ABB 1SDA071436R1 1SDA071436R1 ABB E1.2N 1000 Ekip Touch LSIG 4p F F View larger
Images are for illustrative purposes only. Please refer to data sheet for details

1SDA071436R1 ABB E1.2N 1000 Ekip Touch LSIG 4p F F

1SDA071436R1

071436

ABB

1 Pcs.

E1.2N 1000 Ekip Touch LSIG 4p F F

Automation > Power circuit-breaker for trafo/generator/installation protection
E1.2

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

ABB EcoSolutions
ABB EcoSolutionsYes
ABB Site Meeting Group Waste To Landfill TargetUL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions9AKK108468A2360
Environmental Product Declaration - EPD9AKK108468A1900
9AKK108468A3028
Extended Product LifetimeLifetime Extension Services are Offered
Recyclability Rate of the Product acc. to EN45555Design for Closing Resource Loops - Standard EN45555 - 76.4 %
Material Compliance
REACH Declaration9AKK108466A1425
RoHS Declaration9AKK108466A1424
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
Toxic Substances Control Act - TSCA9AKK108467A8326
SCIP3401ea23-d1fd-45af-aee2-99be50b5b99c India
Simplified SCIP308be1fb-00a3-44b7-9715-a1402cc96aaf France
53a9b548-8c5c-427d-8e74-84639278681e Greece
9df456e7-3aef-4746-9bba-b63b81bc36df Estonia
0e261c6e-e179-483e-b268-80e322315a11 Bulgaria
b4db28d0-2004-459e-b767-f07654e0e39f Sweden
80e61d89-5aba-4d13-a1f4-b772760abd3b Sweden
fb5a636f-2c6b-4ab7-8d6b-f4c84fbcf1ba France
2fa47747-653c-44f3-a955-8c39ecf00605 Poland
3a8e13db-27ee-424b-aeda-1d40e5c215b2 Germany
72eca682-119d-40b3-aa86-c48224846b8f Germany
2d8aa7d8-f496-4d9f-8bbf-bc4dc4765422 Portugal
7d2bb053-80fe-4908-a1a8-12559583b5fe Belgium
453f810d-cadf-4b64-bcc3-09a63ff69725 Spain
b75fd234-9752-4877-ab19-4b490c0e4ab8 Hungary
0f6b930b-68a4-487c-8aa8-dd426f02fca4 Hungary
60b71161-8600-45e4-9b48-4a7e2bf75726 Poland
52e97b0e-77d9-49a0-a8db-49367fc98cef Netherlands
f9f360e4-4d99-4fd2-b350-ea08c147d81f Poland
3d237607-87ef-4304-9acb-a6658b15ce92 Germany
a243adee-8dcb-490e-b711-0fa14576bbd1 Germany
f86a7a88-0644-4f32-823e-754274e5cae7 Croatia
ba7db598-5a35-431e-b2d4-0953e4631520 Finland
9fee68dd-93fd-4eb1-9dc5-ef853b8d4627 Denmark
28e1ca3a-ceb5-4581-ac65-3c560abcda78 Germany
0c29df83-44f1-464d-bac0-bae5bef63a39 Norway
994516e2-2f50-4046-917b-e0a08c6a689a Belgium
ca17248a-6d94-4d22-ad2a-94697e4348fb Czech Republic
Environmental
Environmental Information9AKK108467A6707
Ordering
Order Code US and CanadaZANQEGBF000A000000XX
EAN8015644752866
Minimum Order Quantity1 piece
Customs Tariff Number85362090
Dimensions
Product Net Width280 mm
Product Net Height296 mm
Product Net Depth / Length183 mm
Product Net Weight16 kg
Container Information
Package Level 1 Unitsbox 1 piece
Package Level 1 Width350 mm
Package Level 1 Height350 mm
Package Level 1 Depth / Length330 mm
Package Level 1 Gross Weight18 kg
Package Level 1 EAN8015644752866
Additional Information
Product Main TypeSACE Emax 2
Product NameAir Circuit Breaker
Product TypeAir Circuit Breaker
VersionF
CAD Dimensional Drawing1SDH001252R0042
Technical
Connecting Capacity1000 mm²
Current TypeAC
Electrical DurabilityUe =< 440 V 8000 cycle
Ue = 500 ... 690 V 8000 cycle
30 cycles per hour
Mechanical Durability20000 cycle
60 cycles per hour
Neutral Pole Current ([%Iu])100 %
Number of Poles4P
Power Loss78 W
Rated Current (In)1000 A
Rated Impulse Withstand Voltage (Uimp)acc. to IEC 60947-2 12 kV
Rated Insulation Voltage (Ui)AC 1000 V
Rated Operational Voltage690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)(220 V AC) 50 kA
(230 V AC) 50 kA
(380 V AC) 50 kA
(400 V AC) 50 kA
(415 V AC) 50 kA
(440 V AC) 50 kA
(500 V AC) 50 kA
(660 V AC) 50 kA
(690 V AC) 50 kA
Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics)100 %
Rated Short-time Withstand Current Low Voltage (Icw)for 1 s 50 kA
for 3 s 30 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(400 V AC) 66 kA
(415 V AC) 66 kA
(440 V AC) 66 kA
(500 V AC) 50 kA
(525 V AC) 50 kA
(690 V AC) 50 kA
Rated Uninterrupted Current (Iu)1000 A
Rated Voltage (Ur)690 V
Recommended Screw DriverM12
ReleaseEkip Touch LSIG
Release TypeEL
Short-Circuit Performance LevelN
StandardsIEC
Sub-typeE1.2
Suitable for IT NetworksYes, 690V
Terminal Connection TypeFront
Terminal TypeBolt
Tightening Torque45 N·m
Certificates and Declarations
ATEX CertificateNo certification needed
CSA CertificateNo certification needed
CSA Certificate (Intrinsic Safe)No certification needed
Data Sheet, Technical Information1SDC200023D0209
Declaration of Conformity - CE9AKK106713A5546
EU Data Act Compliance Declaration1SDH002560A1001
UL CertificateNo certification needed
VDE CertificateNo certification needed
Mechanical Drawings1SDH000999R0101
Wiring Diagram1SDM000091R0001
Instructions and Manuals1SDH000999R0002
Instructions and Manuals (Part 2)1SDH001316R1002
External Classifications and Standards
ETIM 9EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 10EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)4926 >> Air circuit breakers
Object Classification CodeQ
UNSPSC39121615
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)
eClassV11.1 : 27370409

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.