View larger
XSDMV-240806-BF 192724 Y7-192724 EATON ELECTRIC Miniature circuit breaker (MCB), 15A, 1p, C-Char, AC
XSDMV-240806-BF
192724
Y7-192724
EATON - MOELLER
1 Pcs.
Automation > Door/operating panel (switchgear cabinet)
Enclosures
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Eaton Moeller miniature circuit breaker automatically interrupts electrical power during an overload or short circuit condition to safeguard downstream wiring and equipment. Such protective devices are standard elements in commercial and industrial electrical distribution panels for branch circuit protection. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated current: I n
- Rated switching capacity acc. to IEC/EN 60947-2: I cu
- Rated voltage according to IEC/EN 60947-2: U n
- Rated switching capacity acc. to IEC/EN 60947-2: I cu
- Rated voltage according to IEC/EN 60898-1: U n
- Rated switching capacity according to IEC/EN 60898-1: I cn
- Rated insulation voltage: U i
- Rated frequency: f
- Electrical: Operations
- Mechanical: Operations
- Model (EF000010): Compartment door
- Version as glazed door (EF006966): No
- Width (EF000008): 595 mm
- Height (EF000040): 197 mm
- Depth (EF000049): 82 mm
- EMC-version (EF001062): No
More info
▲Basic function | Miniature circuit-breakers | ||
Number of poles | 1 pole | ||
Tripping characteristic | C | ||
Application | Switchgear for industrial and advanced commercial applications | ||
Rated current | In | A | 15 |
Rated switching capacity acc. to IEC/EN 60947-2 | Icu | kA | 25 |
Product range | FAZ-T |
| Electrical | |||
Standards | IEC/EN 60947-2 | ||
Rated voltage according to IEC/EN 60947-2 | Un | V AC | 240 |
Rated switching capacity acc. to IEC/EN 60947-2 | Icu | kA | 25 |
Rated service short-circuit breaking capacity according to IEC/EN 60947-2 | Ics | 12,5 kA | |
Max operational voltage according to IEC/EN 60947-2 | V AC | 254 | |
Rated switching capacity according to IEC/EN 60947-2 (max operational voltage) | Icu | kA | 15 |
Rated service short-circuit breaking capacity according to IEC/EN 60947-2 (max operational voltage) | Ics | 7,5 kA | |
Max operational voltage DC according to IEC/EN 60947-2 | V DC | 60/pole | |
Rated voltage according to IEC/EN 60898-1 | Un | V AC | 240 |
Rated switching capacity according to IEC/EN 60898-1 | Icn | kA | 15 |
Rated service short-circuit breaking capacity according to IEC/EN 60898-1 | Ics | 7,5 kA | |
Rated insulation voltage | Ui | V | 440 |
Rated frequency | f | Hz | 50/60 |
Characteristic | B, C, D | ||
Direction of incoming supply | as required | ||
lifespan | |||
Electrical | Operations | ≧ 4000 | |
Mechanical | Operations | ≧ 10000 | |
| Mechanical | |||
Standard front dimension | mm | 45 | |
Enclosure height | mm | 80 | |
Mounting width per pole | mm | 17.5 | |
Mounting | Quick attachment with 3 latch positions for top-hat rail IEC/EN 60715 | ||
Degree of Protection | IP20 | ||
Terminals top and bottom | Twin-purpose terminals | ||
Terminal protection | Finger- and back-of-hand proof according to BGV A3 and ÖVE-EN 6 | ||
Terminal capacities | mm2 | 1 - 25 | |
Tightening torque of fixing screws | N/m | max. 2.4 | |
Thickness of busbar material | mm | 0.8 (exept N 0.5 SU) | |
Mounting position | As required | ||
| Circuit breakers and fuses (EG000020) / Miniature circuit breaker (MCB) (EC000042) | |||
| Electric engineering, automation, process control engineering / Electrical installation, device / Miniature circuit breaker system (MCB) / Miniature circuit breaker (MCB) ([email protected] [AAB905014]) | |||
Release characteristic | C | ||
Number of poles (total) | 1 | ||
Number of protected poles | 1 | ||
Rated current | A | 15 | |
Rated voltage | V | 240 | |
Rated insulation voltage Ui | V | 440 | |
Rated impulse withstand voltage Uimp | kV | 4 | |
Rated short-circuit breaking capacity Icn EN 60898 at 230 V | kA | 15 | |
Rated short-circuit breaking capacity Icn EN 60898 at 400 V | kA | 15 | |
Rated short-circuit breaking capacity Icu IEC 60947-2 at 230 V | kA | 25 | |
Rated short-circuit breaking capacity Icu IEC 60947-2 at 400 V | kA | 25 | |
Voltage type | AC | ||
Frequency | Hz | 50 - 60 | |
Current limiting class | 3 | ||
Suitable for flush-mounted installation | No | ||
Concurrently switching N-neutral | No | ||
Over voltage category | 3 | ||
Pollution degree | 2 | ||
Additional equipment possible | Yes | ||
Width in number of modular spacings | 1 | ||
Built-in depth | mm | 70.5 | |
Degree of protection (IP) | IP20 | ||
Ambient temperature during operating | °C | -25 - 75 | |
Connectable conductor cross section multi-wired | mm² | 1 - 25 | |
Connectable conductor cross section solid-core | mm² | 1 - 25 | |