EATON - MOELLER XV-152-D8-57TVRC-10 XV-152-D8-57TVRC-10 150600 Y7-150600 EATON ELECTRIC Touch panel, 24 V DC, 5.7z, TFTcolor, ethernet, RS232, R.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

XV-152-D8-57TVRC-10 150600 Y7-150600 EATON ELECTRIC Touch panel, 24 V DC, 5.7z, TFTcolor, ethernet, RS232, R..

XV-152-D8-57TVRC-10

150600

Y7-150600

EATON - MOELLER

1 Pcs.

Touch panel, 24 V DC, 5.7z, TFTcolor, ethernet, RS232, RS485, profibus, PLC XV-152-D8-57TVRC-10 User interface, XV-152, Product range: XV150 5.7z, Function: HMIC-PLC (PLC integrated), Common features of the model series: Ethernet interface, USB device, USB Host, Slot for SD card, UL508, cUL approvals, Display - Type: Color display, TFT, Touch-technology: Resistive-Touch, Number of colors: 64 k Colors, Resolution: VGA, 640 x 480 Pixel, Portrait format: yes, Screen diagonal: 5.7 Inch, Metal enclosure and front plate, Operating system: Windows CE 5.0 (license incl.), PLC-license: PLC license inclusive, License certificates for onboard interfaces: Not required, built-in interfaces: 1 x Ethernet 10/100 Mbps, 1 x RS232, 1 x RS485 , 1 x PROFIBUS/MPI, 1 x USB host 2.0, 1 x USB device, Front type: Standard front with standard membrane (fully enclosed), Utilization: Flush mounting, Slots: for SD card: 1, Memory card automation: Optionally with SD card -> article no. 139807, Pluggable communication cards (optional): no, Touch sensor: Glass with film, Heat dissipation: 9.5 W, Degree of protection (IEC/EN 60529, EN50178, VBG 4): IP65 (at front), IP20 (at rear), Enclosure Type 4X (Indoor use only)

Automation > Graphic panel
HMI Touch Terminals

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Eaton Moeller part XV-152-D8-57TVRC-10 is a Touch panel designed for operator interaction in automated industrial systems. HMIs like this unit provide visual dashboards, process monitoring, and control capabilities, allowing technicians to manage machine states and parameters directly from the floor. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Supply voltage AC 50 Hz (EF007532): 0 V
  • Supply voltage AC 60 Hz (EF007533): 0 V
  • Supply voltage DC (EF007534): 20.4 V
  • Voltage type (supply voltage) (EF002991): DC
  • Power consumption (EF000346): 9.5 W
  • Number of HW-interfaces industrial Ethernet (EF003020): 1
  • Number of interfaces PROFINET (EF006932): 0
  • Number of HW-interfaces RS-232 (EF003021): 1
  • Number of HW-interfaces RS-422 (EF003022): 0
  • Number of HW-interfaces RS-485 (EF003023): 1
  • Number of HW-interfaces serial TTY (EF003024): 0
  • Number of HW-interfaces USB (EF003025): 2
  • Number of HW-interfaces parallel (EF003026): 0
  • Number of HW-interfaces wireless (EF006933): 0
  • Number of HW-interfaces other (EF003027): 1
  • With SW interfaces (EF003121): Yes

More info

▲

General specifications

Product Name
Eaton XV-152 Touch panel
Catalog Number
150600
Model Code
XV-152-D8-57TVRC-10
EAN
7640130097223
Product Length/Depth
212 mm
Product Height
52.5 mm
Product Width
156 mm
Product Weight
1.3 kg
Certifications
UL508
IEC/EN 61241-0 (ATEX 94/9/EG: Zone 22, Category 3D (II 3D Ex tc IIIC T70°C IP6x)
EN 60950
IEC/EN 61000-6-4
UL File No.: E205091
IEC/EN 61241-1 (ATEX 94/9/EG: Zone 22, Category 3D (II 3D Ex tc IIIC T70°C IP6x)
Security:
IEC/EN 61000-6-2
CSA File No.: UL report applies to both US and Canada
IEC/EN 61131-2, CE
UL 508
IEC/EN 61131-2
IEC/EN 60950
CUL508
IEC/EN 61000-6-3
UL 60950
ATEX 94/9/EG: Zone 22, Category 3D (II 3D Ex tc IIIC T70°C IP6x)
UL Category Control No.: NRAQ
DNV GL
CSA Class No.: none
IEC/EN 60079-0 (ATEX 94/9/EG: Zone 22, Category 3D (II 3D Ex tc IIIC T70°C IP6x)
UL
Certified by UL for use in Canada
CULus
EN 50178
EAC

