EATON - MOELLER DILET11-30-A DILET11-30-A 048878 EATON ELECTRIC XTMT6A30S11B DILET 11-30-A multifunction timer View larger
Images are for illustrative purposes only. Please refer to data sheet for details

DILET11-30-A 048878 EATON ELECTRIC XTMT6A30S11B DILET 11-30-A multifunction timer

DILET11-30-A

048878

EATON - MOELLER

1 Pcs.

XTMT6A30S11B DILET 11-30-A multifunction timer Electronic timing relay according to IEC/EN 61812-1, VDE 0435, 45 mm wide, 24-240VAC/DC, time range 1.5-30s, on-delayed, ideal for combination with contactors

Automation > Timer relay
Contactors up to 170A

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Program Delivery
Product range
DILET timing relays
The basic function of
Relay timer
The function
In retarded
Sets the timing function
Number of switching contacts
1
Time Range
1.5 - 30 s
Time Range
1.5 - 30 s
Rated Operating Current
AC-11
230 V
Iand One 3
380 V 400 V 415 V
Iand One 3
AC-15
220 V 230 V 240 V
Iand One 3
Voltage range of
ULN V 24 - 240 VAC, 50/60 Hz
24 - 240 V DC
Wide
mm 45
Terminal of the brand according to EN 50042
General
Standards
The IEC/EN 61812 standard
VDE 0435
Life expectancy, mechanics
AC operated
The operations of x 106 30
DC operated
The operations of x 106 30
Climatic correction
Moist, Constant Heat, IEC 60068-2-78
Moist, cyclic heat, IEC 60068-2-30
Ambient Temperature
Open
°C -20 - +60
Closed
°C - 20 - + 45
Mounting position
As required
Shock Resistance Mechanics (IEC/EN 60068-2-27)
Sinusoidal half shock, 20 ms
g
Make contact
g 4
Degree of protection
Terminals
IP20
Weight
kg 0.09
Capacity terminal
mm2
Solid
mm2 1 x (0.75 - 2.5)
2 x (0.75 - 2.5)
Flexible with cap
mm2 1 x (0.75 - 1.5)
2 x (0.75 - 1.5)
Solid or braided
AWG 1 x (18 - 14)
Contacts
Rated Supported Pulse Voltage
Uimp V AC 6000
Overvoltage category/degree of contamination
III/2
Rated insulation voltage
UI V AC 600
Rated Operating Voltage
Uand V AC 440
Safety insulation according to EN 61140
between coil and auxiliary contacts
V AC 250
between auxiliary contacts
V AC 250
The manufacturing capacity of
Nah, no way
One 48
AC-15 cos φ = 0.3 220 V
One 50
DC-11 L/R 40 ms
x Iand 1.1
Breaking capacity
Nah, no way
One 3
Nah, no way
One 3
DC-11 L/R 40 ms
x Iand 1.1
Rated Operating Current
Iand One
CA--14
440 V
Iand One 3
AC-15
220 V 230 V 240 V
Iand One 3
DC-11
Note
Decision Making and Breaking Conditions for DC13, Time Constant as Indicated
L/R max. 15 ms
One
24 V
Iand One 1.5
L/R max. 50 ms
One 1.2
Conv. Thermal Current
ITh One 6
Solderless Short Circuit Rating
Note
When powered directly from the mains or transformer > 1000 VA
Max. fuse, make contacts
One gG/gL 6
Max. fuse, break contacts
One gG/gL 6
Magnet Systems
Rated Operating Voltage
Uand V
AC
24 - 240
DC
24 - 240
AC Rated Frequency
Hz 47 - 63
The tolerance of AC operated min.
x Uc 0.85
The tolerance of AC operated max.
x Uc 1.1
DC tolerance operated min.
x Uc 0.7
The DC tolerance operated max.
x Uc 1.1
Tension tolerance
x Uc
Voltage pick-up
x Us
Min. AC voltage pick-up, operated
x Uc 0.85
AC voltage pick-up operated, max.
x Uc 1.1
DC voltage operated pick-up, min.
x Uc 0.7
Max. pick-up, DC operated
x Uc 1.1
Energy consumption
Pick-up AC
GOES 2
AC Sealing
GOES 2
Pick-up DC
W 1.8
DC Sealing
W 1.8
Duty Factor
% DF 100
Maximum Operating Frequency
Ops/h 4000
Minimal Command Time
AC
Ms 50
DC
Ms 30
Repeat Accuracy (Deviation)
%
Technical data for design verification
Rated operating current specified in heat dissipation
In One 6
Heat dissipation per pole, dependent on the current
Pgrapevine W 0.9
Heat dissipation equipment, dependent on the current
Pgrapevine W 0
Static heat dissipation, not dependent on current
Pvs W 1.8
Heat dissipation capacity
PDiss W 0
Ambient operating temperature min.
°C -20
Operating environment max. temperature
°C 60
IEC/EN 61439 Design Verification
10.2 Strength of Materials and Parts
10.2.2 Corrosion Resistance
Complies with the product standard.
10.2.3.1 Verification of the thermal stability of enclosures
Complies with the product standard.
10.2.3.2 Verification of the Strength of Normal Heat Insulation Materials
Complies with the product standard.
10.2.3.3 Verification of the resistance of insulating materials to abnormal heat and fire due to internal electrical effects
Complies with the product standard.
10.2.4 Ultraviolet (UV) resistance
Complies with the product standard.
10.2.5 Lifting
It is not applied, since all the cells must be evaluated.
10.2.6 Mechanical Impact
It is not applied, since all the cells must be evaluated.
10.2.7 Registrations
Complies with the product standard.
10.3 Degree of protection of the ASSEMBLIES
It is not applied, since all the cells must be evaluated.
10.4 Separations and Creepage Distances
Complies with the product standard.
10.5 Protection against electric shock
It is not applied, since all the cells must be evaluated.
10.6 The Incorporation of Switching Devices and Components
It is not applied, since all the cells must be evaluated.
10.7 Internal Electrical Circuits and Connections
It is the panel of the generator of responsibility.
10.8 Connections for External Conductors
It is the panel of the generator of responsibility.
10.9 Insulation properties
10.9.2 Power Electric Force Frequency
It is the panel of the generator of responsibility.
10.9.3 Impulse Withstand Voltage
It is the panel of the generator of responsibility.
10.9.4 Testing of Insulation Boxes
It is the panel of the generator of responsibility.
10.10 Temperature Rise
The builder panel is responsible for the increase in the calculation temperature. Eaton will provide data heat dissipation for the devices.
10.11 Short Circuit Rating
It is the panel of the generator of responsibility. The cell specifications must be observed.
10.12 Electromagnetic Compatibility
It is the panel of the generator of responsibility. The cell specifications must be observed.
10.13 Mechanical Function
The device meets the requirements, provided that the information on the instruction sheet (IL) is observed.
Technical data ETIM 6.0(Show Features)(Hide).
Relays (EG000019) / Relay Timer (EC001439)
Electrical Engineering, Automation, Process Control, Engineering Low Voltage Switch Technology/Relay and Socket/Timed Relay ([email protected] [AKF092010])
Electrical Connection Type
Connecting screw
Delay function in energization
Yes
Disable delay function
No
Floating contact function in energization
No
Floating contact function on deactivation
No
The star-delta function
No
The pulse function of the conformation of
No
Flashing function, starting with pause, fixed time
No
Intermittent function, starting with pulse, fixed time
No
The clock function, starting with the pause, the variable
No
The clock function, starting with the pulse, the variable
No
With socket of
No
Remote operation possible
No
Suitable for remote control only
No
Pluggable in auxiliary contact block
No
Rated Supply Voltage Control Us AC 50HZ
V 24 - 240
Rated Supply Voltage Control Us AC 60HZ
V 24 - 240
Rated Supply Voltage Control with Us at DC
V 24 - 240
Voltage Drive Type
AC/DC
Time Range
s 1.5 - 30
Number of outputs, undelayed, normally closed contact
0
Number of Outputs, Undelayed, Normally Open Contact
0
Number of Outputs, Undelayed, Switched Contact
0
Number of departures, delayed, normally closed contact
0
Number of departures, delayed, normally open contact
0
Number of departures, delayed, change of contact
1
Outputs, reversible delayed/undelayed
No
With the semiconductor output.
No
Wide
mm 45
Height
mm 58
Depth
mm 52
Approvals
Product Standards IEC/EN 61812-1; IEC/EN 60947-5-1; UL 508; CSA 22.2 No. 14; CE marking
UL File No. E29184
UL Control Category No. NKCR, NKCR7
CSA File No. 12528
CSA Class No. 3211-03
North America Certification UL listed, CSA certified
Degree of Protection IEC: IP20, UL/CSA Type:-
Characteristics
IL04910003Z (AWA2527-1587) Solid State Timing Relay
>>

