View larger
0012446 ÖLFLEX EB 12X1 LAPP Control cable for intrinsically safe circuits according to IEC 60079-14 / EN 600..
0012446
0012446
ÖLFLEX EB 12X1
LAPP
1 m.
Cables > Power cable less 1 kV, for moving application
Control cables for special applications
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The Lapp 0012446 ÖLFLEX EB 12X1 control cable is specifically built for intrinsically safe circuits within hazardous industrial zones and process automation frameworks. Specialized control wiring routes safe signals between explosion-protected devices and control rooms. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- CPR: Article number choice under www.lappkabel.com/cpr
- Outer sheath: PVC, sky blue similar to RAL 5015
- Occasional flexing: 15 x outer diameter
- Fixed installation: 4 x outer diameter
- U0/U: 300/500 V
- Core/core: 3000 V
- Occasional flexing: -5°C to +70°C
- Fixed installation: -40°C to +80°C
- ETIM 5.0 Class-ID: EC000104
- ETIM 5.0 Class-Description: Control cable
- ETIM 6.0 Class-ID: EC000104
- ETIM 6.0 Class-Description: Control cable
More info
▲ÖLFLEX® EB - PVC control cable, flexible and numbered, with blue outer sheath for intrinsically-safe circuits, U0/U: 300/500V
- CPR: Article number choice under www.lappkabel.com/cpr
- For use within intrinsically safe circuits - type of protection 'i'
- UV and weather-resistant according to ISO 4892-2
Benefits
- Space-saving installation due to small cable diameters
- Suitable for outdoor applications
Application range
- For intrinsically safe circuits (type of protection i - intrinsic safety) according to IEC 60079-14:2013 / EN 60079-14:2014 / VDE 0165-1:2014, section 16.2.2
Product features
- UV and weather-resistant according to ISO 4892-2
- Flame-retardant according IEC 60332-1-2
Norm references / Approvals
- Based on EN 50525-2-51
Product Make-up
- Fine-wire strand made of bare copper wires
- PVC insulation LAPP P8/1
- Cores twisted in layers
- Outer sheath: PVC, sky blue similar to RAL 5015
Classification ETIM 5
- ETIM 5.0 Class-ID: EC000104
- ETIM 5.0 Class-Description: Control cable
Classification ETIM 6
- ETIM 6.0 Class-ID: EC000104
- ETIM 6.0 Class-Description: Control cable
Core identification code
- Black with white numbers acc. to VDE 0293-334
Mutual capacitance
- Core/core approx. 140 nF/km
Inductivity
- approx. 0.52 mH/km
Conductor stranding
- Fine wire according to VDE 0295,
class 5/IEC 60228 class 5
Minimum bending radius
- Occasional flexing: 15 x outer diameter
- Fixed installation: 4 x outer diameter
Nominal voltage
- U0/U: 300/500 V
Test voltage
- Core/core: 3000 V
Temperature range
- Occasional flexing: -5°C to +70°C
- Fixed installation: -40°C to +80°C