EATON - MOELLER XV-303-70-CE0-A00-1C XV-303-70-CE0-A00-1C 179656 Y7-179656 EATON ELECTRIC Control panel with PLC as SWD coordinator, 24 VDC, 7 In.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

XV-303-70-CE0-A00-1C 179656 Y7-179656 EATON ELECTRIC Control panel with PLC as SWD coordinator, 24 VDC, 7 In..

XV-303-70-CE0-A00-1C

179656

Y7-179656

EATON - MOELLER

1 Pcs.

Control panel with PLC as SWD coordinator, 24 VDC, 7 Inches PCT-Display, 1024x600 pixels, 1xEthernet, 1xRS232, 1xRS485, 1xCAN, 1xSWD,1xSD card slot XV-303-70-CE0-A00-1C

Automation > Graphic panel
HMI Touch Terminals

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

General specifications

Product Name
Eaton XV-303 Touch panel
Catalog Number
179656
Model Code
XV-303-70-CE0-A00-1C
EAN
7640130098701
Product Length/Depth
196 mm
Product Height
51 mm
Product Width
135 mm
Product Weight
0.84 kg
Certifications
EN 50178
UL 61010-2-201
CE
DNV GL
IEC/EN 61131-2
CUL
EMC according to 2014/30/EU
UL
UL File No.: E205091
Certified by UL for use in Canada

Features & Functions

Enclosure material
Insulated material
Features
USB device
RS232
Slot for SD card
Target and web visualization
Integrated Runtime visualization software license
Fanless CPU and system cooling, natural convection-based passive cooling
USB Host
Overload proof
RS485
Operating System Windows Embedded Compact 7 pro
Portrait format
Ethernet interface
CAN
Fitted with:
1 x USB device (built-in interface)
1 x CANopen®/easyNet (built-in interfaces)
1 x USB host 2.0 (built-in interface)
2 x Ethernet 10/100 Mbps (built-in interface)
1 x RS485 (built-in interface)
1 x SmartWire-DT (built-in interface)
SW interfaces
Message indication
Message system (incl. buffer and confirmation)
Recipes
Printer output
1 x RS232 (built-in interface)
Color display
Functions
Process value representation (output) possible
Process default value (input) possible
SmartWire-DT coordination
Additional software components, loadable

General

Battery runtime
Back-up of real-time clock: BR 2330, non-replaceable (soldered)
Degree of protection
IP20, rear (according to EN 60529-1)
NEMA 12
NEMA 4X
Degree of protection (front side)
NEMA 12
IP65
Fuse type
Built-in fuse (not accessible)
Lifespan
50,000 h (Service life of back-lighting)
Model
Plastic enclosure and glass panel in plastic frame
Mounting method
Flush mounting - Clearance: Width x Height x Depth ≥ 30 mm (1.18")
Flush mounting - Inclination from vertical: ±45° (if using natural convection)
Flush mounting
Potential isolation
Supply voltage UAUX: no
Between UPow and 15 V SmartWire-DT supply voltage: no
Power supply: no
Protection against polarity reversal
Yes, for supply voltage (Siemens MPI optional)
Yes
Product category
SmartWire-DT coordinators
Repetition rate
1 s
Residual ripple
≤ 5 % (input voltage)
RoHs conformity
Yes
Short-circuit protection
No, external fuse FAZ Z3, Supply voltage UAux
Yes, Short-circuit rating, SmartWire-DT supply voltage
Software
XSOFT-CODESYS, Visualization software, Engineering
XSOFT-CODESYS-2, PLC-Programming software, Engineering
XSOFT-CODESYS-3, PLC-Programming software, Engineering
GALILEO, Visualization software, Engineering
Terminal capacity
0.25 - 1.5 mm², flexible with ferrule
24 - 16 AWG, solid or stranded
0.2 - 1.5 mm², solid
Type
Control panel with PLC as a SmartWire-DT coordinator and 2nd Ethernet port
Voltage type
DC

Ambient conditions, mechanical

Shock resistance
15 g, 11 ms, Mechanical
Vibration resistance
60 - 150 Hz, ± 2 g
5 - 9 Hz, ± 3.5 mm
9 - 60 Hz, ± 0.15 mm

