View larger
LN4-4-1000-I 112017 Y7-112017 EATON ELECTRIC Switch-disconnector, 4 p, 1000A, frame size 4
LN4-4-1000-I
112017
Y7-112017
EATON - MOELLER
1 Pcs.
Connectors > Switch disconnector
Circuit Breakers LZM
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Eaton Moeller LN4-4-1000-I switch-disconnector provides safe electrical isolation in heavy-duty industrial power distribution networks. Devices of this type are installed to manually disconnect circuits during maintenance work or emergency shutdowns, protecting downstream machinery. Please note that pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Version as main switch (EF006981): Yes
- Version as maintenance-/service switch (EF006986): Yes
- Version as safety switch (EF006985): No
- Version as emergency stop installation (EF006959): Yes
- Version as reversing switch (EF009408): No
- Max. rated operation voltage Ue AC (EF007355): 400 V
- Rated operating voltage (EF001435): 690 V
- Rated permanent current at AC-21, 400 V (EF009165): 0 A
- Rated operation power at AC-3, 400 V (EF001364): 0 kW
- Rated short-time withstand current lcw (EF007050): 25 kA
- Rated operation power at AC-23, 400 V (EF007027): 560 kW
- Switching power at 400 V (EF009166): 0 kW
- Conditioned rated short-circuit current Iq (EF001444): 100 kA
- Number of poles (EF001391): 4
- Motor drive optional (EF007386): Yes
- Motor drive integrated (EF006697): No
More info
▲General specifications
Product specifications
Version as maintenance-/service switch
Version as main switch
Version as emergency stop installation
Fixed
Intermediate mounting
Built-in device fixed built-in technique
Ground mounting
1600 A (415 V AC-1, making and breaking capacity)
1600 A (690 V AC-22/23A, making and breaking capacity)
1600 A (415 V AC-22/23A, making and breaking capacity)
10 segments of 80 mm x 1 mm (2x) at rear-side width extension
Max. 10 segments of 50 mm x 1 mm (2x) at rear-side connection (punched)
Max. 10 segments of 32 mm x 1 mm (2x) at flat conductor terminal
Min. 10 segments of 50 mm x 1 mm (2x) at rear-side connection (punched)
Min. 6 segments of 16 mm x 0.8 mm at flat conductor terminal
1000 operations at 690 V AC-3
2000 operations at 400 V AC-3
2000 operations at 690 V AC-1
2000 operations at 415 V AC-3
3000 operations at 415 V AC-1
Disconnectors/main switches
Voltage release optional
N4-630…1600: 2 x 800 AgGgL
100 kA at 400/415 V
100 kA at 400/415 V
N4-630…1600: 2 x 800 AgGgL
0.75 mm² - 2.5 mm² (1x)
Max. 80 mm x 10 mm (2x) at rear-side width extension
Min. 60 mm x 10 mm at rear-side width extension
Min. 25 mm x 5 mm direct at switch rear-side connection
M10 at rear-side screw connection
Max. 50 mm x 10 mm (2x) at rear-side 1-hole module plate
Max. 80 mm x 10 mm (2x) direct at switch rear-side connection
Max. 50 mm x 10 mm (2x) direct at switch rear-side connection
50 mm x 10 mm (2x) at rear-side 2-hole module plate
95 mm² - 240 mm² (6x) at rear-side width extension
35 mm² - 185 mm² (4x) at rear-side 2-hole module plate
120 mm² - 300 mm² (1x) at rear-side 1-hole module plate
300 mm² (4x) at rear-side width extension
95 mm² - 185 mm² (2x) at rear-side 2-hole module plate
95 mm² - 300 mm² (2x) at rear-side 1-hole module plate
120 mm² - 185 mm² (1x) direct at switch rear-side connection