View larger
PKZM0-0,16-T 088907 Y7-88907 EATON ELECTRIC Transformer-protective circuit-breaker, 3p, Ir 0.1-0.16A, screw ..
PKZM0-0,16-T
088907
Y7-88907
EATON - MOELLER
1 Pcs.
Automation > Power circuit-breaker for trafo/generator/installation protection
Circuit Breakers PKZ
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A transformer-protective circuit-breaker built by Eaton Moeller (part number PKZM0-0,16-T) is engineered to protect electrical transformers and associated circuits from thermal overloads and short circuits. Such components are typically installed within motor control centers and industrial automation cabinets to maintain system integrity.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated permanent current Iu (EF001389): 0.16 A
- Rated voltage (EF003977): 690 V
- Overload release current setting (EF002336): 0.1 A
- Adjustment range undelayed short-circuit release (EF007131): 2.4 A
- Power loss (EF005387): 5.39 W
- Device construction (EF008240): Built-in device fixed built-in technique
- Integrated earth fault protection (EF007296): No
- Type of electrical connection of main circuit (EF006819): Screw connection
- Suitable for DIN rail (top hat rail) mounting (EF007250): Yes
- DIN rail (top hat rail) mounting optional (EF008904): Yes
- With switched-off indicator (EF007006): Yes
- With integrated under voltage release (EF001390): No
- Number of poles (EF001391): 3
- Type of control element (EF006976): Rotating button
- Complete device with protection unit (EF008906): Yes
- Motor drive integrated (EF006697): No
More info
▲General specifications
IEC/EN 60947
Features & Functions
Transformer protection
General
DIN rail (top hat rail) mounting
≤ 0.25 %/K, residual error for T > 40°
-5 - 40 °C to IEC/EN 60947, VDE 0660
Climatic environmental conditions
Damp heat, constant, to IEC 60068-2-78
Terminal capacities
2 x (1 - 6) mm²
1 Nm, Screw terminals, Control circuit cables
Electrical rating
Short-circuit rating
50 kA, 600 V High Fault, CB, SCCR (UL/CSA) with 600 A, 600 V High Fault, CB, SCCR (UL/CSA)
65 kA, 480 Y/277 V, SCCR (UL/CSA)
Accessories required BK25/3-PKZ0-E
50 kA, 600 Y/347 V, SCCR (UL/CSA)
± 20% tolerance, Trip blocks
2.4 A, Irm, Setting range max.