View larger
LN3-4-400-I 112010 Y7-112010 EATON ELECTRIC Switch-disconnector, 4 p, 400A, frame size 3
LN3-4-400-I
112010
Y7-112010
EATON - MOELLER
1 Pcs.
Connectors > Switch disconnector
Circuit Breakers LZM
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Eaton Moeller LN3-4-400-I 112010 Y7-112010 Eaton Electric Switch-disconnector, 4 p, 400A acts as a robust protective isolation device within heavy electrical distribution grids. Four-pole switch disconnectors safely disconnect phase and neutral lines during maintenance procedures.
All pricing, availability, and lead times are confirmed per enquiry through a formal RFQ.
- Version as main switch (EF006981): Yes
- Version as maintenance-/service switch (EF006986): Yes
- Version as safety switch (EF006985): No
- Version as emergency stop installation (EF006959): Yes
- Version as reversing switch (EF009408): No
- Max. rated operation voltage Ue AC (EF007355): 400 V
- Rated operating voltage (EF001435): 690 V
- Rated permanent current at AC-21, 400 V (EF009165): 0 A
- Rated operation power at AC-3, 400 V (EF001364): 0 kW
- Rated short-time withstand current lcw (EF007050): 12 kA
- Rated operation power at AC-23, 400 V (EF007027): 200 kW
- Switching power at 400 V (EF009166): 0 kW
- Conditioned rated short-circuit current Iq (EF001444): 100 kA
- Number of poles (EF001391): 4
- Motor drive optional (EF007386): Yes
- Motor drive integrated (EF006697): No
More info
▲General specifications
Product specifications
Version as maintenance-/service switch
Version as main switch
Version as emergency stop installation
Distribution board installation
Fixed
Built-in device fixed built-in technique
Intermediate mounting
630 A (415 V AC-1, making and breaking capacity)
630 A (690 V AC-1, making and breaking capacity)
630 A (690 V AC-22/23A, making and breaking capacity)
Max. 8 segments of 24 mm x 1 mm (2x) at box terminal
Min. 6 segments of 16 mm x 0.8 mm at rear-side connection (punched)
Max. 10 segments of 24 mm x 1 mm + 5 segments of 24 mm x 1 mm
Max. 10 segments of 32 mm x 1 mm + 5 segments of 32 mm x 1 mm at rear-side connection (punched)
Min. 6 segments of 16 mm x 0.8 mm at box terminal
2000 operations at 690 V AC-3
3000 operations at 400 V AC-3
3000 operations at 415 V AC-3
3000 operations at 690 V AC-1
5000 operations at 415 V AC-1
Interlockable
Disconnectors/main switches
80 kA at 690 V
100 kA at 400/415 V
PN3(N3)-400…630: 630 AgGgL
100 kA at 400/415 V
0.75 mm² - 1.5 mm² (2x)
Max. 10 mm x 50 mm (2x) at rear-side width extension
M10 at rear-side screw connection
Max. 30 mm x 10 mm + 30 mm x 5 mm direct at switch rear-side connection
16 mm² (2x) direct at switch rear-side connection
16 mm² (2x) at box terminal
16 mm² (1x) direct at switch rear-side connection
300 mm² (2x) at rear-side width extension
25 mm² - 240 mm² (2x) direct at switch rear-side connection
50 mm² - 240 mm² (2x) at 2-hole tunnel terminal
35 mm² - 240 mm² (1x) at box terminal
25 mm² - 120 mm² (2x) at box terminal
25 mm² - 185 mm² (1x) at tunnel terminal
50 mm² - 240 mm² (1x) at 2-hole tunnel terminal