View larger
0011404 ÖLFLEX 140 H05VV5-F 4G1,5 LAPP ÖLFLEX 140 H05VV5-F 4G1,5
0011404
0011404
ÖLFLEX 140 H05VV5-F 4G1,5
LAPP
1 m.
Cables > Power cable less 1 kV, for moving application
ÖLFLEX PVC cable AWM recognized
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Providing dependable performance in automated manufacturing systems, the Lapp 0011404 ÖLFLEX 140 H05VV5-F 4G1,5 control cable connects critical electrical components within industrial panels and machine assemblies.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Oil-resistant according to EN 50363-4-1: TM5
- Harmonised (HAR): H05VV5-F
- CPR: Article number choice under www.lappkabel.com/cpr
- Occasional flexing: 12.5 x outer diameter
- Fixed installation: 4 x outer diameter
- U0/U: 300/500 V
- Occasional flexing: -5°C to +70°C
- Fixed installation: -40°C to +70°C
- ETIM 5.0 Class-ID: EC000104
- ETIM 5.0 Class-Description: Control cable
- ETIM 6.0 Class-ID: EC000104
- ETIM 6.0 Class-Description: Control cable
More info
▲ÖLFLEX® 140 - H05VV5-F harmonised PVC control cable, oil-resistant, flexible and numbered for various applications, U0/U: 300/500 V
- Oil-resistant according to EN 50363-4-1: TM5
- Harmonised (HAR): H05VV5-F
- CPR: Article number choice under www.lappkabel.com/cpr
Benefits
- High acceptance in Europe due to Harmonisation
Application range
- Plant engineering
Industrial machinery
Heating and air-conditioning systems - Machine tools
- Mainly used in dry, damp and wet interiors (including water-oil mixtures), but not for outdoor use
- For fixed installation under medium mechanical load conditions, and applications with occasional flexing at free, non-continuously recurring movement without tensile load or compulsory guidance
Product features
- Flame-retardant according IEC 60332-1-2
- Oil-resistant according to EN 50363-4-1: TM5
Norm references / Approvals
- EN 50525-2-51
Product Make-up
- Fine-wire strand made of bare copper wires
- PVC core insulation
- Cores twisted in layers
- PVC outer sheath, high oil-resistance, grey (similar to RAL 7001)
Classification ETIM 5
- ETIM 5.0 Class-ID: EC000104
- ETIM 5.0 Class-Description: Control cable
Classification ETIM 6
- ETIM 6.0 Class-ID: EC000104
- ETIM 6.0 Class-Description: Control cable
Core identification code
- Black with white numbers acc. to VDE 0293-334
Conductor stranding
- Fine wire according to VDE 0295,
class 5/IEC 60228 class 5
Minimum bending radius
- Occasional flexing: 12.5 x outer diameter
- Fixed installation: 4 x outer diameter
Nominal voltage
- U0/U: 300/500 V
Test voltage
- 2000 V
Protective conductor
- G = with GN-YE protective conductor
- X = without protective conductor
Temperature range
- Occasional flexing: -5°C to +70°C
- Fixed installation: -40°C to +70°C