View larger
SN3-050-EU8
100643
EATON - MOELLER
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Product range | SN3 switched-mode power supply units | ||
Description | Primary pulsed power supply, power reserve from up to 50 % Up to 5 devices can be paralleled to increase power and for redundancy | ||
Phases | Single-phase | ||
Input voltage range | 85 - 264 V AC 100 - 350 V DC | ||
Instructions | At ≧ 264 V DC additionally suitable, use fuse. | ||
Nominal input voltage | 110 - 240 V DC 110 - 240 V DC | ||
Rated output voltage | 24 V DC (-1/5%) | ||
Rated output current | A | 5 | |
Setting range for the output voltage | 22 - 28 V DC | ||
Rated output power | W | 120 | |
For use with | easy… MFD… EC4P… XC-CPU… XIOC… PS4… |
| General | |||
Standards | EN 61204, 2006/95/EC, 2004/108/EC, EN 50178, EN 60950, UL 60950, UL 508, SELV (EN 60950) | ||
Degree of protection | |||
Enclosures | IP20 | ||
Terminals | IP20 | ||
Protection class | according to EN 61140, Class 1 | ||
Mounting | DIN rail (IEC/EN 60715), snap fixing | ||
Mounting position | Horizontal | ||
Heat dissipation | W | part no. ≦ 15 | |
Efficiency | % | 88 | |
Weight | kg | 0.96 | |
Minimum distance to adjacent devices | mm | horizontal 10, vertical 80 | |
| Terminal capacities | |||
| Only operate plug-in terminals off load. | |||
Input circuit | |||
Flexible with ferrule | mm2 | 0.2…2.5 (22…14 AWG) | |
Flexible without ferrule | mm2 | 0.2…2.5 (22…14 AWG) | |
Massive | mm2 | 0.2…2.5 (22…14 AWG) | |
Output circuit | |||
Flexible with ferrule | mm2 | 0.12…2.5 (26…14 AWG) | |
Flexible without ferrule | mm2 | 0.12…2.5 (26…14 AWG) | |
Massive | mm2 | 0.12…2.5 (26…14 AWG) | |
| Environmental compatibility | |||
Ambient temperature, operation | °C | -25 - +70 | |
Ambient temperature, full load | °C | 0 - +60 (without derating) | |
Ambient temperature, storage | °C | - 40 - + 85 | |
Climatic proofing | to IEC 60068-2-3, 93% at +40 °C, no condensation | ||
Overvoltage category/pollution degree | according to EN 50178; 2 | ||
Climatic class (IEC) | according EN 60721; 3K3 | ||
Vibrations (IEC/EN 60068-2-6) | 1…57 Hz, amplitude ±0.075 mm; 57…100 Hz, 5 g | ||
Mechanical shock resistance (IEC 60068-2-27) | 30 g all directions | ||
| Insulation voltage | |||
Inputs/outputs | 3 kV AC (type test), 1.2 kV AC (routine test) | ||
Input | 1.5 kV AC (type test), 1.2 kV AC (routine test) | ||
Output | 350 V AC (routine test) | ||
| Electromagnetic compatibility (EMC) | |||
Interference immunity | EN 61000-6-2 | ||
ESD | Air/contact discharge | kV | according to EN 61000-4-2, level 4-8KV/15KV |
RFI | according to EN 61000-4-3, level 3-10 V/m | ||
Burst | according to EN 61000-4-4, level 4-4 KV | ||
Surge | according to EN 61000-4-5, level 4-2KV symmetrical, Level 3-3KV asymmetrical | ||
Cable-born HF | according to EN 61000-4-6, level 3-10 V | ||
Emitted interference | EN 61000-6-3 | ||
Electromagnetic fields | (0.08…1) / (1,4…2) / (2…2,7) GHz | V/m | according to EN 55022, Class B |
Cable-born HF | according to EN 55022, Class B | ||
| Input circuit | |||
Supply frequency | |||
Rated value | Hz | 50/60 | |
Range | Hz | 47 - 63 | |
Current consumption | |||