Climatic environmental conditions

Air pressure
795 - 1080 hPa (operation)
Ambient operating temperature - min
0 °C
Ambient operating temperature - max
50 °C
Ambient storage temperature - min
-20 °C
Ambient storage temperature - max
60 °C
Climatic proofing
Damp heat, constant, to IEC 60068-2-3
Dry heat to IEC 60068-2-2
Cold to EN 60068-2-1
Environmental conditions
Condensation: Non-condensing
Operating temperature - min
0 °C
Operating temperature - max
50 °C
Relative humidity
10 - 95 % (non-condensing)

Electro magnetic compatibility

Emitted interference
According to IEC/EN 61000-6-4
Interference immunity
According to EN 61000-6-2
Voltage dips
5 ms from undervoltage (19.2 V DC)
≤ 10 ms, Bridging voltage dips
≤ 10 ms from rated voltage (24 V DC)

Electrical rating

Inrush current
12.5 A (for 6 ms)
Permissible voltage
35 V DC (for a duration of < 100 ms)
18.0 - 31.2 V DC, absolute with ripple
18 - 31.2 V DC, battery powered (rated operating voltage -25 %/+30 %)
19.2 - 30 V DC, effective (rated operating voltage -20 %/+25 %)
Power consumption
14 W typ.
Max. 14.4 W
11.9 W
Rated control supply voltage
24 V DC (UAUX, -15 %/+20 %)
24 V DC (UPOW, -15 %/+20 %)
Rated operational current (Ie)
0.7 A
Rated operational voltage
Typically UAUX -0.2 V (for 24 V DC slaves)
14.5 V (± 3 % - SmartWire-DT)
24 V DC (power-supply - safety extra low voltage)
Supply current
0.7 A, Imax, SmartWire-DT supply
If SmartWire-DT modules with a total power consumption > 0.7 A are connected, a power feeder module EU5C-SWD-PF2 has to be used; SmartWire-DT supply
3 A, Imax, Supply voltage UAux
If contactors with a total power consumption > 3 A are connected, a power feeder module EU5C-SWD-PF1/2 has to be used, Supply voltage UAux
Supply voltage at AC, 50 Hz - min
0 VAC
Supply voltage at AC, 50 Hz - max
0 VAC
Supply voltage at DC - min
19.2 VDC
Supply voltage at DC - max
30 VDC

Communication

Addressing
Address set automatically
Communication interface
SmartWire-DT master
Connection
SmartWire-DT blade terminal SWD4-8MF2
Connection to SmartWire-DT
Yes
Connection type
Push in terminals, Supply voltage
SWD: Plug, 8-pole
Data transfer rate
125 kBit/s, SmartWire-DT
250 kBit/s, SmartWire-DT
Interfaces
10/100 Mbps Ethernet connection
USB 2.0 device (not galvanically isolated)
CAN (not galvanically isolated, 9-pin SUB-D plug, UNC)
RS232 (not galvanically isolated, 9-pin SUB-D plug, UNC)
RS485 (not galvanically isolated, 9-pin SUB-D plug, UNC)
USB 2.0 host (not galvanically isolated)
LED indicator
Status indication of SmartWire-DT network: Configurable green or red LED
Status indication of SmartWire-DT master: Green and red LEDs
Status indication of Supply voltage: LED
Number of slots
1 (for SD-Card)
Number of SmartWire-DT slaves
99
Protocol
TCP/IP
Other bus systems
EtherNet/IP
CAN
MODBUS
EtherCAT
Station
SmartWire-DT master, SmartWire-DT network

Display

Display contrast ratio
850:1
Display lighting
LED
Dimmable via software
Display size
153.6 x 90.0 mm
16:9
Display type
Anti-glare tempered glass in plastic bezel
TFT
Color display, TFT, anti-glare
Luminance intensity
400 cd/m²
Number of colors of the display
16777216
Resolution
Screen size (diagonal)
7 in
Touch technology
Projected Capacitive Touch (PCT)
Capacitive multitouch
Multi-touch touch panel touch sensor

System

Backup time
10 years, typ. (time at zero voltage)
Memory
DRAM: 512 MByte RAM
Flash: 1 GByte SLC
SD card, Type: SDSC, SDHC (external memory)
NVRAM: 128kByte Retain
Memory capacity
512,000 kByte
Operating system
Windows Embedded Compact 7 Pro
Processor
ARM Cortex-A9 800 MHz

Design verification

Equipment heat dissipation, current-dependent Pvid
14.4 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
0 A
Static heat dissipation, non-current-dependent Pvs
14.4 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Please enquire
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Meets the product standard's requirements.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.