EATON - MOELLER XV-102-H3-70TWRL-10 XV-102-H3-70TWRL-10 171162 Y7-171162 EATON ELECTRIC Control tableau, 24 VDC, human-machine interface, 7 inch.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

XV-102-H3-70TWRL-10 171162 Y7-171162 EATON ELECTRIC Control tableau, 24 VDC, human-machine interface, 7 inch..

XV-102-H3-70TWRL-10

171162

Y7-171162

EATON - MOELLER

1 Pcs.

Control tableau, 24 VDC, human-machine interface, 7 inch, Ethernet, USB, RS232, CE50C XV-102-H3-70TWRL-10 User interface, XV-102, Product range: XV100 7z, Function: HMI, Common features of the model series: Ethernet interface, USB device, Slot for SD card, UL508, cUL approvals, Display - Type: Color display, TFT, Touch-technology: Resistive-Touch, Number of colors: 64 k Colors, Resolution: WVGA, 800 x 480 Pixel, Portrait format: yes, Screen diagonal: 7 Inch, Insulating enclosure and front plate, Operating system: Windows CE 5.0 (license incl.), PLC-license: no PLC function possible, License certificates for onboard interfaces: Can be expanded as required, see Accessories -> License product certificates , built-in interfaces: 1 x Ethernet 10/100 Mbps, 1 x USB device, 1 x RS232, 1 x USB host 2.0, Front type: Standard front with standard membrane (fully enclosed), Utilization: Flush mounting, Slots: for SD card: 1, Memory card automation: Optionally with SD card -> article no. 139807, Pluggable communication cards (optional): no, Heat dissipation: 9.5 W, Degree of protection (IEC/EN 60529, EN50178, VBG 4): IP65 (at front), IP20 (at rear)

Automation > Graphic panel
HMI Touch Terminals

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

General specifications

Product Name
Eaton XV-102 Touch panel
Catalog Number
171162
Model Code
XV-102-H3-70TWRL-10
EAN
7640130097995
Product Length/Depth
210 mm
Product Height
38 mm
Product Width
135 mm
Product Weight
0.62 kg
Certifications
EN 60950
UL 60950
UL Category Control No.: NWGQ2
UL report applies to both US and Canada
IEC/EN 61000-6-2
CSA-C22.2 No. 60950-1
IEC/EN 61000-6-4
IEC/EN 61131-2
UL 60950-01
CE
CSA Class No.: NWGQ8
CUL508
UL File No.: E208621
Certified by UL for use in Canada
EN 50178
UL Recognized
EAC

Features & Functions

Enclosure material
Plastic
Features
Portrait format
Ethernet interface
UL508, cUL approvals
USB device
Slot for SD card
Fitted with:
1 x RS232 (built-in interface)
Numeric keyboard
Message system (incl. buffer and confirmation)
Recipes
Printer output
Color display
Message indication
1 x USB host 2.0 (built-in interface)
Alpha numeric keyboard
1 x Ethernet 10/100 Mbps (built-in interfaces)
SW interfaces
1 x USB device (built-in interface)
Functions
Process value representation (output) possible
HMI
Process default value (input) possible
Additional software components, loadable

General

Battery runtime
Back-up of real-time clock: CR 2032 (190 mA/h), zero maintenance (soldered)
Conditions of acceptability
The following end-product enclosures are required: Fire
The unit must be supplied via a SELV source.
The provided Ethernet Connection is only allowed to connect to inhouse networks.
UL/CSA
The investigated Pollution Degree is: 2
Degree of protection
IP65
IP20, rear
Degree of protection (front side)
NEMA 4X
IP65
Fuse type
Built-in fuse (not accessible)
Lifespan
40,000 h (Service life of back-lighting)
Model
Insulating enclosure and front plate
Mounting method
Flush mounting
Flush mounting - Clearance: Width x Height x Depth ≥ 30 mm (1.18")
Flush mounting - Inclination from vertical: ±45° (if using natural convection)
Product category
XV-100
RoHs conformity
Yes
Software
GALILEO, Visualization software, Engineering
Voltage type
DC

