View larger
XNH1-1-A250-BT 183050 Y7-183050 EATON ELECTRIC NH fuse-switch 1p box terminal 35 150 mm² mounting plate NH1
XNH1-1-A250-BT
183050
Y7-183050
EATON - MOELLER
1 Pcs.
Connectors > Fuse switch disconnector
Industrial Fuse Bases
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
XNH1-1-A250-BT 183050 Y7-183050 EATON ELECTRIC NH fuse-switch 1p box terminal 35 150 mm² mounting plate NH1 acts as an essential circuit protection and load-break switching device for industrial power distribution. These units provide reliable manual isolation and secure fuse housing for heavy-duty electrical networks. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Version as main switch (EF006981): No
- Version as safety switch (EF006985): No
- Max. rated operation voltage Ue AC (EF007355): 690 V
- Rated permanent current Iu (EF001389): 250 A
- Rated operation power at AC-23, 400 V (EF007027): 0 kW
- Conditioned rated short-circuit current Iq (EF001444): 120 kA
- Rated short-time withstand current lcw (EF007050): 6 kA
- Suitable for fuses (EF006692): NH1
- Number of poles (EF001391): 1
- With error protection (EF007384): No
- Type of electrical connection of main circuit (EF006819): Frame clamp
- Equipped with connectors (EF011696): No
- Suitable for floor mounting (EF007243): Yes
- Suitable for front mounting (EF007246): No
- Suitable for busbar mounting (EF007259): No
- Type of control element (EF006976): Cover grip
More info
▲General specifications
Product specifications
Halogen free
- 400 V (AC-23B)
- 500 V (AC-22B)
- 690 V (AC-21B)
- 250 V (DC-22B)
- 440 V (DC-21B)
IP2XC (contact protection, XNH installed)
IP10 (handle cover open, XNH installed)
Max. 37 mm cable lug width at flange connection
Bolt diameter at flange connection: M10
10 mm² -150 mm² at clamp-type terminal
35 mm² - 150 mm² at box terminal
70 mm² - 95 mm² (2x) at double clamp-type terminal
250 A (AC-21B)
250 A (AC-23B)
250 A (DC-21B)
250 A (DC-22B)
100 kA (690 V)