View larger
EMT6-K 269470 Y7-269470 EATON ELECTRIC Thermistor overload relay for machine protection, 1N/O+1N/C, 24-240VA..
EMT6-K
269470
Y7-269470
EATON - MOELLER
1 Pcs.
Automation > Temperature monitoring relay
Thermal Relays
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller model EMT6-K serves as a thermistor overload relay engineered for machine protection in motor control systems. These protective devices monitor winding temperatures inside electric motors via embedded PTC sensors, disconnecting the circuit to prevent overheating and insulation damage. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Type of electric connection (EF003961): Screw connection
- With detachable clamps (EF003340): No
- Voltage type (supply voltage) (EF002991): AC/DC
- Supply voltage AC 50 Hz (EF007532): 24 V
- Supply voltage AC 60 Hz (EF007533): 24 V
- Supply voltage DC (EF007534): 24 V
- Number of measuring circuits (EF003425): 1
- Error registration possible (EF003423): No
- External reset possible (EF003426): No
- Temperature measuring range (EF009788): 0 °C
- Resistance measuring range (EF011955): 750 Ohm
- Connection type auxiliary circuit (EF006820): Screw connection
- Number of contacts as normally closed contact (EF008255): 1
- Number of contacts as normally open contact (EF008256): 1
- Number of contacts as change-over contact (EF008257): 0
- Voltage type (operating voltage) (EF005294): AC/DC
More info
▲General specifications
CSA Class No.: 3211-03
IEC/EN 60947-8
UL Category Control No.: NKCR
UL File No.: E29184
VDE 0660
CSA File No.: 12528
EN 55011
IEC/EN 61000-4-3
CE
IEC/EN 61000-4-2
CSA-C22.2 No. 14
UL
UL 508
IEC/EN 60947
Features & Functions
Short-circuit in the sensor cable
Test function via separate button
General
6000 V AC
250 V AC, Between the contacts and power supply, According to EN 61140
Climatic environmental conditions
Damp heat, constant, to IEC 60068-2-78
Electro magnetic compatibility
1 kV, Signal cable
According to IEC/EN 61000-4-4
1 V/m at 2.0 - 2.7 GHz (according to IEC EN 61000-4-3)
10 V/m at 80 - 1000 MHz (according to IEC EN 61000-4-3)
According to IEC/EN 61000-4-5, power pulses (Surge), EMC
2 kV, symmetrical, power pulses (Surge), EMC
Terminal capacities
20 - 14 AWG, solid or stranded
2 x (0.5 - 1.5) mm², solid
1 x (0.5 - 2.5) mm², flexible with ferrule
2 x (0.5 - 1.5) mm², flexible with ferrule
2, Terminal screw, Pozidriv screwdriver
Electrical rating
3.5 VA at AC
3 A at AC-14, 380 V 400 V 415 V (NO)
1 A at AC-15, 300 V (NO)
3 A at AC-15, 220 V 230 V 240 V (NO)
1 A at AC-15, 380 V 400 V 415 V (NO)
3 A at AC-14, 300 V (NO)
1 A at AC-15, 300 V (NC)
3 A at AC-14, 300 V (NC)
3 A at AC-14, 380 V 400 V 415 V (NC)
1 A at AC-15, 380 V 400 V 415 V (NC)
3 A at AC-15, 220 V 230 V 240 V (NC)
3 A at AC-15, 220 V 230 V 240 V