Ambient conditions, mechanical

Shock resistance
Mechanical, According to IEC/EN 60068-2-27
Vibration resistance
According to IEC/EN 60068-2-6

Climatic environmental conditions

Air pressure
795 - 1080 hPa (operation)
Ambient operating temperature - min
0 °C
Ambient operating temperature - max
50 °C
Ambient storage temperature - min
-20 °C
Ambient storage temperature - max
60 °C
Operating temperature - min
0 °C
Operating temperature - max
50 °C
Relative humidity
10 - 95 % (non-condensing)

Electro magnetic compatibility

Voltage dips
≤ 10 ms from rated voltage (24 V DC)
5 ms from undervoltage (19.2 V DC)

Electrical rating

Permissible voltage
35 V DC (for a duration of < 100 ms)
18.0 - 31.2 V DC, absolute with ripple
19.2 - 30 V DC, effective (rated operating voltage -20 %/+25 %)
18 - 31.2 V DC, battery powered (rated operating voltage -25 %/+30 %)
Power consumption
Max. 10 W
7 W
Rated control supply voltage
24 V DC (UAUX, -20 %/+25 %)
Rated operational voltage
24 V DC (power-supply - safety extra low voltage)
Supply voltage at AC, 50 Hz - min
0 VAC
Supply voltage at AC, 50 Hz - max
0 VAC
Supply voltage at DC - min
20.4 VDC
Supply voltage at DC - max
28.8 VDC

Communication

Interfaces
Ethernet (100Base-TX/10Base-T)
USB 2.0 device (not galvanically isolated)
USB 2.0 host (1.5 - 12 Mbit/s, not galvanically isolated)
RS232 (not galvanically isolated, 9-pin SUB-D plug, UNC)
Number of slots
1 (for SD-Card)
Protocol
MODBUS
EtherNet/IP
Other bus systems

Display

Display contrast ratio
300:1
Display lighting
LED
Dimmable via software
Display size
152 x 91 mm
Display type
Color display, TFT
TFT
Standard front with standard membrane (fully enclosed)
Luminance intensity
250 cd/m²
Number of colors of the display
65536
Screen size (diagonal)
7 in
Touch technology
Resistive touch
Touch sensor (glass with foil), Resistive touch protective screen

Input/Output

Resolution

Safety

Explosion safety category for dust
ATEX dust-ex-protection, in relation to CE
ATEX dust-ex-protection, II 3D Ex II T70°C IP5x: Zone 22, Category 3D
Explosion safety category for gas
Explosion protection according to EN 61241-1
Explosion protection according to EN 60079-0
Explosion protection according to EN 13463_x
Potential isolation
Power supply: no
Protection against polarity reversal
Yes, for supply voltage (Siemens MPI optional)
Yes

System

Backup time
10 years, typ. (time at zero voltage)
Memory
64 MByte internal DRAM (OS, Program and data memory)
SD Memory Card Slot: SDA Specification 1.00 (External)
128 MByte internal NAND-Flash (can be used for data backup)
Memory capacity
64,000 kByte
Operating system
Windows CE 5.0 (license included)
Processor
RISC CPU, 32 Bit, 400 MHz

Design verification

Equipment heat dissipation, current-dependent Pvid
9.5 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
0 A
Static heat dissipation, non-current-dependent Pvs
9.5 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Please enquire
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Meets the product standard's requirements.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

