View larger
EMT6 066166 Y7-66166 EATON ELECTRIC Thermistor overload relay for machine protection, 1W , 24-240V50/60Hz, 2..
EMT6
066166
Y7-66166
EATON - MOELLER
1 Pcs.
Automation > Temperature monitoring relay
Thermal Relays
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Eaton Moeller EMT6 thermistor overload relay is an essential machine protection component integrated into electrical control panels to monitor the winding temperatures of heavy-duty electric motors. It interrupts the control circuit when connected thermistors detect hazardous thermal accumulation, preventing motor burnouts.
Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Type of electric connection (EF003961): Screw connection
- With detachable clamps (EF003340): No
- Voltage type (supply voltage) (EF002991): AC/DC
- Supply voltage AC 50 Hz (EF007532): 24 V
- Supply voltage AC 60 Hz (EF007533): 24 V
- Supply voltage DC (EF007534): 24 V
- Number of measuring circuits (EF003425): 1
- Error registration possible (EF003423): No
- External reset possible (EF003426): No
- Temperature measuring range (EF009788): 0 °C
- Resistance measuring range (EF011955): 750 Ohm
- Connection type auxiliary circuit (EF006820): Screw connection
- Number of contacts as normally closed contact (EF008255): 1
- Number of contacts as normally open contact (EF008256): 1
- Number of contacts as change-over contact (EF008257): 0
- Voltage type (operating voltage) (EF005294): AC/DC
More info
▲General specifications
IEC/EN 60947-8
UL Category Control No.: NKCR
CSA
CSA-C22.2 No. 14
EN 55011
IEC/EN 60947
IEC/EN 61000-4-2
VDE 0660
CSA File No.: 12528
UL
UL 508
UL File No.: E29184
IEC/EN 61000-4-3
CE
Features & Functions
Notifications of mains and faults via LED display
General
4000 V AC
250 V AC, Between the contacts and power supply, According to EN 61140
Climatic environmental conditions
Damp heat, constant, to IEC 60068-2-78
Electro magnetic compatibility
1 kV, Signal cable
2 kV, Supply cable
3 V/m at 1.4 - 2 GHz (according to IEC EN 61000-4-3)
1 V/m at 2.0 - 2.7 GHz (according to IEC EN 61000-4-3)
2 kV, symmetrical, power pulses (Surge), EMC
4 kV, asymmetrical, power pulses (Surge), EMC
Terminal capacities
1 x (0.5 - 2.5) mm², solid
1 x (0.5 - 2.5) mm², flexible with ferrule
2 x (0.5 - 1.5) mm², flexible with ferrule
20 - 14 AWG, solid or stranded
2, Terminal screw, Pozidriv screwdriver
Electrical rating
3.5 VA at AC
3 A at AC-14, 380 V 400 V 415 V (NO)
3 A at AC-15, 220 V 230 V 240 V (NO)
3 A at AC-15, 220 V 230 V 240 V
3 A at AC-14, 300 V (NO)
1 A at AC-15, 380 V 400 V 415 V (NO)
3 A at AC-14, 300 V (NC)
3 A at AC-14, 400 V (NC)
3 A at AC-14, 380 V 400 V 415 V (NC)
1 A at AC-15, 300 V (NO)
3 A at AC-15, 220 V 230 V 240 V (NC)
1 A at AC-15, 300 V (NC)