EATON - MOELLER S811+T24V3S S811+T24V3S 168989 EATON ELECTRIC Soft starter, 3p, 240A, Ue 575-690VAC View larger
Images are for illustrative purposes only. Please refer to data sheet for details

S811+T24V3S 168989 EATON ELECTRIC Soft starter, 3p, 240A, Ue 575-690VAC

S811+T24V3S

168989

EATON - MOELLER

1 Pcs.

Soft starter, 3p, 240A, Ue= 575-690VAC Soft starter, Description: With internal bypass contacts, Function: Soft starter for three-phase loads, with control unit and pump algorithm, for 690-V grids, Mains supply voltage (50/60 Hz): ULN= 200 - 690 V AC, Supply voltage: Us= 24 V DC, Control voltage: UC= 24 V DC, Assigned motor rating (Standard connection, In-Line) at 400 V, 50 Hz: P= 132 kW, at 690 V, 50 Hz: P= 200 kW, at 460 V, 60 Hz: P= 200 HP, Rated operational current AC-53: Ie= 240 A, Startup class: CLASS 10 (star-delta replacement), CLASS 20 (heavy starting duty 3 x Ie for 45 s), CLASS 30 (6 x Ie for 30 s), Rated operational voltage: Ue= 200 V, 230 V, 400 V, 480 V, 600 V , 690 V, Connection to SmartWire-DT: no, Frame size: T, Ordering information: Terminal blocks for the terminals are required for frame sizes T, U, and V -> Accessories, Standards: IEC/EN 60947-4-2, UL 508, CSA22.2-14-1995, GB14048

Automation > Soft starter
High Performance Soft Starters

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Delivery programme
Description
With internal bypass contacts
Function
Soft starter for three-phase loads, with control unit and pump algorithm, for 690-V grids
Mains supply voltage (50/60 Hz)
ULN V AC 200 - 690
Supply voltage
Us 24 V DC
Control voltage
UC 24 V DC
Assigned motor rating (Standard connection, In-Line)
at 400 V, 50 Hz
P kW 132
at 690 V, 50 Hz
P kW 200
at 460 V, 60 Hz
P HP 200
Rated operational current
AC-53
Ie A 240
Startup class
CLASS 10 (star-delta replacement)
CLASS 20 (heavy starting duty 3 x Iefor 45 s)
CLASS 30 (6 x Iefor 30 s)
Rated operational voltage
Ue 200 V
230 V
400 V
480 V
600 V
690 V
Connection to SmartWire-DT
no
Frame size
T
Ordering information
Terminal blocks for the terminals are required for frame sizes T, U, and V -> Accessories
Technical data
General
Standards
IEC/EN 60947-4-2
UL 508
CSA22.2-14-1995
GB14048
Approvals
CE
Approvals
UL
CSA
C-Tick
CCC
Climatic proofing
Damp heat, constant, to IEC 60068-2-3
Damp heat, cyclic, to IEC 60068-2-10
Ambient temperature
Operation
ϑ °C -30 - +50
Storage
ϑ °C -50 - +70
Altitude
m 0 - 2000 m, above that each 100 m 0.5% Derating
Mounting position
As required
Degree of protection
Degree of Protection
IP20 (terminals IP00)
Integrated
An IP20 degree of protection can be achieved on all sides by using optional terminal covers SS-IP20-TU.
Protection against direct contact
Finger- and back-of-hand proof
Overvoltage category/pollution degree
II/3
Shock resistance
15 g
Radio interference level (IEC/EN 55011)
A
Static heat dissipation, non-current-dependent
Pvs W 25
Weight
kg 18.6
Main conducting paths
Rated operating voltage
Ue V AC 200 - 690
Supply frequency
fLN Hz 50/60
Rated operational current
Ie A
AC-53
Ie A 240
Assigned motor rating (Standard connection, In-Line)
at 230 V, 50 Hz
P kW 75
at 400 V, 50 Hz
P kW 132
at 500 V, 50 Hz
P kW 160
at 690 V, 50 Hz
P kW 200
at 200 V, 60 Hz
P HP 75
at 230 V, 60 Hz
P HP 75
at 460 V, 60 Hz
P HP 200
at 600 V, 60 Hz
P HP 200
at 690 V, 60 Hz
P HP 250
Assigned motor rating (delta connection)
at 690 V, 60 Hz
P HP 500
Overload cycle to IEC/EN 60947-4-2
AC-53a
240 A: AC-53a: 4.0 - 32: 99 - 3
Internal bypass contacts
Technical data for design verification
Rated operational current for specified heat dissipation
In A 240
Heat dissipation per pole, current-dependent
Pvid W 0
Equipment heat dissipation, current-dependent
Pvid W 25
Static heat dissipation, non-current-dependent
Pvs W 25
Heat dissipation capacity
Pdiss W 0
Operating ambient temperature min.
°C -30
Operating ambient temperature max.
°C 50
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Technical data ETIM 6.0(Show features)(Hide features)
Low-voltage industrial components (EG000017) / Soft starter (EC000640)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Load breakout, motor breakout / Semiconductor motor controller or soft starter ([email protected] [ACO300008])
Rated operation current Ie at 40 °C Tu
A 240
Rated operating voltage Ue
V 200 - 690
Rated power three-phase motor, inline, at 230 V
kW 75
Rated power three-phase motor, inline, at 400 V
kW 132
Rated power three-phase motor, inside delta, at 230 V
kW 132
Rated power three-phase motor, inside delta, at 400 V
kW 200
Internal bypass
Yes
With display
Yes
Torque control
No
Rated surrounding temperature without derating
°C 50
Rated control supply voltage Us at AC 50HZ
V 0 - 0
Rated control supply voltage Us at AC 60HZ
V 0 - 0
Rated control supply voltage Us at DC
V 24 - 24
Voltage type for actuating
DC
Integrated motor overload protection
Yes
Approvals
Product Standards IEC/EN 60947-4-2; UL 508;CE marking
UL File No. E202571
UL Category Control No. NMFT
North America Certification UL listed
Suitable for Branch Circuits, not as BCPD
Max. Voltage Rating 690 Vac
Degree of Protection IP20 with kit
Dimensions
>

ETIM for 168989 Low-voltage industrial controls and switchgear (EC000640)
Feature Name Feature Value
Rated operation current Ie at 40 °C Tu (EF007039) 240 A
Rated operating voltage Ue (EF002418) 200 V
Rated power three-phase motor, inline, at 230 V (EF007053) 75 kW
Rated power three-phase motor, inline, at 400 V (EF007054) 132 kW
Rated power three-phase motor, inside delta, at 230 V (EF007055) 132 kW
Rated power three-phase motor, inside delta, at 400 V (EF007056) 200 kW
Function (EF000030) Single direction
Internal bypass (EF009214) Yes
With display (EF000458) Yes
Torque control (EF009215) No
Rated surrounding temperature without derating (EF007074) 50 °C
Rated control supply voltage AC 50 Hz (EF003978) 0 V
Rated control supply voltage AC 60 Hz (EF003979) 0 V
Rated control supply voltage DC (EF003980) 24 V
Voltage type for actuating (EF008242) DC
Integrated motor overload protection (EF007297) Yes
Release class (EF006668) Adjustable
Degree of protection (IP) (EF005474) IP00

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.