View larger
S811+T24V3S 168989 EATON ELECTRIC Soft starter, 3p, 240A, Ue 575-690VAC
S811+T24V3S
168989
EATON - MOELLER
1 Pcs.
Automation > Soft starter
High Performance Soft Starters
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller soft starter S811+T24V3S is a heavy-duty electronic motor controller designed to provide smooth acceleration and deceleration for three-phase AC motors. Solid-state starters are widely deployed across industrial plants to reduce mechanical wear on drives and prevent severe voltage drops during motor startup.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Mains supply voltage (50/60 Hz): U LN
- Supply voltage: U s
- Control voltage: U C
- at 400 V, 50 Hz: P
- at 690 V, 50 Hz: P
- at 460 V, 60 Hz: P
- AC-53: I e
- Rated operational voltage: U e
- Operation: ϑ
- Storage: ϑ
- Static heat dissipation, non-current-dependent: P vs
- Main conducting paths Rated operating voltage: U e
- Supply frequency: f LN
- Rated operational current: I e
- at 230 V, 50 Hz: P
More info
▲Description | With internal bypass contacts | ||
Function | Soft starter for three-phase loads, with control unit and pump algorithm, for 690-V grids | ||
Mains supply voltage (50/60 Hz) | ULN | V AC | 200 - 690 |
Supply voltage | Us | 24 V DC | |
Control voltage | UC | 24 V DC | |
Assigned motor rating (Standard connection, In-Line) | |||
at 400 V, 50 Hz | P | kW | 132 |
at 690 V, 50 Hz | P | kW | 200 |
at 460 V, 60 Hz | P | HP | 200 |
Rated operational current | |||
AC-53 | Ie | A | 240 |
Startup class | CLASS 10 (star-delta replacement) CLASS 20 (heavy starting duty 3 x Iefor 45 s) CLASS 30 (6 x Iefor 30 s) | ||
Rated operational voltage | Ue | 200 V 230 V 400 V 480 V 600 V 690 V | |
Connection to SmartWire-DT | no | ||
Frame size | T | ||
Ordering information | Terminal blocks for the terminals are required for frame sizes T, U, and V -> Accessories |
| General | |||
Standards | IEC/EN 60947-4-2 UL 508 CSA22.2-14-1995 GB14048 | ||
Approvals | CE | ||
Approvals | UL CSA C-Tick CCC | ||
Climatic proofing | Damp heat, constant, to IEC 60068-2-3 Damp heat, cyclic, to IEC 60068-2-10 | ||
Ambient temperature | |||
Operation | ϑ | °C | -30 - +50 |
Storage | ϑ | °C | -50 - +70 |
Altitude | m | 0 - 2000 m, above that each 100 m 0.5% Derating | |
Mounting position | As required | ||
Degree of protection | |||
Degree of Protection | IP20 (terminals IP00) | ||
Integrated | An IP20 degree of protection can be achieved on all sides by using optional terminal covers SS-IP20-TU. | ||
Protection against direct contact | Finger- and back-of-hand proof | ||
Overvoltage category/pollution degree | II/3 | ||
Shock resistance | 15 g | ||
Radio interference level (IEC/EN 55011) | A | ||
Static heat dissipation, non-current-dependent | Pvs | W | 25 |
Weight | kg | 18.6 | |
| Main conducting paths | |||
Rated operating voltage | Ue | V AC | 200 - 690 |
Supply frequency | fLN | Hz | 50/60 |
Rated operational current | Ie | A | |
AC-53 | Ie | A | 240 |
Assigned motor rating (Standard connection, In-Line) | |||
at 230 V, 50 Hz | P | kW | 75 |
at 400 V, 50 Hz | P | kW | 132 |
at 500 V, 50 Hz | P | kW | 160 |
at 690 V, 50 Hz | P | kW | 200 |
at 200 V, 60 Hz | P | HP | 75 |
at 230 V, 60 Hz | P | HP | 75 |
at 460 V, 60 Hz | P | HP | 200 |
at 600 V, 60 Hz | P | HP | 200 |
at 690 V, 60 Hz | P | HP | 250 |
Assigned motor rating (delta connection) | |||
at 690 V, 60 Hz | P | HP | 500 |
Overload cycle to IEC/EN 60947-4-2 | |||
AC-53a | 240 A: AC-53a: 4.0 - 32: 99 - 3 | ||
Internal bypass contacts | |||
