EATON - MOELLER DTZ2,5(*/*)* DTZ2,5(*/*)* 914808 Y7-914808 EATON ELECTRIC Three-phase control/isolation/safety transformer, 2.5kVA, non-s.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

DTZ2,5(*/*)* 914808 Y7-914808 EATON ELECTRIC Three-phase control/isolation/safety transformer, 2.5kVA, non-s..

DTZ2,5(*/*)*

914808

Y7-914808

EATON - MOELLER

1 Pcs.

Three-phase control/isolation/safety transformer, 2.5kVA, non-standard voltage DTZ2,5(*/*)* Eaton Moeller® series DTZ Three-phase control isolating safety transformer, 2.5 kVA, Rated input voltage 50 – 950 ± 5 % V, Rated output voltage 18.5 – 1000 V Three-phase control transformer performed according to VDE 0550, VDE 0550 part1, IEC/EN 61558-2-2, VDE0570 part 2-2 as safety transformer VDE 0570 part 2-6 and as isolating transformer VDE 0570 part 2-4, UL 506, CSA 22.2 No.66, OVE. Rated input voltage selectable of 50-950V +-5%, rated output voltage can be selected from 18.5 - 1000 rated power 2.5 kVA (*/*) = wildcard for rated input voltage / rated output voltage

Automation > Three-phase control transformer
Transformers

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Eaton Moeller DTZ2,5(*/*)* is a three-phase control/isolation/safety transformer deployed in industrial environments to step down voltage while galvanically isolating sensitive circuits from the power source. Isolation and safety transformers are standard requirements in control cabinets to reduce shock hazards and maintain stable secondary power distribution.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Built as safety transformer (EF007235): Yes
  • Built as isolating transformer (EF007238): Yes
  • Built as energy saving transformer (EF007005): No
  • Primary voltage 1 (EF006125): 50 V
  • Primary voltage 2 (EF006126): 50 V
  • Primary voltage 3 (EF006127): 50 V
  • Primary voltage 4 (EF007410): 50 V
  • Primary voltage 5 (EF007411): 50 V
  • Primary voltage 6 (EF007412): 50 V
  • Primary voltage 7 (EF007413): 0 V
  • Primary voltage 8 (EF007414): 0 V
  • Primary voltage 9 (EF007415): 0 V
  • Primary voltage 10 (EF007409): 0 V
  • Secondary voltage 1 (EF007472): 18.5 V
  • Secondary voltage 2 (EF007474): 18.5 V
  • Secondary voltage 3 (EF007475): 18.5 V

More info

▲

General specifications

Product Name
Eaton Moeller® series DTZ Control transformer
Catalog Number
914808
Model Code
DTZ2,5(*/*)*
Product Length/Depth
132 mm
Product Height
299 mm
Product Width
265 mm
Product Weight
29.3 kg
Certifications
UL5085-1
IEC/EN 61558-2-2
CSA-C22.2 No. 66
UL Recognized
UL report applies to both US and Canada
Certified by UL for use in Canada
UL 506
UL 5085-2
UL Category Control No.: XPTQ2, XPTQ8
CE
CSA-C22.2 No. 66.2-06
CSA-C22.2 No. 66.1-06
UL File No.: E167225

General

Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
40 °C
Product category
Three-phase DTZ control transformers
Suitable for
Branch circuits, (UL/CSA)

Electrical rating

Rated power
2500 VA
Relative short-circuit voltage
2.5 %
Short-time rating
5.5 kVA
Voltage rating - max
600 V

Design verification

Equipment heat dissipation, current-dependent Pvid
0 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
0 A
Static heat dissipation, non-current-dependent Pvs
165 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.