View larger
DILM32-XTED11-1(RAC240) 105212 Y7-105212 EATON ELECTRIC Timer module, 200-240VAC, 0.05-1s, off-delayed
DILM32-XTED11-1(RAC240)
105212
Y7-105212
EATON - MOELLER
1 Pcs.
Automation > Timer block
Contactors up to 170A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller timer module, 200-240VAC, 0.05-1s, off-delayed part number DILM32-XTED11-1(RAC240) (105212) attaches directly to contactors to introduce time-delayed switching functions into motor control circuits. Timer modules are widely used in industrial motor starters to manage sequential operations, star-delta transitions, or controlled shutdown intervals. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Manufacturer: Eaton Moeller
- Manufacturer part number: DILM32-XTED11-1(RAC240)
- Catalogue code: 105212
- Product description: General specifications Product Name Eaton Moeller® series DILM timer module Catalog Number 105212 Model Code DILM32-XTED11-1(RAC240) EAN 4015081050093 Product Length/Depth 86 mm Product Height 38 mm Product Width 45 mm P
More info
▲General specifications
IEC/EN 60947
UL File No.: E29184
UL Category Control No.: NKCR
CE
UL
UL 508
VDE 0660
CSA-C22.2 No. 14-05
IEC/EN 60947-4-1
CSA
CSA Class No.: 3211-03
DIN EN 61812
Features & Functions
General
200 ms, Off-delayed
3,000,000 Operations (DC operated)
3600 Operations/h
Ambient conditions, mechanical
6 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
Climatic environmental conditions
Damp heat, constant, to IEC 60068-2-78
Terminal capacities
1 x (0.75 - 1.5) mm²
2 x (0.75 - 1.5) mm²
0.8 x 5.5/1 x 6 mm, Terminal screw, Standard screwdriver
Electrical Rating
0.1 A at 220 V, DC-13 L/R - 50 ms (with 1 contact in series)
0.2 A at 110 V, DC-13 L/R - 50 ms (with 1 contact in series)
0.2 A at 110 V, DC-13 L/R - 300 ms (with 1 contact in series)
0.2 A at 60 V, DC-13 L/R - 50 ms (with 1 contact in series)
0.1 A at 220 V, DC-13 L/R - 300 ms (with 1 contact in series)
1 A at 24 V, DC-13 L/R - 50 ms (with 1 contact in series)
0.2 A at 60 V, DC-13 L/R - 300 ms (with 1 contact in series)
3 A at AC-15, 220 V 230 V 240 V
Short-circuit rating
5 kA, SCCR (UL/CSA)
125 A, max. CB, SCCR (UL/CSA)
10/100 kA, Fuse, SCCR (UL/CSA)
10/65 kA, CB, SCCR (UL/CSA)
50/32 A, max. CB, SCCR (UL/CSA)
10/22 kA, CB, SCCR (UL/CSA)
50/32 A, max. CB, SCCR (UL/CSA)
10/100 kA, Fuse, SCCR (UL/CSA)
Conventional thermal current
Switching capacity
5 A, 24 V DC, (UL/CSA)
R300, DC operated (UL/CSA)
Magnet system
0.7 - 1.2 V DC x Uc
Contacts
Safety
250 V AC, Between auxiliary contacts, According to EN 61140