Request QuoteProduct Overview
The Eaton Moeller ETR4-69-A is a timing relay offering versatile multi-function capabilities for controlling time-critical processes in industrial switchboards. Technicians deploy multi-function timing units to handle complex switching tasks such as cyclic flashing, star-delta transitions, and delayed responses.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Type of electric connection (EF003961): Screw connection
- Complete with socket (EF003359): No
- Suitable for DIN rail (top hat rail) mounting (EF007250): Yes
- Suitable for front mounting (EF020288): No
- Pluggable on auxiliary contact block (EF006952): No
- Function delay-on energization (EF003374): Yes
- Function delay on de-energization (EF003401): Yes
- Function floating contact on energization (EF003378): Yes
- Function floating contact on de-energization (EF003402): Yes
- Function star-delta (EF003380): No
- Function pulse shaping (EF003403): Yes
- Clock function, starting with pause, variable (EF003365): Yes
- Clock function, starting with pulse, variable (EF003366): Yes
- Time range (EF003384): 0.05 s
- Remote operation possible (EF003361): No
- Suitable as remote control (EF003362): No
More info
▲General specifications
VDE 0435
UL 508
CSA-22.2 No. 14
IEC/EN 61000-4-3
Standard IEC/EN 61812
IEC/EN 60947-5-1
IEC/EN 61000-4-2
UL File No.: E29184
UL
UL Category Control No.: NKCR
CE
CSA
CSA Class No.: 3211-03
IEC/EN 61812-1
Features & Functions
On- and Off-delayed
Pulse generating
Adjustable timing function
Outputs, reversible delayed/undelayed
Off-delayed
Pulse forming
Delay on de-energization
Multi-functional
Fleeting contact on energization
Clock function, starting with pause, variable
Clock function, starting with pulse, variable
On-delayed
Delay-on energization
Flashing, starting with pulse, fixed time
Fleeting contact on de-energization
Flashing, starting with pause, fixed time
Pulse shaping
General
Terminals: IP20
30,000,000 Operations (AC operated)
6000 V AC
1 x (20 - 14) AWG, solid or stranded
2 x (0.5 - 1.5) mm², flexible with ferrule
1 x (0.5 - 2.5) mm², solid
2 x (0.5 - 1.5) mm², solid
Climatic environmental conditions
Damp heat, cyclic, to IEC 60068-2-30
Electro magnetic compatibility
According to IEC/EN 61000-4-4
1 kV, Signal cable
10 V/m at 80 - 1000 MHz (according to IEC EN 61000-4-3)
1 V/m at 2.0 - 2.7 GHz (according to IEC EN 61000-4-3)
Class B (EN 55011, conducted)
4 kV, asymmetrical, power pulses (Surge), EMC
According to IEC/EN 61000-4-5, power pulses (Surge), EMC
Electrical rating
24 - 240 V AC (at 50/60 Hz)
3 A at AC-14 (cos ϕ = 0.3 440 V)
1.1 x Iₑ (DC-11 L/R - 40 ms)
48 A (AC-14 cos ϕ = 0.3 400 V)
50 A (AC-15 cos ϕ = 0.3 220 V)
1.5 A at DC-11, 24 V
3 A at AC-15, 380 V 400 V 415 V
3 A at AC-15, 300 V
3 A at AC-15, 220 V 230 V 240 V
1.2 A at DC-11, L/R max. 50 ms
3 A at AC-14, 440 V
3 A at AC-14, 300 V (NC)
250 V AC, Between coil and auxiliary contacts, According to EN 61140
Max. 6 A gG/gL, Fuse, Short-circuit rating without welding, Contacts
Magnet system
50 ms, AC
0.85 - 1.1 V AC x Uc
1.8 W at DC (Pick-up power)
2 VA at AC (Sealing power)
1.8 W at DC (Sealing power)