View larger
0032474 RD-Y(ST)Y 16x2x0,5 GY LAPP RD-Y(ST)Y 16x2x0,5 GY
0032474
0032474
RD-Y(ST)Y 16x2x0,5 GY
LAPP
100 m.
Cables > Data and communication cable
UNITRONIC low frequency
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Industrial process instrumentation relies on the Lapp 0032474 RD-Y(ST)Y 16x2x0,5 GY signal cable to link measurement transducers with control panels. Multipair instrumentation cables organize multi-channel sensor data inside process control facilities.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Outer sheath colour: grey or blue for intrinsically safe systems
- Outer sheath colour: grey
- Pair no. 1: a-conductor: blue b-conductor: red Pair no. 2: a-conductor: grey b-conductor: yellow
- Pair no. 3: a-core: green b-core brown Pair no. 4: a-core: white b-core black
- At 800 Hz: ≤ 100 nF/km The values may be exceeded by 20 % on cables with up to 4 double cores.
- (loop): ≤ 73.6 Ohm/km
- At 1 kHz: approx. 1.2 dB/km
- At 10 kHz: approx. 2.8 dB/km
- Occasional flexing: 15 x outer diameter
- Fixed installation: 7.5 x outer diameter
- At 10 kHz and 500 m cable length: min. 60 dB
- C/C: 2000 V
- C/S: 2000 V
- At 1 kHz: approx. 370 ohm
- At 10 kHz: approx. 130 ohm
- Occasional flexing: -5°C to +50°C
More info
▲RD-Y(ST)Y: PVC Process control data cable for, e.g., control stations/ units and monitoring systems, Maxi TERMI-POINT®, Paired stranding, Static screen foil
Benefits
- Decoupling of circuits by means of twisted-pair (TP) design (crosstalk effects)
Application range
- RD-Y(ST)Y is used as a data transmission cable for applications such as monitoring systems and control units
- Measurement, control and regulation technology and also in control rooms of power plants and industrial facilities.
- Suitable for transmission of analog and digital signals up to a frequency of about 10 kHz
- Designed for fixed installations in enclosed rooms.
Product features
- Outer sheath colour: grey or
blue for intrinsically safe systems - Variant with 2 double cores twisted as star quad
- Flame retardant acc. to IEC 60332-1-2
Norm references / Approvals
- Based on DIN VDE 0815
Product Make-up
- 7-wire bare stranded copper conductor,
core insulation made of PVC - Cores twisted into pairs,
4 pairs twisted into a bundle,
bundles in layers,
bundles labelled using numbered foil - Aluminium-laminated plastic foil static screen with tinned drain wire
- Outer sheath made of PVC
- Outer sheath colour: grey
Classification ETIM 5
- ETIM 5.0 Class-ID: EC000104
- ETIM 5.0 Class-Description: Control cable
Classification ETIM 6
- ETIM 6.0 Class-ID: EC000104
- ETIM 6.0 Class-Description: Control cable
Core identification code
- Pair no. 1: a-conductor: blue
b-conductor: red
Pair no. 2: a-conductor: grey
b-conductor: yellow - Pair no. 3: a-core: green
b-core brown
Pair no. 4: a-core: white
b-core black
Mutual capacitance
- At 800 Hz: ≤ 100 nF/km
The values may be exceeded by 20 % on cables with up to 4 double cores.
Conductor resistance
- (loop): ≤ 73.6 Ohm/km
Cable attenuation/attenuation
- At 1 kHz: approx. 1.2 dB/km
- At 10 kHz: approx. 2.8 dB/km
Minimum bending radius
- Occasional flexing: 15 x outer diameter
- Fixed installation: 7.5 x outer diameter
Short-range crosstalk attenuation
- At 10 kHz and 500 m cable length:
min. 60 dB
Test voltage
- C/C: 2000 V
- C/S: 2000 V
Characteristic impedance
- At 1 kHz: approx. 370 ohm
- At 10 kHz: approx. 130 ohm
Temperature range
- Occasional flexing: -5°C to +50°C
- Fixed installation: -40°C to +80°C