Plant engineering Industrial machinery Heating and air-conditioning systems
Machine tools
Mainly used in dry, damp and wet interiors (including water-oil mixtures), but not for outdoor use
For fixed installation under medium mechanical load conditions, and applications with occasional flexing at free, non-continuously recurring movement without tensile load or compulsory guidance
Product features
Flame-retardant according IEC 60332-1-2
Oil-resistant according to EN 50363-4-1: TM5
Norm references / Approvals
EN 50525-2-51
Product Make-up
Fine-wire strand made of bare copper wires
PVC core insulation
Cores twisted in layers
PVC outer sheath, high oil-resistance, grey (similar to RAL 7001)
Classification ETIM 5
ETIM 5.0 Class-ID: EC000104
ETIM 5.0 Class-Description: Control cable
Classification ETIM 6
ETIM 6.0 Class-ID: EC000104
ETIM 6.0 Class-Description: Control cable
Core identification code
Black with white numbers acc. to VDE 0293-334
Conductor stranding
Fine wire according to VDE 0295, class 5/IEC 60228 class 5
Minimum bending radius
Occasional flexing: 12.5 x outer diameter
Fixed installation: 4 x outer diameter
Nominal voltage
U0/U: 300/500 V
Test voltage
2000 V
Protective conductor
G = with GN-YE protective conductor
X = without protective conductor
Temperature range
Occasional flexing: -5°C to +70°C
Fixed installation: -40°C to +70°C
Product Datasheet
Electrica Online Product DatasheetPrepared from the current product description, catalog data and structured technical attributes.