Analog input module; 8 current inputs 0/4 up to 20 mA XN-322-8AI-I Eaton XN-322 Analog input module; 8 current inputs 0/4 up to 20 mA XN-322 analog input slice module in XN300 I/O system, featuring eight 0-20 mA / 4-20 mA current inputs with an accuracy of +/-0.5% of final value, measurement indication in uA, 16Bit (0.3uA resolution), current consumption 5V:55 mA, current consumption 24V:35 mA

Automation > Fieldbus, decentr. periphery - analogue I/O module
Remote I / O Modules XN300

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

An Analog input module 8 current inputs 0/4 up to 20 mA serves as a critical interface for gathering measurement data from multiple field sensors simultaneously within a centralized control architecture. Eaton Moeller engineered this unit, part number XN-322-8AI-I, to bridge physical automation instruments with processing networks seamlessly. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Supply voltage AC 50 Hz (EF007532): 0 V
  • Supply voltage AC 60 Hz (EF007533): 0 V
  • Supply voltage DC (EF007534): 18 V
  • Voltage type (supply voltage) (EF002991): DC
  • Power consumption (EF000346): 0.6 W
  • Input, current (EF003204): Yes
  • Input, voltage (EF003205): No
  • Input, resistor (EF003206): No
  • Input, resistance thermometer (EF003207): No
  • Input, thermocouple (EF003208): No
  • Input signal, configurable (EF003209): Yes
  • Resolution of the analogue inputs (EF003575): 16 Bit
  • Output, current (EF003212): No
  • Output, voltage (EF003213): No
  • Output signal configurable (EF003214): No
  • Resolution of the analogue outputs (EF003577): 0 Bit

More info

▲

General specifications

Product Name
Eaton XN-322 Input module
Catalog Number
179288
Model Code
XN-322-8AI-I
EAN
7640130098381
Product Length/Depth
104.2 mm
Product Height
16.8 mm
Product Width
80.3 mm
Product Weight
0.056 kg
Certifications
UL File No.: E135462
IEC/EN 61000-6-4
CULus
IEC/EN 61131-2
IEC/EN 61000-6-2
CE
Catalog Notes
The max. heat dissipation is specified as the maximum power produced inside the device's housing.

Features & Functions

Current measurement
50 Ω typ., input resistance
0 - 20 mA
4 - 20 mA
Electric connection type
Plug-in connection
Features
Fieldbus connection over separate bus coupler possible
Analog outputs configurable
Input, current
Analog inputs configurable
Input signal, configurable
Fitted with:
Parameterizable Software input filter
1 kHz, third-order low-pass input filter
Value representation
SIGNED16, Current measurement

General

Current consumption
30 mA (typ.), for +24 V, Power supply - Input
50 mA (typ.), for +5 V power supply (internal), Power supply - Input
Degree of protection
IP20
NEMA 1
Limit frequency
1 kHz (third-order low-pass filter)
Mounting method
Rail mounting possible
Number of channels
8, Analog Inputs
Overvoltage category
III
Pollution degree
3
Product category
XN-322 analog input module
Resolution
16 Bit (Analog inputs)
Type
XN300 I/O slice module
Used with
XN-312-…
XN300
Voltage type
DC

Ambient conditions, mechanical

Height of fall (IEC/EN 60068-2-32) - max
1 m
Mounting position
Horizontal
Shock resistance
15 g, Mechanical, Half-sinusoidal shock 11 ms, 18 Impacts
Vibration resistance
5 - 8.4 / 8.4 -150 Hz, 3,5 mm / 1 g

Climatic environmental conditions

Air pressure
795 - 1080 hPa (operation)
Ambient operating temperature - min
0 °C
Ambient operating temperature - max
60 °C
Ambient storage temperature - min
-20 °C
Ambient storage temperature - max
85 °C
Climatic proofing
Dry heat to IEC 60068-2-2
Damp heat, constant, to IEC 60068-2-3
Environmental conditions
Condensation: prevent with appropriate measures
Relative humidity
0 - 95 % (non-condensing)

Electro magnetic compatibility

Air discharge
8 kV
Burst impulse
2 kV, Supply cable
1 kV, Signal cable
Contact discharge
4 kV
Electromagnetic fields
10 V/m at 0.08 - 1.0 GHz (according to IEC EN 61000-4-3)
1 V/m at 2 - 2.7 GHz (according to IEC EN 61000-4-3)
3 V/m at 1.4 - 2 GHz (according to IEC EN 61000-4-3)
Emitted interference
40 dB (at 30 - 230 MHz, Class A, radiated, high frequency)
47 dB (at 230 - 1000 MHz, Class A, radiated, high frequency)
Radiated RFI
10 V
Surge rating
1 kV, Signal cable, unbalanced, EMC
0.5/0.5 kV, Supply cable, balanced/unbalanced), EMC
Voltage dips
Voltage dips: 10 ms/Voltage fluctuations: Yes

Terminal capacities

Terminal capacity
0.2 - 1.5 mm², flexible without ferrule, H07V-K
0.25 - 1.5 mm², with ferrules with plastic collar according to DIN 46228-1 (ferrules crimped gas-tight)
0.25 - 1.5 mm², with ferrules without plastic collar according to DIN 46228-1 (ferrules crimped gas-tight)
0.2 - 1.5 mm², solid, H07V-U
24 - 16 AWG
Gauge pin
A1 (according to IEC/EN 60947-1)
Stripping length (main cable)
10 mm
Insulating material group
I

Electrical rating

Rated operational voltage
160 V (terminations)
Supply voltage at AC, 50 Hz - min
0 VAC
Supply voltage at AC, 50 Hz - max
0 VAC
Supply voltage at DC - min
18 VDC
Supply voltage at DC - max
30 VDC

Communication

Connection type
2 conductors, Current measurement
Push-in spring-cage terminal (plug-in connection), Connection design in TOP direction
Protocol
Other bus systems

Input/Output

Accuracy
± 0.5 % of full scale, Current measurement
Input
8 Analog current inputs (0/4 - 20 mA)
Input current
Max. 100 mA
Load current
Not specified by plug manufacturer
Measured variables
Current
Number of inputs (analog)
8
Number of outputs (analog)
0
Value refresh time/cycle time
Min. 1 / 1 ms (per channel / all channels), Analog Inputs

Safety

Explosion safety category for dust
None
Explosion safety category for gas
None
Potential isolation
Analog inputs: no

Design verification

Equipment heat dissipation, current-dependent Pvid
0 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0.97 W
Rated operational current for specified heat dissipation (In)
0 A
Static heat dissipation, non-current-dependent Pvs
1.485 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Meets the product standard's requirements.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Product Datasheet