View larger
0011197 ÖLFLEX 191CY 7G2,5 LAPP ÖLFLEX 191CY 7G2,5
0011197
0011197
ÖLFLEX 191CY 7G2,5
LAPP
1 m.
Cables > Power cable less 1 kV, for moving application
ÖLFLEX PVC cable AWM recognized
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A Lapp control cable, represented by part number 0011197 ÖLFLEX 191CY 7G2,5, functions as a shielded multi-core cable engineered for industrial machinery where electromagnetic compatibility and signal integrity are essential. Technicians install this type of component in production lines, manufacturing plants, and processing equipment to protect delicate control signals from external electrical interference.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Further items with 0,75 mm²: see ÖLFLEX® 150 CY
- Oil-resistant according to EN 50363-4-1: TM5
- Occasional flexing: 20 x outer diameter
- Fixed installation: 6 x outer diameter
- HAR U0/U: 300/500 V
- UL/CSA: 600 V
- Occasional flexing: -5°C to +70°C UL/CSA: -5°C to +90°C
- Fixed installation: -40°C to +70°C UL/CSA: +90°C
- ETIM 5.0 Class-ID: EC000104
- ETIM 5.0 Class-Description: Control cable
- ETIM 6.0 Class-ID: EC000104
- ETIM 6.0 Class-Description: Control cable
More info
▲ÖLFLEX® 191 CY - PVC control cable with UL/CSA AWM, oil-resistant, screened and flexible for various applications, UL/CSA: 600V
- Conductor cross-section up to 120 mm²
- Further items with 0,75 mm²: see ÖLFLEX® 150 CY
- Oil-resistant according to EN 50363-4-1: TM5
Benefits
- High electrical performance due to 4 kV test voltage
- Multifunctional application possibilities
Application range
- Plant engineering
Industrial machinery
Heating and air-conditioning systems - In EMC-sensitive environments
(electromagnetic compatibility) - Mainly used in dry, damp and wet interiors (including water-oil mixtures), but not for outdoor use
- For fixed installation under medium mechanical load conditions, and applications with occasional flexing at free, non-continuously recurring movement without tensile load or compulsory guidance
- Note: for the use of AWM (Appliance Wiring Material) cables in industrial machinery (USA) according to NFPA 79: please see the catalogue appendix table T29
Product features
- Flame-retardant according to IEC 60332-1-2
and UL 1581 §1061 Cable Flame Test - Oil-resistant according to EN 50363-4-1: TM5
- High degree of screening
low transfer impedance
(max. 250 Ω/km at 30 MHz)
Norm references / Approvals
- UL AWM Style 21098
CSA AWM I A/B II A/B - Multi-standard cables have conductor strands with nominal sizes in mm² or AWG/kcmil. The master size is mentioned in the table below, while the equivalent size of the other system can be found in the Appendix T16 of this catalogue. For this related secondary size the cross-section of the conductor mostly works out to be greater than the
specified nominal value.
Product Make-up
- Fine-wire strand made of bare copper wires
- PVC core insulation
- Cores twisted in layers
- PVC inner sheath, grey
- Tinned-copper braiding
- PVC outer sheath, high oil-resistance, grey (similar to RAL 7001)
Classification ETIM 5
- ETIM 5.0 Class-ID: EC000104
- ETIM 5.0 Class-Description: Control cable
Classification ETIM 6
- ETIM 6.0 Class-ID: EC000104
- ETIM 6.0 Class-Description: Control cable
Core identification code
- Black with white numbers acc. to VDE 0293-334
Conductor stranding
- Fine wire according to VDE 0295,
class 5/IEC 60228 class 5
Minimum bending radius
- Occasional flexing: 20 x outer diameter
- Fixed installation: 6 x outer diameter
Nominal voltage
- HAR U0/U: 300/500 V
- UL/CSA: 600 V
Test voltage
- 4000 V
Protective conductor
- G = with GN-YE protective conductor
- X = without protective conductor
Temperature range
- Occasional flexing: -5°C to +70°C
UL/CSA: -5°C to +90°C - Fixed installation: -40°C to +70°C
UL/CSA: +90°C