EATON - MOELLER NZM3-XKA2 NZM3-XKA2 271461 Y7-271461 EATON ELECTRIC Tunnel terminal, 3p, 1 page, max. 240mm², size 3 View larger
Images are for illustrative purposes only. Please refer to data sheet for details

NZM3-XKA2 271461 Y7-271461 EATON ELECTRIC Tunnel terminal, 3p, 1 page, max. 240mm², size 3

NZM3-XKA2

271461

Y7-271461

EATON - MOELLER

1 Pcs.

Tunnel terminal, 3p, 1 page, max. 240mm², size 3 NZM3-XKA2 Eaton Moeller series NZM - Molded Case Circuit Breaker. Tunnel terminal, 3p, 1 page, max. 2x240mm², size 3 Optional accessories for the circuit-breaker series NZM offers a comprehensive portfolio of application options for use world wide. The mounting is always flexible and easy thanks to the modular function groups. Notes: part no. contains parts for a terminal located at top or bottom for 3 or 4 pole switches. A standard with control circuit terminal for 1x0.75-2.5 mm² (18-14 AWG) or 2x0.75-1.5 mm² (18-16 AWG) copper conductors. Fitted outside the switch housing use ferrules with flexible and highly flexible conductors. Max. cross section shown can only be connected when flexible and without ferrules . Cover NZM3(-4)-XKSA must be fitted (included as standard). Can be used for: NZM3(-4), PN3(-4), N(N/O)3(-4)

Automation > Wiring set for power circuit breaker
Circuit Breakers NZM

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

General specifications

Product Name
Eaton Moeller series NZM connection type
Catalog Number
271461
Model Code
NZM3-XKA2
EAN
4015082714611
Product Length/Depth
92.5 mm
Product Height
102 mm
Product Width
137 mm
Product Weight
1.162 kg
Compliances
IEC
UL/CSA
RoHS conform
Certifications
CSA (File No. 22086)
UL (Category Control Number DIHS)
IEC60947
CSA (Class No. 1432-01)
CE marking
UL (File No. E31593)
CSA-C22.2 No. 5-09
UL489
UL listed
CSA certified

Product specifications

Type
Amperage Rating
630 A (IEC), 550 A (UL/CSA)
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
Frame
NZM3
Used with
NZM3, PN3, N(S)3
Suitable for
Copper cable
Three-pole
Number of poles
Three-pole
Model
Other
Terminal capacity (stranded cable)
50 mm² - 240 mm² (2x) at digital input of supply connection
Max. 500 AWG/kcmil (2x)
Max. 500 AWG/kcmil (1x)
50 mm² - 240 mm² (1x) at digital input of supply connection

ETIM for 271461 Low-voltage industrial controls and switchgear (EC002050)
Feature Name Feature Value
Suitable for number of poles (EF001589) 3
Model (EF000010) Other

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.