Standards
IEC 60 947 -7 -1
RoHS (in accordance with Directive 2002/95/EC of the European Parliament and Council)
conform
Heat deflection temperature
100 °C
UL 94 flame classification
V-0
Comparative tracking index
600 V
Degree of Protection
IP10
Assembly details
Clicks on DIN-rail or on base plate.
Save time on wiring.
Save 80% on space used.
Modular construction, 1-4 pole Systems can be built with several blocks.
Important
This Power Distribution Block is suitable for ALU and CU conductors.
Please pay attention to the common handling guidelines when connecting the Aluminium conductors.
Clean and brush the contact surfaces and lubricate them with an appropriate grease.
As precaution the connections should get retightened regularly.
IECMax. electrical load / Al
630 A
IECMax. electrical load / Cu
800 A
IECMax. operating voltage / Al
1000 V AC
IECMax. operating voltage / Al
1500 V DC
IECMax. operating voltage / Cu
1000 V AC
IECMax. operating voltage / Cu
1500 V DC
MaterialClamping body
Aluminium
MaterialHexagon socket set screw
Steel
Surface finishClamping body
Plated
Surface finishHexagon socket set screw
Zn-Plated
ColourHousing
grey, RAL 7035
Incomersingle wire/multi wire
35 - 300 mm²
Incomersingle wire/multi wire
2 - 600 MCM AWG
Incomerfine wire (with sleeve)
16 - 240 mm²
Incomerfine wire (with sleeve)
6 - 500 MCM AWG
IncomerFlat copper bars
9 x 4 - 50 x 10
IncomerTorque
25 - 35 N/m
IncomerTorque
221 - 309.7 lbf
Outgoingssingle wire/multi wire
35 - 300 mm²
Outgoingsfine wire (with sleeve)
16 - 240 mm²
OutgoingsFlat copper bars
9 x 4 - 24 x 10 mm
OutgoingsTorque
25 - 35 N/m
OutgoingsTorque
221 - 309.7 lbf
Notes regarding connection
Al-sector conductors tested up to 70mm²