Technical data for design verification | |||
Rated operational current for specified heat dissipation | In | A | 240 |
Heat dissipation per pole, current-dependent | Pvid | W | 0 |
Equipment heat dissipation, current-dependent | Pvid | W | 25 |
Static heat dissipation, non-current-dependent | Pvs | W | 25 |
Heat dissipation capacity | Pdiss | W | 0 |
Operating ambient temperature min. | °C | -30 | |
Operating ambient temperature max. | °C | 50 | |
IEC/EN 61439 design verification | |||
10.2 Strength of materials and parts | |||
10.2.2 Corrosion resistance | Meets the product standard's requirements. | ||
10.2.3.1 Verification of thermal stability of enclosures | Meets the product standard's requirements. | ||
10.2.3.2 Verification of resistance of insulating materials to normal heat | Meets the product standard's requirements. | ||
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects | Meets the product standard's requirements. | ||
10.2.4 Resistance to ultra-violet (UV) radiation | Meets the product standard's requirements. | ||
10.2.5 Lifting | Does not apply, since the entire switchgear needs to be evaluated. | ||
10.2.6 Mechanical impact | Does not apply, since the entire switchgear needs to be evaluated. | ||
10.2.7 Inscriptions | Meets the product standard's requirements. | ||
10.3 Degree of protection of ASSEMBLIES | Does not apply, since the entire switchgear needs to be evaluated. | ||
10.4 Clearances and creepage distances | Meets the product standard's requirements. | ||
10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. | ||
10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. | ||
10.7 Internal electrical circuits and connections | Is the panel builder's responsibility. | ||
10.8 Connections for external conductors | Is the panel builder's responsibility. | ||
10.9 Insulation properties | |||
10.9.2 Power-frequency electric strength | Is the panel builder's responsibility. | ||
10.9.3 Impulse withstand voltage | Is the panel builder's responsibility. | ||
10.9.4 Testing of enclosures made of insulating material | Is the panel builder's responsibility. | ||
10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. | ||
10.11 Short-circuit rating | Is the panel builder's responsibility. The specifications for the switchgear must be observed. | ||
10.12 Electromagnetic compatibility | Is the panel builder's responsibility. The specifications for the switchgear must be observed. | ||
10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. | ||
| Low-voltage industrial components (EG000017) / Soft starter (EC000640) | |||
| Electric engineering, automation, process control engineering / Low-voltage switch technology / Load breakout, motor breakout / Semiconductor motor controller or soft starter ([email protected] [ACO300008]) | |||
Rated operation current Ie at 40 °C Tu | A | 240 | |
Rated operating voltage Ue | V | 200 - 690 | |
Rated power three-phase motor, inline, at 230 V | kW | 75 | |
Rated power three-phase motor, inline, at 400 V | kW | 132 | |
Rated power three-phase motor, inside delta, at 230 V | kW | 132 | |
Rated power three-phase motor, inside delta, at 400 V | kW | 200 | |
Internal bypass | Yes | ||
With display | Yes | ||
Torque control | No | ||
Rated surrounding temperature without derating | °C | 50 | |
Rated control supply voltage Us at AC 50HZ | V | 0 - 0 | |
Rated control supply voltage Us at AC 60HZ | V | 0 - 0 | |
Rated control supply voltage Us at DC | V | 24 - 24 | |
Voltage type for actuating | DC | ||