ETIM for 171162 PLC's (EC001412)
Feature Name Feature Value
Supply voltage AC 50 Hz (EF007532) 0 V
Supply voltage AC 60 Hz (EF007533) 0 V
Supply voltage DC (EF007534) 20.4 V
Voltage type (supply voltage) (EF002991) DC
Power consumption (EF000346) 10 W
Number of HW-interfaces industrial Ethernet (EF003020) 1
Number of interfaces PROFINET (EF006932) 0
Number of HW-interfaces RS-232 (EF003021) 1
Number of HW-interfaces RS-422 (EF003022) 0
Number of HW-interfaces RS-485 (EF003023) 0
Number of HW-interfaces serial TTY (EF003024) 0
Number of HW-interfaces USB (EF003025) 1
Number of HW-interfaces parallel (EF003026) 0
Number of HW-interfaces wireless (EF006933) 0
Number of HW-interfaces other (EF003027) 0
With SW interfaces (EF003121) Yes
Supporting protocol for EtherCAT (EF017564) No
Supporting protocol for TCP/IP (EF003050) No
Supporting protocol for PROFIBUS (EF003052) No
Supporting protocol for CAN (EF003053) No
Supporting protocol for INTERBUS (EF003054) No
Supporting protocol for ASI (EF003051) No
Supporting protocol for KNX (EF003055) No
Supporting protocol for Modbus (EF003057) Yes
Supporting protocol for Data-Highway (EF003058) No
Supporting protocol for DeviceNet (EF003059) No
Supporting protocol for SUCONET (EF003060) No
Supporting protocol for LON (EF003017) No
Supporting protocol for PROFINET IO (EF007525) No
Supporting protocol for PROFINET CBA (EF007524) No
Supporting protocol for SERCOS (EF006657) No
Supporting protocol for Foundation Fieldbus (EF007522) No
Supporting protocol for EtherNet/IP (EF007521) Yes
Supporting protocol for AS-Interface Safety at Work (EF007519) No
Supporting protocol for DeviceNet Safety (EF007520) No
Supporting protocol for INTERBUS-Safety (EF006662) No
Supporting protocol for PROFIsafe (EF007526) No
Supporting protocol for SafetyBUS p (EF007527) No
Supporting protocol for other bus systems (EF003062) Yes
Radio standard Bluetooth (EF007178) No
Radio standard WLAN 802.11 (EF007179) No
Radio standard GPRS (EF008523) No
Radio standard GSM (EF008524) No
Radio standard UMTS (EF008525) No
IO link master (EF007298) No
Type of display (EF008244) TFT
Colour display (EF003097) Yes
Number of colours of the display (EF003098) 65536
Number of grey-scales/blue-scales of display (EF008515) 0
Screen diagonal (EF002032) 7 inch
Number of pixels, horizontal (EF003099) 800
Number of pixels, vertical (EF003100) 480
Useful project memory/user memory (EF003108) 64000 kByte
With numeric keyboard (EF003105) Yes
With alpha numeric keyboard (EF003106) Yes
Number of function buttons, programmable (EF003103) 0
Number of buttons with LED (EF009259) 0
Number of system buttons (EF009260) 1
Touch technology (EF010884) Resistive touch
With message indication (EF003109) Yes
With message system (incl. buffer and confirmation) (EF003110) Yes
Process value representation (output) possible (EF003111) Yes
Process default value (input) possible (EF003112) Yes
With recipes (EF003113) Yes
Number of password levels (EF003114) 200
With printer output (EF003115) Yes
Number of online languages (EF003116) 100
Additional software components, loadable (EF003117) Yes
Degree of protection (IP), front side (EF003118) IP65
Degree of protection (NEMA), front side (EF011961) 4X
Certified for UL hazardous location class I (EF017622) No
Certified for UL hazardous location class II (EF017625) No
Certified for UL hazardous location class III (EF017627) No
Certified for UL hazardous location division 1 (EF017628) No
Certified for UL hazardous location division 2 (EF017629) No
Certified for UL hazardous location group A (acetylene) (EF017632) No
Certified for UL hazardous location group B (hydrogen) (EF017633) No
Certified for UL hazardous location group C (ethylene) (EF017635) No
Certified for UL hazardous location group D (propane) (EF017636) No
Certified for UL hazardous location group E (metal dusts) (EF017637) No
Certified for UL hazardous location group F (carbonaceous dusts) (EF017638) No
Certified for UL hazardous location group G (non-conductive dusts) (EF017639) No
Operating temperature (EF002393) 0 °C
Suitable for rail mounting (EF003972) No
Wall mounting/direct mounting (EF007020) No
Suitable for safety functions (EF001597) No
Width of the front (EF003651) 210 mm
Height of the front (EF003652) 135 mm
Built-in depth (EF000218) 33 mm

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.