Features & Functions

Enclosure material
Metal, anodized
Features
USB device
UL508, cUL approvals
Slot for SD card
Ethernet interface
USB Host
Fanless CPU and system cooling, natural convection-based passive cooling
Portrait format
Fitted with:
1 x RS232 (built-in interface)
Numeric keyboard
SW interfaces
Color display
Printer output
1 x Ethernet 10/100 Mbps (built-in interfaces)
1 x RS485 (built-in interface)
Alpha numeric keyboard
Message indication
1 x USB device (built-in interface)
1 x PROFIBUS/MPI (built-in interface)
Message system (incl. buffer and confirmation)
1 x USB host 2.0 (built-in interface)
Recipes
Functions
Process value representation (output) possible
Process default value (input) possible
Additional software components, loadable

General

Battery runtime
Back-up of real-time clock: CR 2032 (190 mA/h), zero maintenance (soldered)
Current consumption
0.4 A, continuous current, Power Supply, 24 V DC
Degree of protection
NEMA 4X
IP20, rear
IP20
Degree of protection (front side)
NEMA 4X
IP65
Fuse type
Built-in fuse (not accessible)
Lifespan
40,000 h (Service life of back-lighting)
Model
Metal enclosure and front plate
Mounting method
Flush mounting - Clearance: Width x Height x Depth ≥ 30 mm (1.18")
Flush mounting - Inclination from vertical: ±45° (if using natural convection)
Flush mounting
Product category
HMI-PLC (integrated SPS function)
RoHs conformity
Yes
Software
GALILEO, Visualization software, Engineering
XSOFT-CODESYS-2, Visualization software, Engineering
XSOFT-CODESYS-2, PLC-Programming software, Engineering
XSOFT-CODESYS-3, PLC-Programming software, Engineering
EPAM, Visualization software, Engineering
XSOFT-CODESYS-3, Visualization software, Engineering
Voltage type
DC

Ambient conditions, mechanical

Shock resistance
Mechanical, According to IEC/EN 60068-2-27
Vibration resistance
According to IEC/EN 60068-2-6

Climatic environmental conditions

Air pressure
795 - 1080 hPa (operation)
Ambient operating temperature - min
0 °C
Ambient operating temperature - max
50 °C
Ambient storage temperature - min
-20 °C
Ambient storage temperature - max
60 °C
Operating temperature - min
0 °C
Operating temperature - max
50 °C
Relative humidity
IEC/EN 50178
10 - 95 % (non-condensing)

Electro magnetic compatibility

Voltage dips
5 ms from undervoltage (19.2 V DC)
≤ 10 ms from rated voltage (24 V DC)

Electrical rating

Inrush current
12.5 A (for 6 ms)
Permissible voltage
18 - 31.2 V DC, battery powered (rated operating voltage -25 %/+30 %)
35 V DC (for a duration of < 100 ms)
18.0 - 31.2 V DC, absolute with ripple
19.2 - 30 V DC, effective (rated operating voltage -20 %/+25 %)
Power consumption
9.5 W total
2.5 W (USB Slave to USB Host)
Max. 7 W
7 W
Rated control supply voltage
24 V DC (UAUX, -20 %/+25 %)
24 V DC (UPOW, -20 %/+25 %)
Rated operational voltage
24 V DC (power-supply - safety extra low voltage)
Supply voltage at AC, 50 Hz - min
0 VAC
Supply voltage at AC, 50 Hz - max
0 VAC
Supply voltage at DC - min
20.4 VDC
Supply voltage at DC - max
28.8 VDC

Communication

Interfaces
USB 2.0 device (not galvanically isolated)
Ethernet (100Base-TX/10Base-T)
Number of slots
1 (for SD-Card)
Protocol
MODBUS
PROFIBUS
TCP/IP
Other bus systems
EtherNet/IP

Display

Display contrast ratio
300:1
Display lighting
LED
Dimmable via software
Display size
115 x 86 mm
Display type
TFT
Color display, TFT
Standard front with standard membrane (fully enclosed)
Luminance intensity
250 cd/m²
Number of colors of the display
65536
Screen size (diagonal)
5.7 in
Touch technology
Glass with film touch sensor
Touch sensor (glass with foil), Resistive touch protective screen
Resistive touch

Input/Output

Resolution

Safety

Explosion safety category for dust
ATEX dust-ex-protection, in relation to CE
ATEX dust-ex-protection, II 3D Ex II T70°C IP5x: Zone 22, Category 3D
Potential isolation
UAUX: no
Power supply: no
Protection against polarity reversal
Yes
Yes, for supply voltage (Siemens MPI optional)

System

Backup time
10 years, typ. (time at zero voltage)
Memory
SD Memory Card Slot: SDA Specification 1.00 (External)
64 MByte internal DRAM (OS, Program and data memory)
NVRAM (Retain data): 125 kByte
NAND-Flash (can be used for data backup): approx. 64 MByte available
NOR-Flash: 2 MByte
Memory capacity
64,000 kByte
Operating system
Windows CE 5.0 (license included)
Processor
RISC CPU, 32 Bit, 400 MHz

Design verification

Equipment heat dissipation, current-dependent Pvid
9.5 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
0 A
Static heat dissipation, non-current-dependent Pvs
9.5 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Please enquire
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Meets the product standard's requirements.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Product Datasheet