View larger
PKE-XTUA-12 121729 Y7-121729 EATON ELECTRIC Trip block, 3-12A, networkable, motor protection
PKE-XTUA-12
121729
Y7-121729
EATON - MOELLER
1 Pcs.
Automation > Tripping bloc for power circuit-breaker
Electronic Circuit Breakers
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller PKE-XTUA-12 121729 Y7-121729 trip block serves as a networkable motor protection accessory for industrial automation control panels. This modular device attaches to circuit breakers to monitor electrical loads, offering dependable overload interruption capabilities to protect connected machinery from damage.
Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Type of motor protection (EF008234): Electronic release
- Number of poles (EF001391): 3
- Rated permanent current Iu (EF001389): 12 A
- Overload release current setting (EF002336): 3 A
- Short-circuit release function (EF001413): Delayed
- With ground fault protection function (EF005601): No
- External power supply required (EF003292): No
- Width (EF000008): 45 mm
- Height (EF000040): 64.2 mm
- Depth (EF000049): 41.6 mm
More info
▲General specifications
CSA-C22.2 No. 14-10
VDE 0660
CSA
IEC/EN 60947-4-1
UL
UL Category Control No.: NLRV
IEC/EN 60947
UL File No.: E36332
CSA Class No.: 3211-05
UL 508
CSA File No.: 165628
Features & Functions
Motor protection
Overload release
General
700 (Class 10) AC-4 cycle operation, Main conducting paths
For all combinations with an SWD activation, you need not adhere to the minimum current flow times and minimum cut-out periods.
500 (Class 5) AC-4 cycle operation, Main conducting paths
1000 (Class 20) AC-4 cycle operation, Main conducting paths
900 (Class 15) AC-4 cycle operation, Main conducting paths
Device: IP20
-5 - 40 °C to IEC/EN 60947, VDE 0660
Ambient conditions, mechanical
Climatic environmental conditions
Damp heat, constant, to IEC 60068-2-78
Electrical rating
Short-circuit rating
± 20% tolerance, Trip blocks
Delayed approx. 60 ms, Trip blocks
Switching capacity
Magnet system
Communication
In conjunction with PKE-SWD-32 SmartWire DT PKE module
Yes