EATON - MOELLER XV-102-BE-35TQRC-10 XV-102-BE-35TQRC-10 153524 Y7-153524 EATON ELECTRIC Touch panel, 24 V DC, 3.5z, TFTcolor, ethernet, SWDT, PLC View larger
Images are for illustrative purposes only. Please refer to data sheet for details

XV-102-BE-35TQRC-10 153524 Y7-153524 EATON ELECTRIC Touch panel, 24 V DC, 3.5z, TFTcolor, ethernet, SWDT, PLC

XV-102-BE-35TQRC-10

153524

Y7-153524

EATON - MOELLER

1 Pcs.

Touch panel, 24 V DC, 3.5z, TFTcolor, ethernet, SWDT, PLC XV-102-BE-35TQRC-10 Eaton XV-102 Touch panel, 24 V DC, 3.5z, TFTcolor, ethernet, SWDT, PLC User interface, XV-102, Product range: XV100 3.5z, Subrange: SmartWire-DT touch display with integrated controller (HMI PLC), Function: SmartWire-DT coordinator, Description: XV100 touch display with PLC function for flush mounting plates, Coordinator for the SmartWire-DT communications system, Common features of the model series: Ethernet interface, USB device, Slot for SD card, UL508, cUL approvals, Display - Type: Color display, TFT, Touch-technology: Resistive-Touch, Number of colors: 64 k Colors, Resolution: QVGA, 320 x 240 Pixel, Portrait format: yes, Screen diagonal: 3.5 Inch, Insulating enclosure and front plate , Operating system: Windows CE 5.0 (license incl.), PLC-license: PLC license inclusive, License certificates for onboard interfaces: Not required, built-in interfaces: 1 x Ethernet 10/100 Mbps, 1 x USB device, 1 x SmartWire-DT, Front type: Standard front with standard membrane (fully enclosed), Utilization: Flush mounting, Slots: for SD card: 1, Memory card automation: Optionally with SD card -> article no. 139807, Pluggable communication cards (optional): no, Touch sensor: Glass with film, Heat dissipation: 5 W, Connection to SmartWire-DT: yes, Degree of protection (IEC/EN 60529, EN50178, VBG 4): IP65 (at front), IP20 (at rear)

Automation > Graphic panel
HMI Touch Terminals

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

An Eaton Moeller XV-102-BE-35TQRC-10 touch panel, 24 V DC, 3.5z, TFTcolor, ethernet, SWDT, PLC functions as a compact operator interface terminal designed to facilitate machine interaction and basic process control in industrial environments. Such HMI devices are frequently utilized in space-constrained control cabinets to display system parameters, issue commands, and monitor connected automation hardware. Pricing, availability, and lead time are confirmed per enquiry through an RFQ.

  • Supply voltage AC 50 Hz (EF007532): 0 V
  • Supply voltage AC 60 Hz (EF007533): 0 V
  • Supply voltage DC (EF007534): 20.4 V
  • Voltage type (supply voltage) (EF002991): DC
  • Power consumption (EF000346): 2.5 W
  • Number of HW-interfaces industrial Ethernet (EF003020): 1
  • Number of interfaces PROFINET (EF006932): 0
  • Number of HW-interfaces RS-232 (EF003021): 0
  • Number of HW-interfaces RS-422 (EF003022): 0
  • Number of HW-interfaces RS-485 (EF003023): 0
  • Number of HW-interfaces serial TTY (EF003024): 0
  • Number of HW-interfaces USB (EF003025): 1
  • Number of HW-interfaces parallel (EF003026): 0
  • Number of HW-interfaces wireless (EF006933): 0
  • Number of HW-interfaces other (EF003027): 1
  • With SW interfaces (EF003121): Yes

More info

▲

General specifications

Product Name
Eaton XV-102 Touch panel
Catalog Number
153524
Model Code
XV-102-BE-35TQRC-10
EAN
7640130097599
Product Length/Depth
136 mm
Product Height
30 mm
Product Width
100 mm
Product Weight
0.275 kg
Certifications
DNV GL
EN 50178
CSA File No.: UL report applies to both US and Canada
IEC/EN 61131-2, CE
UL
UL508
IEC/EN 61000-6-4
EN 60950
UL Category Control No.: NRAQ
UL File No.: E205091
CUL508
CULus
IEC/EN 61131-2
UL 60950
CSA Class No.: none
Certified by UL for use in Canada
IEC/EN 61000-6-2
EAC

Features & Functions

Enclosure material
Plastic
Features
Fanless CPU and system cooling, natural convection-based passive cooling
UL508, cUL approvals
Target and web visualization
Ethernet interface
USB device
Overload proof
Portrait format
Slot for SD card
Fitted with:
Numeric keyboard
1 x USB device (built-in interface)
Message indication
1 x Ethernet 10/100 Mbps (built-in interfaces)
Alpha numeric keyboard
Color display
1 x SmartWire-DT (built-in interface)
Message system (incl. buffer and confirmation)
Recipes
Printer output
SW interfaces
Functions
Process default value (input) possible
Additional software components, loadable
Process value representation (output) possible
SmartWire-DT coordination

