Product range | Variable frequency drives | ||
Part group reference (e.g. DIL) | DG1 | ||
Rated operational voltage | Ue | 600 V AC, 3-phase | |
Output voltage with Ve | U2 | 600 V AC, 3-phase | |
Mains voltage (50/60Hz) | ULN | V | 500 (-10%) - 600 (+10%) |
Rated operational current | |||
At 150% overload | Ie | A | 13.5 |
At 110% overload | Ie | A | 18 |
Note | Rated operational current for a switching frequency of 1 - 6 kHz and an ambient temperature of +50 °C for a 150% overload and +40 °C for a 110% overload | ||
Assigned motor rating | |||
Note | for normal internally and externally ventilated 4 pole, three-phase asynchronous motors with 1500 rpm-1at 50 Hz or 1800 min-1at 60 Hz | ||
Note | Overload cycle for 60 s every 600 s | ||
Note | at 525 V, 50 Hz | ||
150 % Overload | P | kW | 7.5 |
110 % Overload | P | kW | 11 |
150 % Overload | IM | A | 12.1 |
110 % Overload | IM | A | 17.4 |
Note | at 600 V, 50 Hz | ||
150 % Overload | P | kW | 7.5 |
110 % Overload | P | kW | 11 |
150 % Overload | IM | A | 10.6 |
110 % Overload | IM | A | 15.1 |
Note | at 600 V, 60 Hz | ||
150 % Overload | P | HP | 10 |
110 % Overload | P | HP | 15 |
150 % Overload | IM | A | 11 |
110 % Overload | IM | A | 17 |
Degree of Protection | IP21/NEMA1 | ||
Interface/field bus (built-in) | Modbus RTU Modbus TCP BACnet MS/TP Ethernet IP | ||
Fieldbus connection (optional) | PROFIBUS CANopen® DeviceNet SmartWire-DT | ||
Fitted with | Radio interference suppression filter Additional PCB protection Multi-line graphic display Brake chopper DC link choke | ||
Frame size | FS2 | ||
Connection to SmartWire-DT | yes in conjunction with DXG-NET-SWD SmartWire DT module |
| General | |||
Standards | Specification for general requirements: IEC/EN 61800-2 EMC requirements: IEC/EN 61800-3 Safety requirements: IEC/EN 61800-5 | ||
Certifications | CE, UL, cUL, c-Tick, UkrSEPRO, EAC | ||
Production quality | RoHS, ISO 9001 | ||
Climatic proofing | ρw | % | < 95%, average relative humidity (RH), non-condensing, non-corrosive |
Air quality | 3C2, 3S2 | ||
Ambient temperature | |||
operation (150 % overload) | ϑ | °C | -30 - +50 (max. +60 with 1 % derating per Kelvin temperature rise) |
operation (110 % overload) | ϑ | °C | -30 - +40 (max. +55 mit 1 % Derating pro Kelvin Temperaturerhöhung) |
Storage | ϑ | °C | -40 - +70 |
Overvoltage category | III | ||
Pollution degree | 2 | ||
Radio interference level | |||
Radio interference class (EMC) | C1 (with external filter, for conducted emissions only), C2, C3, depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary. | ||
Environment (EMC) | 1st and 2nd environments as per EN 61800-3 | ||
maximum motor cable length | I | m | C3 ≤ 10 m |
Mechanical shock resistance | g | EN 61800-5-1, EN 60068-2-27 UPS drop test (for weights inside the UPS frame) Storage and transportation: maximum 15 g, 11 ms (inside the packaging) | |
Vibration | EN 61800-5-1, EN 60068-2-6: 5 - 150 Hz Amplitude: 1 mm (peak) at 5 - 15.8 Hz Maximum acceleration amplitude: 1 g at 15.8 – 150 Hz | ||
Mounting position | Vertical | ||
Altitude | m | 0 - 1000 m above sea level Above 1000 m: 1% derating for every 100 m max. 2000 m | |
Degree of Protection | IP21/NEMA1 | ||
Protection against direct contact | BGV A3 (VBG4, finger- and back-of-hand proof) | ||
| Main circuit | |||
Supply | |||
Rated operational voltage | Ue | 600 V AC, 3-phase | |
Mains voltage (50/60Hz) | ULN | V | 500 (-10%) - 600 (+10%) |
Input current (150% overload) | ILN | A | 12.5 |
Input current (110% overload) | ILN | T | 16.7 |
System configuration | TN-S, TN-C, TN-C-S, TT, IT | ||
Supply frequency | fLN | Hz | 50/60 |
Frequency range | fLN | Hz | 45 - 66 |
Mains switch-on frequency | Maximum of one time every 60 seconds | ||
Mains current distortion | THD | % | 36.7 |
Rated conditional short-circuit current | Iq | kA | < 100 |
Power section | |||
Function | Variable frequency drive with internal DC link, DC link choke and IGBT inverter | ||
Overload current (150% overload) | IL | A | 20.25 |
Overload current (110% overload) | IL | A | 19.8 |
