mitigate electromagnetic interference between internal circuits in standard automation environments. Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- CPR: Article number choice under www.lappkabel.com/cpr
- Outer sheath: made of PVC
- Outer sheath colour: grey (similar to pebble grey/ RAL 7032)
- Occasional flexing: 10 x outer diameter
- Fixed installation: 4 x Outer diameter
- Occasional flexing temperature: -5°C to +70°C
- Fixed installation temperature: -40°C to +80°C
- ETIM 5.0 Class-ID: EC000104
- ETIM 5.0 Class-Description: Control cable
- ETIM 6.0 Class-ID: EC000104
- ETIM 6.0 Class-Description: Control cable
More info
▲UNITRONIC® LiYY (TP): Low-frequency PVC data cable DIN 47100 coded, Flexible, 0.34mm² Maxi TERMI-POINT®, Twisted Pairs, Flame retardant, Instrumentation Control
- TP = twisted pair
- CPR: Article number choice under www.lappkabel.com/cpr
Benefits
- Decoupling of circuits by means of twisted-pair (TP) design (crosstalk effects)
Application range
- Dry or damp rooms
Product features
- Twisted in pairs to reduce decoupling. As a result, additional screening is often not required.
- Flame-retardant according IEC 60332-1-2
Norm references / Approvals
- Based on VDE 0812
Product Make-up
- Fine-wire strand made of bare copper wires
- Core insulation made of PVC
- TP structure
- Outer sheath made of PVC
Outer sheath colour: grey (similar to pebble grey/ RAL 7032)
Classification ETIM 5
- ETIM 5.0 Class-ID: EC000104
- ETIM 5.0 Class-Description: Control cable
Classification ETIM 6
- ETIM 6.0 Class-ID: EC000104
- ETIM 6.0 Class-Description: Control cable
Core identification code
- DIN 47100, refer to Appendix T9
Mutual capacitance
- Approx. 120 nF/km
Inductivity
- approx. 0.65 mH/km
Conductor stranding
- Fine copper wire strands
Minimum bending radius
- Occasional flexing: 10 x outer diameter
- Fixed installation: 4 x Outer diameter
Temperature range
- Occasional flexing: -5°C to +70°C
- Fixed installation: -40°C to +80°C