ETIM for 048878 Relays (EC001439)
Feature Name Feature Value
Type of electric connection (EF003961) Screw connection
Complete with socket (EF003359) No
Suitable for DIN rail (top hat rail) mounting (EF007250) No
Suitable for front mounting (EF020288) No
Pluggable on auxiliary contact block (EF006952) No
Function delay-on energization (EF003374) Yes
Function delay on de-energization (EF003401) No
Function floating contact on energization (EF003378) No
Function floating contact on de-energization (EF003402) No
Function star-delta (EF003380) No
Function pulse shaping (EF003403) No
Function flashing, starting with pause, fixed time (EF003363) No
Function flashing, starting with pulse, fixed time (EF003364) No
Clock function, starting with pause, variable (EF003365) No
Clock function, starting with pulse, variable (EF003366) No
Time range (EF003384) 1.5 s
Remote operation possible (EF003361) No
Suitable as remote control (EF003362) No
Rated control supply voltage AC 50 Hz (EF003978) 24 V
Rated control supply voltage AC 60 Hz (EF003979) 24 V
Rated control supply voltage DC (EF003980) 24 V
Voltage type for actuating (EF008242) AC/DC
Number of outputs, undelayed, normally closed contact (EF006835) 0
Number of outputs, undelayed, normally open contact (EF006836) 0
Number of outputs, undelayed, change-over contact (EF006837) 0
Number of outputs, delayed, normally closed contact (EF006838) 0
Number of outputs, delayed, normally open contact (EF006839) 0
Number of outputs, delayed, change-over contact (EF006840) 1
Outputs, reversible delayed/undelayed (EF006988) No
With semiconductor output (EF003373) No
Degree of protection (IP) (EF005474) IP20
Width (EF000008) 45 mm
Height (EF000040) 58 mm
Depth (EF000049) 52 mm

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.