View larger
XNH2-S400 183065 Y7-183065 EATON ELECTRIC NH fuse-switch 3p flange connection M10 max. 240 mm² busbar 60 mm ..
XNH2-S400
183065
Y7-183065
EATON - MOELLER
1 Pcs.
Connectors > Fuse switch disconnector
Industrial Fuse Bases
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Eaton Moeller NH fuse-switch safely interrupts high current loads and protects electrical distribution circuits from faults using standard NH fuse links. It is commonly deployed on standardized busbar setups within commercial and industrial facilities.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Version as main switch (EF006981): No
- Version as safety switch (EF006985): No
- Max. rated operation voltage Ue AC (EF007355): 690 V
- Rated permanent current Iu (EF001389): 400 A
- Rated operation power at AC-23, 400 V (EF007027): 0 kW
- Conditioned rated short-circuit current Iq (EF001444): 120 kA
- Rated short-time withstand current lcw (EF007050): 3 kA
- Suitable for fuses (EF006692): NH2
- Number of poles (EF001391): 3
- With error protection (EF007384): No
- Type of electrical connection of main circuit (EF006819): Screw connection
- Equipped with connectors (EF011696): No
- Suitable for floor mounting (EF007243): No
- Suitable for front mounting (EF007246): No
- Suitable for busbar mounting (EF007259): Yes
- Type of control element (EF006976): Cover grip
More info
▲General specifications
Product specifications
Standard sealable
- 400 V (AC-23B)
- 500 V (AC-22B)
- 690 V (AC-21B)
- 400 V (AC-23B)
- 500 V (AC-22B)
- 690 V (AC-21B)
IP20 (operating status, XNH installed)
IP2XC (contact protection, XNH installed)
Max. 48 mm cable lug width at flange connection
Bolt diameter at flange connection: M10
120 mm² - 150 mm² (2x) at double clamp-type terminal
25 mm² - 240 mm² at box terminal
120 mm² - 240 mm² at clamp-type terminal
400 A (AC-21B)
400 A (AC-23B)
400 A (DC-22B)
120 kA (500 V)