View larger
XNH1-FCE-A250-BT 183048 Y7-183048 EATON ELECTRIC NH fuse-switch 3p box terminal 35 150 mm² mounting plate el..
XNH1-FCE-A250-BT
183048
Y7-183048
EATON - MOELLER
1 Pcs.
Connectors > Fuse switch disconnector
Industrial Fuse Bases
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Eaton Moeller XNH1-FCE-A250-BT NH fuse-switch functions as a critical protective component in electrical power distribution, allowing operators to safely isolate circuits and interrupt high fault currents. Such devices are widely integrated into industrial control panels, switchboards, and motor control centers to safeguard machinery and infrastructure against overcurrent conditions. Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Version as main switch (EF006981): No
- Version as safety switch (EF006985): No
- Max. rated operation voltage Ue AC (EF007355): 500 V
- Rated permanent current Iu (EF001389): 250 A
- Rated operation power at AC-23, 400 V (EF007027): 0 kW
- Conditioned rated short-circuit current Iq (EF001444): 120 kA
- Rated short-time withstand current lcw (EF007050): 6 kA
- Suitable for fuses (EF006692): NH1
- Number of poles (EF001391): 3
- With error protection (EF007384): Yes
- Type of electrical connection of main circuit (EF006819): Frame clamp
- Equipped with connectors (EF011696): Yes
- Suitable for floor mounting (EF007243): Yes
- Suitable for front mounting (EF007246): No
- Suitable for busbar mounting (EF007259): No
- Type of control element (EF006976): Cover grip
More info
▲General specifications
Product specifications
Halogen free
Standard sealable
Electronic fuse monitoring and EMC (Electromagnetic compatibility) as of IEC 61000-4-4
Error protection
- Ambient temperature range: -25 °C - 55 °C
- Operating temperature range: -5 °C - 55 °C
- 400 V (AC-23B)
- 500 V (AC-22B)
- 690 V (AC-21B)
- 250 V (DC-22B)
- 440 V (DC-21B)
IP10 (handle cover open, XNH installed)
IP20 (operating status, XNH installed)
IP3X
III (230/400 V)
II (500 V)
DIN rail
1.5 VA
Test button for relay + LEDs
1 LED green
Self-supplied
3 LEDs (F1, F2, F3) red
NH with live handle straps
> 1 kOhm/V
1 NO
Max. 37 mm cable lug width at flange connection
30 mm x 10 mm
25 mm² - 150 mm² at box terminal
35 mm² - 150 mm² at box terminal
10 mm² -150 mm² at clamp-type terminal
250 A (AC-21B)
250 A (AC-23B)
250 A (AC-22B)
250 A (DC-22B)
100 kA (690 V)