LAPP 0016047 0016047 ÖLFLEX CLASSIC 100 SY 7G1 LAPP ÖLFLEX CLASSIC 100 SY 7G1 View larger
Images are for illustrative purposes only. Please refer to data sheet for details

0016047 ÖLFLEX CLASSIC 100 SY 7G1 LAPP ÖLFLEX CLASSIC 100 SY 7G1

0016047

0016047

ÖLFLEX CLASSIC 100 SY 7G1

LAPP

1 m.

ÖLFLEX CLASSIC 100 SY 7G1 ÖLFLEX® CLASSIC 100 SY

Cables > Power cable less 1 kV, for moving application
ÖLFLEX PVC, coloured cores, screened

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

ÖLFLEX® CLASSIC 100 SY - flexible PVC cable, colour coded with steel wire braid, power and control cable for various applications

  • CPR: Article number choice under www.lappkabel.com/cpr
  • Steel wire braiding for extra mechanical protection

Benefits

  • Extra mechanical protection due to braided steel wire

Application range

  • Plant engineering
    Industrial machinery
    Heating and air-conditioning systems
  • Areas with high mechanical stress

Product features

  • Flame-retardant according IEC 60332-1-2
  • Good chemical resistance, see catalogue appendix T1

Norm references / Approvals

  • Based on IEC 60227-5 and EN 50525-2-51

Product Make-up

  • Fine-wire strand made of bare copper wires
  • PVC insulation LAPP P8/1
  • Cores twisted in layers
  • PVC inner sheath, grey
  • Braid of galvanized steel wires
  • PVC outer sheath, transparent

Classification ETIM 5

  • ETIM 5.0 Class-ID: EC001578
  • ETIM 5.0 Class-Description: Flexible cable

Classification ETIM 6

  • ETIM 6.0 Class-ID: EC001578
  • ETIM 6.0 Class-Description: Flexible cable

Core identification code

  • Up to 5 cores: colour-coded according to VDE 0293-308, refer to Appendix T9
  • From 6 cores: ÖLFLEX® colour code, refer to Appendix T7

Conductor stranding

  • Fine wire according to VDE 0295,
    class 5/IEC 60228 class 5

Minimum bending radius

  • Occasional flexing: 20 x outer diameter
  • Fixed installation: 6 x outer diameter

Nominal voltage

  • Up to 1.5 mm²: U0/U: 300/500 V
  • From 2.5 mm²: U0/U: 450/750 V
    From 2.5 mm², in the case of fixed and protected installations: U0/U: 600/1000 V

Test voltage

  • 4000 V

Protective conductor

  • G = with GN-YE protective conductor
  • X = without protective conductor

Temperature range

  • Occasional flexing: -5°C to +70°C
  • Fixed installation: -40°C to +80°C

Product Datasheet