max. starting current (High Overload) | IH | % | 200 |
Note about max. starting current | for 2 seconds every 20 seconds | ||
Output voltage with Ve | U2 | 600 V AC, 3-phase | |
Output Frequency | f2 | Hz | 0 - 50/60 (max. 400) |
Switching frequency | fPWM | kHz | 1.5 adjustable 1 - 6 |
Operation Mode | U/f control Speed control with slip compensation sensorless vector control (SLV) Torque regulation | ||
Frequency resolution (setpoint value) | Δf | Hz | 0.01 |
Rated operational current | |||
At 150% overload | Ie | A | 13.5 |
At 110% overload | Ie | A | 18 |
Note | Rated operational current for a switching frequency of 1 - 6 kHz and an ambient temperature of +50 °C for a 150% overload and +40 °C for a 110% overload | ||
Motor current limit | I | A | 0.1 - 2 x IH(CT) |
Power loss | |||
Heat dissipation at rated operational current Ie=150 % | PV | W | 221 |
Heat dissipation at rated operational current Ie=110% | PV | W | 303 |
Efficiency | η | % | 98.2 |
Maximum leakage current to ground (PE) without motor | IPE | mA | 9.8 |
Fan | temperature controlled Tool-less swapping | ||
Internal fan delivery rate | m3/h | 94 | |
Fitted with | Radio interference suppression filter Additional PCB protection Multi-line graphic display Brake chopper DC link choke | ||
Safety function | STO (Safe Torque Off, SIL1, PLc Cat 1) | ||
Frame size | FS2 | ||
Motor feeder | |||
Note | for normal internally and externally ventilated 4 pole, three-phase asynchronous motors with 1500 rpm-1at 50 Hz or 1800 min-1at 60 Hz | ||
Note | Overload cycle for 60 s every 600 s | ||
Note | at 525 V, 50 Hz | ||
150 % Overload | P | kW | 7.5 |
110 % Overload | P | kW | 11 |
Note | at 600 V, 50 Hz | ||
150 % Overload | P | kW | 7.5 |
110 % Overload | P | kW | 11 |
Note | at 600 V, 60 Hz | ||
150 % Overload | P | HP | 10 |
110 % Overload | P | HP | 15 |
maximum permissible cable length | I | m | screened: 150 |
Apparent power | |||
Apparent power at rated operation 600 V | S | kVA | 18.7 |
Braking function | |||
Standard braking torque | max. 30 % MN | ||
DC braking torque | adjustable to 150 % | ||
Braking torque with external braking resistance | Max. 100% of rated operational current Iewith external braking resistor | ||
minimum external braking resistance | Rmin | Ω | 30 |
Switch-on threshold for the braking transistor | UDC | V | Supply voltage UAUX 1050 V DC |
DC braking | % | I/Ie | ≦ 150, adjustable |
| Control section | |||
External control voltage | Uc | V | 24 V DC (max. 250 mA options incl.) |
Reference voltage | Us | V | 10 V DC (max. 10 mA) |
Analog inputs | 2, parameterizable, 0 - 10 V DC, 2 - 10 V DC, -10 - +10 V DC, 0/4 - 20 mA | ||
Analog outputs | 2, parameterizable, 0 - 10 V, 0/4 - 20 mA | ||
Digital inputs | 8, parameterizable, max. 30 V DC | ||
Digital outputs | 1, parameterizable, 24 V DC | ||
Relay outputs | 3, parameterizable, 2 changeover contacts and 1 N/O, 6 A (240 VAC) / 6 A (24 VDC) | ||
Interface/field bus (built-in) | Modbus RTU Modbus TCP BACnet MS/TP Ethernet IP | ||
Expansion slots | 2 | ||
| Assigned switching and protective elements | |||
Power Wiring | |||
Safety device (fuse or miniature circuit-breaker) | |||
IEC (Type B, gG), 150 % | PKZM0-16 | ||
IEC (Type B, gG), 110 % | PKZM0-20 | ||
UL (Class CC or J) | A | 30 | |
Mains contactor | |||
150 % overload (CT/IH, at 50 °C) | DILM7 | ||
110 % overload (VT/IL, at 40 °C) | DILM7 | ||
Main choke | |||
150 % overload (CT/IH, at 50 °C) | Integrated DC link choke, uk = 5% | ||
110 % overload (VT/IL, at 40 °C) | Integrated DC link choke, uk = 5% | ||
Note regarding radio interference suppression filter | Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments | ||
DC link connection | |||
Braking resistance | |||
10 % duty factor (DF) | DX-BR040-3K1 | ||
20 % duty factor (DF) | DX-BR040-5K1 | ||
40 % duty factor (DF) | DX-BR047-9K2 | ||
Notes concerning braking resistances: | PnRm: = Connect every "n" resistors in parallel, then connect the resulting combinations "m" times in series. A total of "n" x "m" resistors will be needed. | ||
Motor feeder | |||
motor choke | |||