At 110 … 240 V AC | A | Approx. 2.2…1.2 | |
Power consumption | W | Normally 135 | |
Inrush current limiter/i2t (cold start) | ≦ 23 A / ca. 0.9 A2s | ||
Mains failure bridging | ms | typ. ≧ 100 | |
Run-up time after mains voltage applied | ms | Normally ≧ 100 | |
Transient overvoltage protection | Varistors | ||
Internal input fuse (device protection, not accessible) | 4 AT | ||
Discharge current to PE | mA | < 3.5 mA | |
| Output circuit | |||
L+, L+, L-, L- | Proof against short-circuit, no-load and overload | ||
Rated output power | W | 120 | |
Rated output current Tu≦ 60 °C | A | 5 | |
Peak output current (power reserves) Tu ≦ 40 °C | A | Normally ≦ 7.25 | |
Derating 60 °C ≦ Tu≦ 70 °C | 2.5 % per Kelvin temperature increase | ||
Control deviation at | |||
Load change 10…90 %, static | Normally | ±0.05 % | |
Load change 10…90 %, dynamic | Normally | ±3 % | |
Controller acting time | ms | Normally 1 | |
Input voltage deviation ±10 % | Normally ±0.05 % | ||
Rise time 10…90 % | ms | Normally ≦ 30 | |
Residual ripple and switching peaks | 20 MHz typically < 50 mVss | ||
Can be switched in parallel | yes, up to 5 devices for redundancy and for power increase, non symetrical current | ||
Series connection capability | yes, for voltage increase (max. 2 off) | ||
Resistance to reverse feed | yes, limited to approx. 35 V AC | ||
Power factor correction (PFC) | Yes | ||
Status indication | OUTPUT OK: LED green | ||
Overload characteristics | → AWA2727-2318 (www.moeller.net/support) | ||
Behaviour on short-circuit | continuously with current limitation | ||
Current limitation at short-circuit | A | Approx. 11 | |
Short-circuit protection | Proof against sustained short circuit | ||
Overload protection | thermal protection | ||
Capacitive load starting | Not restricted | ||
| Notes | |||
| At U ≧ 264 V DC additionally suitable, use external fuse. | |||
| PLC's (EG000024) / PLC system power supply (EC000599) | |||
| Electric engineering, automation, process control engineering / Control / Programmable logic control (SPS) / SPS system power supply (ecl@ss8-27-24-22-09 [AKE532010]) | |||
Input voltage at AC 50 Hz | V | 85 - 264 | |
Input voltage at AC 60 Hz | V | 85 - 264 | |
Input voltage at DC | V | 100 - 350 | |
Type of voltage (input voltage) | AC/DC | ||
Max. input current AC 50 Hz | A | 2.2 | |
Max. input current AC 60 Hz | A | 2.2 | |
Max. input current DC | A | 1.35 | |
Type of output voltage | DC | ||
Output voltage at AC 50 Hz | V | 0 - 0 | |
Output voltage at AC 60 Hz | V | 0 - 0 | |
Output voltage at DC | V | 0 - 0 | |
Max. output current AC 50 Hz | A | 0 | |
Max. output current AC 60 Hz | A | 0 | |
Max. output current DC | A | 5 | |
Redundancy | Yes | ||
Suited for safety functions | Yes | ||
Width | mm | 130 | |
Height | mm | 130 | |
Depth | mm | 57 | |
| Feature Name | Feature Value |
|---|---|
| Input voltage AC 50 Hz (EF007118) | 85 V |
| Input voltage DC (EF007120) | 100 V |
| Output voltage DC (EF007001) | 22 V |
| Max. output current AC 50 Hz (EF007351) | 5 A |
| Redundancy (EF003156) | No |
| Suitable for safety functions (EF001597) | No |
| Width (EF000008) | 57 mm |
| Height (EF000040) | 130 mm |
| Depth (EF000049) | 130 mm |