View larger
ETR4-11-A 031882 Y7-31882 EATON ELECTRIC Timing relay, 1W, 0.05s-100h, 24-240V50/60Hz, 24-240VDC, on-delayed
ETR4-11-A
031882
Y7-31882
EATON - MOELLER
1 Pcs.
Automation > Timer relay
Relay timers (KETR, KEMR, KESR)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Eaton Moeller ETR4-11-A timing relay provides reliable on-delay switching functionality within automated industrial installations, governing when auxiliary equipment activates. These robust control components are widely installed in distribution boards to sequence loads and prevent simultaneous inrush currents across plant machinery.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Type of electric connection (EF003961): Screw connection
- Complete with socket (EF003359): No
- Suitable for DIN rail (top hat rail) mounting (EF007250): Yes
- Suitable for front mounting (EF020288): No
- Pluggable on auxiliary contact block (EF006952): No
- Function delay-on energization (EF003374): Yes
- Function delay on de-energization (EF003401): No
- Function floating contact on energization (EF003378): No
- Function floating contact on de-energization (EF003402): No
- Function star-delta (EF003380): No
- Function pulse shaping (EF003403): No
- Clock function, starting with pause, variable (EF003365): No
- Clock function, starting with pulse, variable (EF003366): No
- Time range (EF003384): 0.05 s
- Remote operation possible (EF003361): No
- Suitable as remote control (EF003362): No
More info
▲General specifications
Standard IEC/EN 61812
CSA
CSA-22.2 No. 14
UL
VDE 0435
CE
CSA Class No.: 3211-03
UL Category Control No.: NKCR
CSA File No.: 012528
IEC/EN 61000-4-2
UL 508
IEC/EN 60947-5-1
IEC/EN 61000-4-3
IEC/EN 61812-1
Features & Functions
On-delayed
Delay-on energization
General
IP20
30,000,000 Operations (AC operated)
4000 V AC
1 x (20 - 14) AWG, solid or stranded
2 x (0.5 - 1.5) mm², solid
1 x (0.5 - 2.5) mm², solid
1 x (0.5 - 2.5) mm², flexible with ferrule
Climatic environmental conditions
Damp heat, cyclic, to IEC 60068-2-30
Electro magnetic compatibility
According to IEC/EN 61000-4-4
2 kV, Supply cable
1 V/m at 2.0 - 2.7 GHz (according to IEC EN 61000-4-3)
3 V/m at 1.4 - 2 GHz (according to IEC EN 61000-4-3)
Class B (EN 55011, radiated)
According to IEC/EN 61000-4-5, power pulses (Surge), EMC
2 kV, symmetrical, power pulses (Surge), EMC
Electrical rating
24 – 240 V DC
1.1 x Iₑ (DC-11 L/R - 40 ms)
3 A at AC-15 (cos ϕ = 0.3 220 V)
50 A (AC-15 cos ϕ = 0.3 220 V)
48 A (AC-14 cos ϕ = 0.3 400 V)
3 A at AC-14, 380 V 400 V 415 V
1.5 A at DC-11, 24 V
3 A at AC-15, 380 V 400 V 415 V
1.2 A at DC-11, L/R max. 50 ms
3 A at AC-15, 300 V
3 A at AC-15, 220 V 230 V 240 V
3 A at AC-14, 300 V (NC)
250 V AC, Between coil and auxiliary contacts, According to EN 61140
Max. 6 A gG/gL, fuse, Without welding, Contacts
Magnet system
30 ms, DC
0.7 - 1.1 V DC x Uc
2 VA at AC (Pick-up power)
1.8 W at DC (Sealing power)
1.8 W at DC (Pick-up power)
1.1 x Uc, DC operated max.
0.7 x Uc, DC operated min.
1.1 x Uc, AC operated max.