View larger
LN1-4-100-I 111999 Y7-111999 EATON ELECTRIC Switch-disconnector, 4 p, 100A, frame size 1
LN1-4-100-I
111999
Y7-111999
EATON - MOELLER
1 Pcs.
Connectors > Switch disconnector
Circuit Breakers LZM
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
LN1-4-100-I 111999 Y7-111999 EATON ELECTRIC Switch-disconnector, 4 p, 100A, frame size 1 operates as a secure manual disconnect device designed to interrupt power feeds in industrial electrical panels. Technicians typically install these units to ensure safe isolation during maintenance and emergency shut down procedures. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Version as main switch (EF006981): Yes
- Version as maintenance-/service switch (EF006986): Yes
- Version as safety switch (EF006985): No
- Version as emergency stop installation (EF006959): Yes
- Version as reversing switch (EF009408): No
- Max. rated operation voltage Ue AC (EF007355): 400 V
- Rated operating voltage (EF001435): 690 V
- Rated permanent current at AC-21, 400 V (EF009165): 0 A
- Rated operation power at AC-3, 400 V (EF001364): 0 kW
- Rated short-time withstand current lcw (EF007050): 2 kA
- Rated operation power at AC-23, 400 V (EF007027): 55 kW
- Switching power at 400 V (EF009166): 0 kW
- Conditioned rated short-circuit current Iq (EF001444): 100 kA
- Number of poles (EF001391): 4
- Motor drive optional (EF007386): Yes
- Motor drive integrated (EF006697): No
More info
▲General specifications
Product specifications
Version as emergency stop installation
Version as main switch
Version as maintenance-/service switch
Intermediate mounting
Fixed
Ground mounting
Distribution board installation
160 A (690 V AC-1, making and breaking capacity)
160 A (415 V AC-22/23A, making and breaking capacity)
160 A (415 V AC-1, making and breaking capacity)
Max. 9 segments of 9 mm x 0.8 mm at box terminal
7500 operations at 400 V AC-3
7500 operations at 690 V AC-1
10000 operations at 400 V AC-1
10000 operations at 415 V AC-1
7500 operations at 415 V AC-3
Interlockable
Disconnectors/main switches
PN1(N1)-63…125: 125 AgGgL; PN1(N1)-160: 160 AgGgL
80 kA at 690 V
100 kA at 400/415 V
PN1(N1)-63…125: 125 AgGgL; PN1(N1)-160: 160 AgGgL
0.75 mm² - 2.5 mm² (1x)
M6 at rear-side screw connection
Max. 16 mm x 5 mm direct at switch rear-side connection
10 mm² - 16 mm² (1x) direct at switch rear-side connection
10 mm² - 16 mm² (1x) at box terminal
16 mm² (1x) at tunnel terminal
6 mm² - 16 mm² (2x) at box terminal
25 mm² - 70 mm² (1x) at box terminal
25 mm² - 70 mm² (1x) direct at switch rear-side connection
25 mm² (2x) at box terminal
25 mm² - 95 mm² (1x) at tunnel terminal