General

Battery runtime
Back-up of real-time clock: CR 2032 (190 mA/h), zero maintenance (soldered)
Degree of protection
IP20
IP20, rear
Degree of protection (front side)
IP65
NEMA 4X
Fuse type
Built-in fuse (not accessible)
Lifespan
40,000 h (Service life of back-lighting)
Model
Insulating enclosure and front plate
Mounting method
Flush mounting - Clearance: Width x Height x Depth ≥ 30 mm (1.18")
Flush mounting - Inclination from vertical: ±45° (if using natural convection)
Flush mounting
Product category
SmartWire-DT coordinators
Repetition rate
1 s
Residual ripple
≤ 5 % (input voltage)
RoHs conformity
Yes
Short-circuit protection
No, external fuse FAZ Z3, Supply voltage UAux
Yes, Short-circuit rating, SmartWire-DT supply voltage
Software
XSOFT-CODESYS-3, PLC-Programming software, Engineering
EPAM, Visualization software, Engineering
GALILEO, Visualization software, Engineering
XSOFT-CODESYS-2, PLC-Programming software, Engineering
XSOFT-CODESYS-3, Visualization software, Engineering
XSOFT-CODESYS-2, Visualization software, Engineering
Terminal capacity
0.25 - 1.5 mm², flexible with ferrule
0.2 - 1.5 mm², solid
24 - 16 AWG, solid or stranded
Type
Coordinator for the SmartWire-DT communications system
Voltage type
DC

Ambient conditions, mechanical

Shock resistance
Mechanical, According to IEC/EN 60068-2-27
Vibration resistance
According to IEC/EN 60068-2-6

Climatic environmental conditions

Air pressure
795 - 1080 hPa (operation)
Ambient operating temperature - min
0 °C
Ambient operating temperature - max
50 °C
Ambient storage temperature - min
-20 °C
Ambient storage temperature - max
60 °C
Operating temperature - min
0 °C
Operating temperature - max
50 °C
Relative humidity
10 - 95 % (non-condensing)

Electro magnetic compatibility

Voltage dips
5 ms from undervoltage (19.2 V DC)
≤ 10 ms, Bridging voltage dips
≤ 10 ms from rated voltage (24 V DC)

Electrical rating

Inrush current
12.5 A (for 6 ms)
Permissible voltage
18 - 31.2 V DC, battery powered (rated operating voltage -25 %/+30 %)
18.0 - 31.2 V DC, absolute with ripple
35 V DC (for a duration of < 100 ms)
19.2 - 30 V DC, effective (rated operating voltage -20 %/+25 %)
Power consumption
2.5 W (USB Slave to USB Host)
9.5 W total
Max. 5 W
5 W
Rated control supply voltage
24 V DC (UAUX, -20 %/+25 %)
24 V DC (UPOW, -20 %/+25 %)
Rated operational current (Ie)
0.7 A
Rated operational voltage
14.5 V (± 3 % - SmartWire-DT)
Typically UAUX -0.2 V (for 24 V DC slaves)
24 V DC (power-supply - safety extra low voltage)
Supply current
3 A, Imax, Supply voltage UAux
If SmartWire-DT modules with a total power consumption > 0.7 A are connected, a power feeder module EU5C-SWD-PF2 has to be used; SmartWire-DT supply
0.7 A, Imax, SmartWire-DT supply
Supply voltage at AC, 50 Hz - min
0 VAC
Supply voltage at AC, 50 Hz - max
0 VAC
Supply voltage at DC - min
20.4 VDC
Supply voltage at DC - max
28.8 VDC

Communication

Addressing
Address set automatically
Communication interface
SmartWire-DT master
Connection
SmartWire-DT blade terminal SWD4-8MF2
Connection to SmartWire-DT
Yes
Connection type
Push in terminals, Supply voltage
SWD: Plug, 8-pole
Data transfer rate
125 kBit/s, SmartWire-DT
250 kBit/s, SmartWire-DT
Interfaces
Ethernet (100Base-TX/10Base-T)
USB 2.0 device (not galvanically isolated)
LED indicator
Status indication of SmartWire-DT network: Configurable green or red LED
Status indication of SmartWire-DT master: Green and red LEDs
Status indication of Supply voltage: LED
Number of slots
1 (for SD-Card)
Number of SmartWire-DT slaves
99
Protocol
Other bus systems
MODBUS
EtherNet/IP
TCP/IP
Station
SmartWire-DT master, SmartWire-DT network

Display

Display contrast ratio
300:1
Display lighting
LED
Dimmable via software
Display size
70 x 53 mm
Display type
Color display, TFT
TFT
Standard front with standard membrane (fully enclosed)
Luminance intensity
250 cd/m²
Number of colors of the display
65536
Screen size (diagonal)
3.5 in
Touch technology
Touch sensor (glass with foil), Resistive touch protective screen
Resistive touch
Glass with film touch sensor

Input/Output

Resolution

Safety

Explosion safety category for dust
ATEX dust-ex-protection, II 3D Ex II T70°C IP5x: Zone 22, Category 3D
ATEX dust-ex-protection, in relation to CE
Explosion safety category for gas
Explosion protection according to EN 61241-1
Explosion protection according to EN 60079-0
Explosion protection according to EN 13463_x
Potential isolation
Supply voltage UAUX: no
Between UPow and 15 V SmartWire-DT supply voltage: no
Power supply: no
Protection against polarity reversal
Yes
Yes, for supply voltage (Siemens MPI optional)

System

Backup time
10 years, typ. (time at zero voltage)
Memory
32 kByte internal NVRAM (retained data)
SD Memory Card Slot: SDA Specification 1.00 (External)
128 MByte internal NAND-Flash (can be used for data backup)
64 MByte internal DRAM (OS, Program and data memory)
Memory capacity
64,000 kByte
Operating system
Windows CE 5.0 (license included)
Processor
RISC CPU, 32 Bit, 400 MHz

Design verification

Equipment heat dissipation, current-dependent Pvid
5 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
0 A
Static heat dissipation, non-current-dependent Pvs
5 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Please enquire
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Meets the product standard's requirements.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.