EMT6-DBK 066168 Y7-66168 EATON ELECTRIC Thermistor overload relay for machine protection, multi-function, 24..
EMT6-DBK
066168
Y7-66168
EATON - MOELLER
1 Pcs.
Automation > Temperature monitoring relay
Thermal Relays
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller EMT6-DBK is a thermistor overload relay designed for machine protection applications, guarding industrial motors and windings against overheating by monitoring temperature sensors embedded within the equipment. These relays are commonly integrated into control panels to safely interrupt power circuits when thermal limits are exceeded, preventing premature motor failure in demanding processing environments.
Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Type of electric connection (EF003961): Screw connection
- With detachable clamps (EF003340): No
- Voltage type (supply voltage) (EF002991): AC/DC
- Supply voltage AC 50 Hz (EF007532): 24 V
- Supply voltage AC 60 Hz (EF007533): 24 V
- Supply voltage DC (EF007534): 24 V
- Number of measuring circuits (EF003425): 1
- Error registration possible (EF003423): Yes
- External reset possible (EF003426): Yes
- Temperature measuring range (EF009788): 0 °C
- Resistance measuring range (EF011955): 750 Ohm
- Connection type auxiliary circuit (EF006820): Screw connection
- Number of contacts as normally closed contact (EF008255): 1
- Number of contacts as normally open contact (EF008256): 1
- Number of contacts as change-over contact (EF008257): 0
- Voltage type (operating voltage) (EF005294): AC/DC
More info
▲General specifications
IEC/EN 60947
UL
IEC/EN 60947-8
UL 508
CE
CSA-C22.2 No. 14
IEC/EN 61000-4-3
IEC/EN 61000-4-2
UL Category Control No.: NKCR
CSA Class No.: 3211-03
UL File No.: E29184
CSA File No.: 12528
EN 55011
VDE 0660
Features & Functions
Notifications of mains and faults via LED display
Test function via separate button
External reset possible
Manual or remote resetting
Trip with short-circuit in the sensor cable
Zero-voltage safe
Error registration possible
Short-circuit recognition and zero-voltage safety can be deactivated
General
4000 V AC
250 V AC, Between the contacts, According to EN 61140
Climatic environmental conditions
Damp heat, cyclic, to IEC 60068-2-30
Electro magnetic compatibility
1 kV, Signal cable
2 kV, Supply cable
3 V/m at 1.4 - 2 GHz (according to IEC EN 61000-4-3)
1 V/m at 2.0 - 2.7 GHz (according to IEC EN 61000-4-3)
2 kV, symmetrical, power pulses (Surge), EMC
4 kV, asymmetrical, power pulses (Surge), EMC
Terminal capacities
1 x (0.5 - 2.5) mm², flexible with ferrule
20 - 14 AWG, solid or stranded
2 x (0.5 - 1.5) mm², solid
2 x (0.5 - 1.5) mm², flexible with ferrule
1 x 6 mm, Terminal screw, Standard screwdriver
Electrical rating
3.5 VA at AC
3 A at AC-14, 380 V 400 V 415 V (NC)
3 A at AC-15, 220 V 230 V 240 V
3 A at AC-14, 400 V (NC)
3 A at AC-15, 220 V 230 V 240 V (NC)
3 A at AC-14, 380 V 400 V 415 V (NO)
1 A at AC-15, 300 V (NO)
1 A at AC-15, 380 V 400 V 415 V (NO)
3 A at AC-15, 220 V 230 V 240 V (NO)
1 A at AC-15, 300 V (NC)
3 A at AC-14, 300 V (NO)
1 A at AC-15, 380 V 400 V 415 V (NC)