View larger
NZM1-XUHIV20KL24AC 284388 Y7-284388 EATON ELECTRIC Undervoltage release, 24VAC +2early N/O
NZM1-XUHIV20KL24AC
284388
Y7-284388
EATON - MOELLER
1 Pcs.
Automation > Under voltage coil
Circuit Breakers NZM
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller NZM1-XUHIV20KL24AC is a dedicated undervoltage release equipped with auxiliary contacts, engineered to monitor line voltage and trip circuit protection equipment instantly upon failure. Technicians install these units to prevent dangerous equipment behavior during unexpected power losses.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz (EF003978): 24 V
- Rated control supply voltage AC 60 Hz (EF003979): 24 V
- Rated control supply voltage DC (EF003980): 0 V
- Voltage type for actuating (EF008242): AC
- Type of electric connection (EF003961): Screw connection
- Number of contacts as normally open contact (EF008256): 2
- Number of contacts as normally closed contact (EF008255): 0
- Number of contacts as change-over contact (EF008257): 0
- Delayed (EF001541): No
- Suitable for power circuit breaker (EF005863): No
- Suitable for off-load switch (EF001543): Yes
- Suitable for motor safety switch (EF005826): No
- Suitable for overload relay (EF001545): No
More info
▲General specifications
UL/CSA
RoHS conform
UL489
CSA (File No. 22086)
IEC60947
UL (File No. E140305)
CSA certified
CSA (Class No. 1437-01)
CE marking
CSA-C22.2 No. 5-09
UL (Category Control Number DIHS)
Product specifications
Auxiliary contact terminals with 3 m of loose connection cables
18 - 14 AWG (1x) for undervoltage releases, off-delayed
18 - 14 AWG (1x) at shunt release
18 - 14 AWG (2x) at shunt release
0.75 mm² - 2.5 mm² (2x) for undervoltage releases, off-delayed with ferrule
18 - 14 AWG (2x) for undervoltage releases, off-delayed
0.75 mm² - 2.5 mm² (1x) for undervoltage releases, off-delayed with ferrule
0.75 mm² - 2.5 mm² (1x) at shunt release with ferrule
1.5 VA (sealing AC)