View larger
00350173 ÖLFLEX CLASSIC 100 CY 4G2,5 LAPP ÖLFLEX CLASSIC 100 CY 450/750V 4G2,5
00350173
00350173
ÖLFLEX CLASSIC 100 CY 4G2,5
LAPP
1 m.
Cables > Power cable less 1 kV, for moving application
ÖLFLEX PVC, coloured cores, screened
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Formulated as a flexible cable, the 00350173 ÖLFLEX CLASSIC 100 CY 4G2,5 LAPP ÖLFLEX CLASSIC 100 CY 450/750V 4G2,5 provides reliable signal transmission shielded against electrical interference. Screened instrumentation and power cables are heavily utilized in industrial automation environments where sensitive data signals run adjacent to power lines. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- CPR compliance: Article number choice under www.lappkabel.com/cpr
- Application note: For nominal voltage U0/U: 300/500V and conductor cross-sections below 1,5mm² see ÖLFLEX® CLASSIC 100 CY 300/500V
- Core identification: Up to 5 cores: colour-coded according to VDE 0293-308, refer to Appendix T9; From 6 cores: ÖLFLEX® colour code, refer to Appendix T7
- Bending radius: Occasional flexing: 20 x outer diameter; Fixed installation: 6 x outer diameter
- Nominal voltage U0/U: 450/750 VAC In protected and fixed installations: U0/U: 600/1000 V
- Temperature range: Occasional flexing: -5°C to +70°C; Fixed installation: -40°C to +80°C
- ETIM 5.0 Class: EC001578 Flexible cable
- ETIM 6.0 Class: EC001578 Flexible cable
More info
▲ÖLFLEX® CLASSIC 100 CY 450/750V - flexible PVC cable, colour coded and screened, power and control cable for various applications
- CPR: Article number choice under www.lappkabel.com/cpr
- EMC-compliant
- For nominal voltage U0/U: 300/500V and conductor cross-sections below 1,5mm² see ÖLFLEX® CLASSIC 100 CY 300/500V
Benefits
- High electrical performance due to 4 kV test voltage
- Shielding against electromagnetic fields
Application range
- Plant engineering
Industrial machinery
Heating and air-conditioning systems - Conveyor and transport systems
- Servo drives
- In EMC-sensitive environments
(electromagnetic compatibility)
Product features
- Flame-retardant according IEC 60332-1-2
- Good chemical resistance, see catalogue appendix T1
- High degree of screening
low transfer impedance
(max. 250 Ω/km at 30 MHz)
Norm references / Approvals
- Based on EN 50525-2-51
- Based on EN 50525-2-11 and EN 50525-2-31
Product Make-up
- Fine-wire strand made of bare copper wires
- PVC insulation LAPP P8/1
- Cores twisted in layers
- PVC inner sheath, grey
- Tinned-copper braiding
- PVC outer sheath, transparent
Classification ETIM 5
- ETIM 5.0 Class-ID: EC001578
- ETIM 5.0 Class-Description: Flexible cable
Classification ETIM 6
- ETIM 6.0 Class-ID: EC001578
- ETIM 6.0 Class-Description: Flexible cable
Core identification code
- Up to 5 cores: colour-coded according to VDE 0293-308, refer to Appendix T9
- From 6 cores: ÖLFLEX® colour code, refer to Appendix T7
Conductor stranding
- Fine wire according to VDE 0295,
class 5/IEC 60228 class 5
Minimum bending radius
- Occasional flexing: 20 x outer diameter
- Fixed installation: 6 x outer diameter
Nominal voltage
- U0/U: 450/750 VAC
In protected and fixed installations:
U0/U: 600/1000 V
Test voltage
- 4000 V
Protective conductor
- G = with GN-YE protective conductor
- X = without protective conductor
Temperature range
- Occasional flexing: -5°C to +70°C
- Fixed installation: -40°C to +80°C