View larger
1SDA060283R1
060283
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| ABB EcoSolutions | |
|---|---|
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | 93672a72-5bf0-48a7-80c0-afd7f2845497 China |
| Simplified SCIP | 2825306c-67b2-47eb-a061-5bc952fbd8bf Germany |
| 486ce9b5-a46c-423d-b7c2-acc8d1321b5f Denmark | |
| 0fb2be62-8e52-4611-b747-cbbc79319d07 Greece | |
| f773946c-79f7-46ab-ac38-077985bdc5f4 Hungary | |
| fb4884f3-50a1-46fb-b5da-201719d16c37 Germany | |
| e5a776c9-732f-4af2-86a2-5c872655ea8e Norway | |
| c91c022d-8e0e-4562-8884-a77791e511f3 Germany | |
| d447634b-39af-45d4-a86e-9bdba8d7da41 France | |
| cca389ff-9ec4-4c36-a0bf-f646f5ae953e Poland | |
| a0410760-68cd-4640-b2c7-f527d470e24d Spain | |
| db4fdcb1-b571-4ea5-b636-19682e99ba74 Germany | |
| f20d8497-28d9-416d-a8c4-e82759d91ad7 Finland | |
| b1cc034f-40a1-4fc3-94a6-fcd2fb2860f8 Portugal | |
| 9ba226f6-d821-4039-8fa8-9567d3c4c755 Germany | |
| b14dbc96-3a24-4058-8aec-11bcc0e8559b Sweden | |
| 0b7f5bdc-e9c3-4d6f-969e-a46f7e3b9f64 France | |
| 04663a4e-96c6-4c8d-9282-afef8643ffee Netherlands | |
| 1bc1a55f-1abc-49bb-a56a-021d682d714d Poland | |
| 2d93a4f3-fda9-4722-aad7-59bab6be0822 Sweden | |
| a4791fc0-bc65-468a-923f-b408db76d6c8 Poland | |
| 857a531d-cbec-4584-965e-b01aa8bec45d Bulgaria | |
| 7b47158b-ad1d-4008-9757-edd28568a14f Czech Republic | |
| 14a868bd-0026-4761-a055-ed5d5298cdd5 Belgium | |
| Environmental | |
| Environmental Information | 9AKK10103A1058 |
| 9AKK108467A6707 | |
| Ordering | |
| E-Number (Finland) | 3655427 |
| EAN | 8015644627454 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 280 mm |
| Product Net Height | 268 mm |
| Product Net Depth / Length | 103.5 mm |
| Product Net Weight | 12 kg |
| Container Information | |
| Package Level 1 Units | 1 piece |
| Package Level 1 Width | 305 mm |
| Package Level 1 Height | 285 mm |
| Package Level 1 Depth / Length | 370 mm |
| Package Level 1 Gross Weight | 14 kg |
| Package Level 1 EAN | 8015644627454 |
| Additional Information | |
| Product Main Type | SACE Tmax T |
| Product Name | Moulded Case Circuit Breaker |
| Product Type | Automatic Circuit Breaker |
| Suitable For | T6 |
| Suitable for Product Class | Moulded Case Circuit Breakers |
| Version | F |
| Technical | |
| Electrical Durability | 5000 cycle |
| 60 cycles per hour | |
| Mechanical Durability | 20000 cycle |
| 120 cycles per hour | |
| Number of Poles | 4P |
| Power Loss | at Rated Operating Conditions per Pole 32 W |
| Rated Current (In) | 800 A |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 85 kA |
| (230 V AC) 85 kA | |
| (380 V AC) 50 kA | |
| (400 V AC) 50 kA | |
| (415 V AC) 50 kA | |
| (440 V AC) 45 kA | |
| (500 V AC) 35 kA | |
| (690 V AC) 16.5 kA | |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 10 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 85 kA |
| (230 V AC) 85 kA | |
| (380 V AC) 50 kA | |
| (400 V AC) 50 kA | |
| (415 V AC) 50 kA | |
| (440 V AC) 45 kA | |
| (500 V AC) 35 kA | |
| (690 V AC) 22 kA | |
| Rated Uninterrupted Current (Iu) | 800 A |
| Release | PR221DS-LS/I |
| Release Type | EL |
| Short-Circuit Performance Level | S |
| Standards | IEC |
| Sub-type | T6 |
| Terminal Connection Type | Fixed Circuit-Breakers |
| Front | |
| Test Voltage Max (Utest) | 3500 V |
| Certificates and Declarations | |
| Data Sheet, Technical Information | 1SDC210015D0201 |
| Declaration of Conformity - CE | 9AKK106713A5538 |
| EU Data Act Compliance Declaration | 1SDH002560A1001 |
| Instructions and Manuals | 1SDH000511R0001 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code | Q |
| UNSPSC | 39121100 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |