View larger
1SDA068089R1
068089
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2351 |
| Environmental Product Declaration - EPD | 9AKK108469A1857 |
| 9AKK108468A1892 | |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 56.30 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | 745b6d39-8f0d-4ac6-bc4a-6fac086c16e7 Italy |
| Simplified SCIP | 7f5e9447-0def-454a-b273-99aacc9f91d5 Belgium |
| 8035855e-1693-4925-ad10-1a2fc1f3a256 France | |
| 54606708-badf-40e7-9011-e0f4c6a16046 Spain | |
| 9998efdd-c533-42b9-81e8-d4fa12ffa691 Hungary | |
| 413955b3-62ca-480b-8d35-e5577e67ee3c Czech Republic | |
| 335347cb-4e9e-4bc7-8532-bba289754638 Germany | |
| ba53fb9e-96a2-41e8-b402-0a7964dfc568 Croatia | |
| 22e39f6a-9279-4c5b-a636-7c154e35f61c Germany | |
| 39cf5c34-fbf4-4beb-a445-182605e622d0 Germany | |
| 17152744-f5af-47c9-b2ce-0550b01a3247 Sweden | |
| d6c22644-e041-4dc0-9284-9bdf262a4813 Germany | |
| 8ba92875-ee47-497b-ab27-a01edad2efac Norway | |
| 43b7b3bd-24f3-4611-9221-86c1f2ba9ab4 Poland | |
| 60997a29-72e7-4ce1-8e41-9a9f64712aa4 Bulgaria | |
| 59629924-f0dc-4d5a-b876-acc94e10f515 Poland | |
| 55418ea7-cf8f-4608-9e84-811f1f1ba510 Netherlands | |
| 99a74fe6-4915-4af7-8921-3e2e945a1bb2 Sweden | |
| 5f25017d-f803-4c68-aac8-910da62b517e Finland | |
| 16e2623d-fe6a-4948-ace5-a55f7d857999 Hungary | |
| 085dcb90-66a4-47f7-8da1-8aa118aefedb Poland | |
| 6e402778-43cd-48ff-bcb0-b6fc5a332718 Denmark | |
| 2860ea47-b0fe-465b-8951-163d15465168 France | |
| 874de171-f8ed-4993-8e09-fcb6d9e49f8d Greece | |
| 164b1aef-ac46-49fb-8819-90240e0807c0 Portugal | |
| b5d97084-8eb5-47a4-91ef-de174eab3bbf Germany | |
| 2d4b6a55-466b-4086-a813-b650137e5972 Belgium | |
| 4875e291-4f4b-419a-9d7c-ad0d18b5807c Estonia | |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | XT4NE3160BFF000XXX |
| E-Number (Norway) | 4379854 |
| EAN | 8015644019822 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 105 mm |
| Product Net Height | 160 mm |
| Product Net Depth / Length | 82.5 mm |
| Product Net Weight | 2.5 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 145 mm |
| Package Level 1 Height | 210 mm |
| Package Level 1 Depth / Length | 168 mm |
| Package Level 1 Gross Weight | 2.5 kg |
| Package Level 1 EAN | 8015644019822 |
| Additional Information | |
| Circuit Breaker Type to be Associated | Power Distribution |
| Product Main Type | SACE Tmax XT |
| Product Name | Moulded Case Circuit Breaker |
| Product Type | Automatic Circuit Breaker |
| Version | F |
| CAD Dimensional Drawing | 1SDH002230A1003 |
| Technical | |
| Connecting Capacity Main Circuit | Busbar 85..200 mm² |
| Current Type | AC/DC |
| Electrical Durability | 120 cycles per hour |
| 8000 cycle | |
| Mechanical Durability | 240 cycles per hour |
| 25000 cycle | |
| Number of Poles | 3P |
| Opening Time | CB with SOR 30 ms |
| CB with UVR 30 ms | |
| Order Multiple | 1 piece |
| Power Loss | at Rated Operating Conditions per Pole 8.88 W |
| Rated Current (In) | 160 A |
| Rated Frequency (f) | 50 / 60 Hz |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Instantaneous Short-Circuit Current Setting (Ii) | 800…1600 A |
| Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Voltage | 690 V AC |
| 750 V DC | |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 65 kA |
| (230 V AC) 65 kA | |
| (240 V AC) 65 kA | |
| (380 V AC) 36 kA | |
| (415 V AC) 36 kA | |
| (440 V AC) 36 kA | |
| (500 V AC) 30 kA | |
| (525 V AC) 20 kA | |
| (690 V AC) 10 kA | |
| (250 V DC) 2 Poles in Series 36 kA | |
| (500 V DC) 2 Poles in Series 36 kA | |
| (500 V DC) 3 Poles in Series 36 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 65 kA |
| (230 V AC) 65 kA | |
| (240 V AC) 65 kA | |
| (380 V AC) 36 kA | |
| (415 V AC) 36 kA | |
| (440 V AC) 36 kA | |
| (500 V AC) 30 kA | |
| (525 V AC) 20 kA | |
| (690 V AC) 10 kA | |
| (250 V DC) 2 Poles in Series 36 kA | |
| (500 V DC) 2 Poles in Series 36 kA | |
| (500 V DC) 3 Poles in Series 36 kA | |
| Rated Uninterrupted Current (Iu) | 160 A |
| Rated Voltage (Ur) | 690 V |
| Recommended Screw Driver | Main Circuit M8 |
| Release | TMA |
| Release Type | TM |
| Setting Range | 112...160 A |
| Short-Circuit Performance Level | N |
| Standards | IEC60947-2 |
| Sub-type | XT4 |
| Terminal Connection Type | Front |
| Terminal Type | Bolt |
| Tightening Torque | 8 N·m |
| Certificates and Declarations | |
| ATEX Certificate | No certification needed |
| Data Sheet, Technical Information | 1SDC210100D0206 |
| 1SDC210099D0206 | |
| Declaration of Conformity - CE | 9AKK106713A5529 |
| GL Certificate | 1SDL000163R0095 |
| LR Certificate | 1SDL000163R0100 |
| UL Certificate | No certification needed |
| VDE Certificate | No certification needed |
| Dimension Diagram | 1SDH000722R0100 |
| Mechanical Drawings | 1SDH000722R0100 |
| Wiring Diagram | 1SDM000068R0001 |
| Instructions and Manuals | 1SDH000722R0001 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code | Q |
| UNSPSC | 39120000 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |