This busbar-mounted fuse-switch provides high-capacity current distribution and rapid manual isolation for demanding electrical distribution networks. Engineers specify these units within switchboards to protect critical branch circuits while facilitating safe maintenance procedures. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Version as main switch (EF006981): No
- Version as safety switch (EF006985): No
- Max. rated operation voltage Ue AC (EF007355): 690 V
- Rated permanent current Iu (EF001389): 630 A
- Rated operation power at AC-23, 400 V (EF007027): 0 kW
- Conditioned rated short-circuit current Iq (EF001444): 120 kA
- Rated short-time withstand current lcw (EF007050): 3 kA
- Suitable for fuses (EF006692): NH3
- Number of poles (EF001391): 3
- With error protection (EF007384): No
- Type of electrical connection of main circuit (EF006819): Frame clamp
- Equipped with connectors (EF011696): No
- Suitable for floor mounting (EF007243): No
- Suitable for front mounting (EF007246): No
- Suitable for busbar mounting (EF007259): Yes
- Type of control element (EF006976): Cover grip
More info
▲General specifications
Product specifications
Halogen free
- 400 V (AC-23B)
- 500 V (AC-22B)
- 690 V (AC-21B)
- 440 V (DC-22B)
- 250 V (DC-21B)
IP10 (handle cover open, XNH installed)
IP2XC (contact protection, XNH installed)
Max. 56 mm cable lug width at flange connection
50 mm x 10 mm
120 mm² - 300 mm² at clamp-type terminal
95 mm² - 300 mm² (1x) at box terminal
120 mm² - 240 mm² (2x) at double clamp-type terminal
630 A (AC-21B)
630 A (AC-22B)
630 A (DC-21B)
630 A (AC-23B)
120 kA (500 V)