View larger
PKZM0-0,4-T 088909 Y7-88909 EATON ELECTRIC Transformer-protective circuit-breaker, 3p, Ir 0.25-0.4A, screw c..
PKZM0-0,4-T
088909
Y7-88909
EATON - MOELLER
1 Pcs.
Automation > Power circuit-breaker for trafo/generator/installation protection
Circuit Breakers PKZ
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller part number PKZM0-0,4-T is a specialized transformer-protective circuit-breaker engineered to safeguard control transformers from overcurrent conditions. These breakers provide reliable thermal and magnetic tripping to prevent transformer burnout in automated control panels. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Manufacturer: Eaton Moeller
- Manufacturer part number: PKZM0-0,4-T
- Catalogue code: 088909
- Catalogue title: PKZM0-0,4-T 088909 Y7-88909 EATON ELECTRIC Transformer-protective circuit-breaker, 3p, Ir 0.25-0.4A, screw c..
- Product description: General specifications Product Name Eaton Moeller® series PKZM0 Transformer-protective circuit-breaker Catalog Number 088909 Model Code PKZM0-0,4-T EAN 4015080889090 Product Length/Depth 76 mm Product Height 93 mm Produc
- Manufacturer summary: Transformer-protective circuit-breaker, 3p, Ir=0.25-0.4A, screw connection Transformer Protective Switch 3 poles Ir=0.25-0.4 A Connection Eaton Moeller® series PKZM0 Transformer-protective circuit-breaker, 3p, Ir=0.25-0.4.
More info
▲General specifications
VDE 0660
Features & Functions
Complete device with protection unit
For the protection of transformers with a high inrush current
General
Also motors with efficiency class IE3
-25 - 55 °C, Operating range
≤ 0.25 %/K, residual error for T > 40°
Climatic environmental conditions
Damp heat, constant, to IEC 60068-2-78
Terminal capacities
2 x (1 - 6) mm², ferrule to DIN 46228
2 x (1 - 6) mm²
1.7 Nm, Screw terminals, Main cable
Electrical rating
Short-circuit rating
50 kA, 600 V High Fault, CB, SCCR (UL/CSA) with 600 A, 600 V High Fault, CB, SCCR (UL/CSA)
Basic device, fixed 20 x Iu, Trip Blocks
6.8 A, Irm, Setting range max.