Wide application range due to multiple certifications
Application range
Plant engineering Industrial machinery Heating and air-conditioning systems
Machine tools
Mainly used in dry, damp and wet interiors (including water-oil mixtures), but not for outdoor use
For fixed installation under medium mechanical load conditions, and applications with occasional flexing at free, non-continuously recurring movement without tensile load or compulsory guidance
Note: for the use of AWM (Appliance Wiring Material) cables in industrial machinery (USA) according to NFPA 79: please see the catalogue appendix table T29
Product features
Flame-retardant according to IEC 60332-1-2 and UL 1581 §1061 Cable Flame Test
Oil-resistant according to EN 50363-4-1: TM5
Norm references / Approvals
H05VV5-F (EN 50525-2-51)
UL AWM Style 21098 CSA AWM I A/B II A/B
Multi-standard cables have conductor strands with nominal sizes in mm² or AWG/kcmil. The master size is mentioned in the table below, while the equivalent size of the other system can be found in the Appendix T16 of this catalogue. For this related secondary size the cross-section of the conductor mostly works out to be greater than the specified nominal value.
Product Make-up
Fine-wire strand made of bare copper wires
PVC core insulation
Cores twisted in layers
PVC outer sheath, high oil-resistance, grey (similar to RAL 7001)
Classification ETIM 5
ETIM 5.0 Class-ID: EC000104
ETIM 5.0 Class-Description: Control cable
Classification ETIM 6
ETIM 6.0 Class-ID: EC000104
ETIM 6.0 Class-Description: Control cable
Core identification code
Black with white numbers acc. to VDE 0293-334
Conductor stranding
Fine wire according to VDE 0295, class 5/IEC 60228 class 5
Minimum bending radius
Occasional flexing: 12.5 x outer diameter
Fixed installation: 4 x outer diameter
Nominal voltage
HAR U0/U: 300/500 V
UL/CSA: 600 V
Test voltage
3000 V
Protective conductor
G = with GN-YE protective conductor
X = without protective conductor
Temperature range
Occasional flexing: HAR: -5°C to +70°C UL/CSA: +90°C
Fixed installation: HAR: -40°C to +70°C UL/CSA: +90°C
Product Datasheet