View larger
Images are for illustrative purposes only. Please refer to data sheet for details
00136323 ÖLFLEX 550 P 4G2,5 LAPP ÖLFLEX 550 P 4G2,5
00136323
00136323
ÖLFLEX 550 P 4G2,5
LAPP
1 m.
ÖLFLEX 550 P 4G2,5
ÖLFLEX® 550 P*
Cables > Power cable less 1 kV, for moving application
ÖLFLEX PUR/TPE coloured
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteMore info
▲ÖLFLEX® 550 P - PUR power cable, harmonized according H05BQ-F / H07BQ-F type for oil and abrasion resistant use witgh handheld equipment or building machines
- High mechanical strength
- Good oil resistance
- H05BQ-F/H07BQ-F design standard
Benefits
- Harmonised use in Europe
- Increased durability under harsh conditions thanks to robust PUR outer sheath
- Resistant to contact with many mineral oil-based lubricants, diluted acids, aqueous alkaline solutions and other chemical media
- Wide temperature range for applications in harsh climatic environments
- The signal colour of the outer sheath increases safety and visual perception
Application range
- Portable handheld electrical devices such as drills, sanders, jig saws or grinders
- Building sites, camp sites, stage applications
- Construction machinery
- Agricultural equipment
- For indoor and outdoor use
Product features
- Oil-resistant
- Abrasion and notch-resistant
- Flexible down to -40°C
- Resistant to hydrolysis and microbes
Norm references / Approvals
- EN 50525-2-21
- H05BQ-F/H07BQ-F design standard
Product Make-up
- Fine-wire, bare copper conductor
- Core insulation: rubber compound
- Cores twisted together
- PUR outer sheath
- Sheath colour: orange
Classification ETIM 5
- ETIM 5.0 Class-ID: EC001578
- ETIM 5.0 Class-Description: Flexible cable
Classification ETIM 6
- ETIM 6.0 Class-ID: EC001578
- ETIM 6.0 Class-Description: Flexible cable
Core identification code
- Colours according to VDE 0293-308, refer to Appendix T9
Conductor stranding
- Fine wire according to VDE 0295,
class 5/IEC 60228 class 5
Minimum bending radius
- For flexible use:
12.5 x outer diameter - Fixed installation: 4 x outer diameter
Nominal voltage
- Up to 1.0 mm²: U0/U: 300/500 V
- From 1.5 mm²: U0/U: 450/750 V
Test voltage
- 3000 V
Protective conductor
- G = with GN-YE protective conductor
- X = without protective conductor
Temperature range
- Occasional flexing: -40°C to +90°C
- Fixed installation: -50°C to +90°C