View larger
XNH3-FCE-A630 183075 Y7-183075 EATON ELECTRIC NH fuse-switch 3p flange connection M10 max. 300 mm² mounting ..
XNH3-FCE-A630
183075
Y7-183075
EATON - MOELLER
1 Pcs.
Connectors > Fuse switch disconnector
Industrial Fuse Bases
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An NH fuse-switch acts as a modular switching and protective device in industrial power distribution, allowing safe manual disconnection of circuits using blade-type fuses. The Eaton Moeller NH fuse-switch handles high fault currents safely in heavy electrical panels.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Version as main switch (EF006981): No
- Version as safety switch (EF006985): No
- Max. rated operation voltage Ue AC (EF007355): 500 V
- Rated permanent current Iu (EF001389): 630 A
- Rated operation power at AC-23, 400 V (EF007027): 0 kW
- Conditioned rated short-circuit current Iq (EF001444): 120 kA
- Rated short-time withstand current lcw (EF007050): 3 kA
- Suitable for fuses (EF006692): NH3
- Number of poles (EF001391): 3
- With error protection (EF007384): Yes
- Type of electrical connection of main circuit (EF006819): Screw connection
- Equipped with connectors (EF011696): Yes
- Suitable for floor mounting (EF007243): Yes
- Suitable for front mounting (EF007246): No
- Suitable for busbar mounting (EF007259): No
- Type of control element (EF006976): Cover grip
More info
▲General specifications
Product specifications
Electronic fuse monitoring and EMC (Electromagnetic compatibility) as of IEC 61000-4-4
Standard sealable
Electronic fuse monitoring and EMC (Electromagnetic compatibility) as of IEC 61000-4-5
Error protection
- Ambient temperature range: -25 °C - 55 °C
- Operating temperature range: -5 °C - 55 °C
- 400 V (AC-23B)
- 500 V (AC-22B)
- 690 V (AC-21B)
- 440 V (DC-22B)
- 250 V (DC-21B)
IP20 (operating status, XNH installed)
IP2XC (contact protection, XNH installed)
IP3X
III (230/400 V)
II (500 V)
DIN rail
1 NO
NH with live handle straps
1 NC
Self-supplied
3 LEDs (F1, F2, F3) red
> 1 kOhm/V
1.5 VA
Test button for relay + LEDs
Bolt diameter at flange connection: M10
50 mm x 10 mm
120 mm² - 300 mm² at clamp-type terminal
95 mm² - 300 mm² (1x) at box terminal
On demand
630 A (AC-22B)
630 A (AC-23B)
630 A (DC-21B)
630 A (DC-22B)
100 kA (690 V)