150 % overload (CT/IH, at 50 °C) | DX-LM3-016 | ||
110 % overload (VT/IL, at 40 °C) | DX-LM3-035 | ||
Sine filter | |||
150 % overload (CT/IH, at 50 °C) | DX-SIN3-016 | ||
110 % overload (VT/IL, at 40 °C) | DX-SIN3-023 | ||
All-pole sine filter | |||
150 % overload (CT/IH, at 50 °C) | DX-SIN3-024-A | ||
110 % overload (VT/IL, at 40 °C) | DX-SIN3-024-A | ||
| Product Standards | UL508C, CSA-C22.2 No. 274-13; IEC/EN61800-3; IEC/EN61800-5; CE marking | ||
| UL File No. | E134360 | ||
| UL Category Control No. | NMMS, NMMS7 | ||
| CSA File No. | UL report applies to both US and Canada | ||
| North America Certification | UL listed, certified by UL for use in Canada | ||
| Suitable for | Branch circuits | ||
| Max. Voltage Rating | 3~600 V AC IEC: TN-S UL/CSA: 'Y' (Solidly Grounded Wey) | ||
| Degree of Protection | IP21/NEMA1 |
| Low-voltage industrial components (EG000017) / Frequency converter =< 1 kV (EC001857) | |||
| Electric engineering, automation, process control engineering / Electrical drive / Static frequency converter / Static frequency converter = < 1 kV ([email protected] [AKE177014]) | |||
Mains voltage | V | 525 - 600 | |
Mains frequency | 50/60 Hz | ||
Number of phases input | 3 | ||
Number of phases output | 3 | ||
Max. output frequency | Hz | 400 | |
Max. output voltage | V | 575 | |
Nominal output current I2N | A | 13.5 | |
Max. output at quadratic load at rated output voltage | kW | 11 | |
Max. output at linear load at rated output voltage | kW | 15 | |
Relative symmetric net frequency tolerance | % | 10 | |
Relative symmetric net voltage tolerance | % | 10 | |
Number of analogue outputs | |||
Number of analogue inputs | |||
Number of digital outputs | |||
Number of digital inputs | |||
With control unit | Yes | ||
Application in industrial area permitted | Yes | ||
Application in domestic- and commercial area permitted | Yes | ||
Supporting protocol for TCP/IP | Yes | ||
Supporting protocol for PROFIBUS | Yes | ||
Supporting protocol for CAN | Yes | ||
Supporting protocol for INTERBUS | No | ||
Supporting protocol for ASI | No | ||
Supporting protocol for KNX | No | ||
Supporting protocol for MODBUS | Yes | ||
Supporting protocol for Data-Highway | No | ||
Supporting protocol for DeviceNet | Yes | ||
Supporting protocol for SUCONET | No | ||
Supporting protocol for LON | No | ||
Supporting protocol for PROFINET IO | Yes | ||
Supporting protocol for PROFINET CBA | No | ||
Supporting protocol for SERCOS | No | ||
Supporting protocol for Foundation Fieldbus | No | ||
Supporting protocol for EtherNet/IP | No | ||
Supporting protocol for AS-Interface Safety at Work | No | ||
Supporting protocol for DeviceNet Safety | No | ||
Supporting protocol for INTERBUS-Safety | No | ||
Supporting protocol for PROFIsafe | No | ||
Supporting protocol for SafetyBUS p | No | ||
Supporting protocol for BACnet | |||
Supporting protocol for other bus systems | Yes | ||
Number of HW-interfaces industrial Ethernet | 1 | ||
Number of interfaces PROFINET | 1 | ||
Number of HW-interfaces RS-232 | 0 | ||
Number of HW-interfaces RS-422 | 0 | ||
Number of HW-interfaces RS-485 | 1 | ||
Number of HW-interfaces serial TTY | 0 | ||
Number of HW-interfaces USB | 0 | ||
Number of HW-interfaces parallel | 0 | ||
Number of HW-interfaces other | 1 | ||
With optical interface | No | ||
With PC connection | Yes | ||
Integrated breaking resistance | Yes | ||
4-quadrant operation possible | Yes | ||
Type of converter | U converter | ||
Degree of protection (IP) | IP21 | ||
Degree of protection (NEMA) | |||
Height | mm | 419 | |
Width | mm | 169 | |
Depth | mm | 244 | |
| Feature Name | Feature Value |
|---|---|
| Model (EF000010) | Other |
| Version as glazed door (EF006966) | No |
| Version as door for disconnecting switch interlocking (EF006967) | No |
| Width (EF000008) | 595 mm |
| Height (EF000040) | 497 mm |
| Depth (EF000049) | 82 mm |
| EMC-version (EF001062) | No |
| Material (EF002169) | Other |
| Surface finishing (EF006569) | Powder coated |
| Colour (EF000007) | Grey |
| Degree of protection (IP) (EF005474) | IP55 |