EATON - MOELLER SN3-050-BU8 SN3-050-BU8 100640 EATON ELECTRIC Moni stabilized power source View larger
Images are for illustrative purposes only. Please refer to data sheet for details

SN3-050-BU8 100640 EATON ELECTRIC Moni stabilized power source

SN3-050-BU8

100640

EATON - MOELLER

1 Pcs.

Moni stabilized power source Primary pulsed switched-mode power supply unit, input voltage range:85-264VAC or 100-350VDC, output voltage 24VDC fixed, rated output current 5A, power reserves up to 50%, up to 5 devices can be paralleled to increase power and for redundancy, high efficiency up to 90%

Automation > PLC system power supply

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Delivery programme
Product range
SN3 switched-mode power supply units
Description
Primary pulsed power supply, power reserve from up to 50 %
Up to 5 devices can be paralleled to increase power and for redundancy
Phases
Single-phase
Input voltage range
85 - 264 V AC
100 - 350 V DC
Instructions
At
General
Standards
EN 61204, 2006/95/EC, 2004/108/EC, EN 50178, EN 60950, UL 60950, UL 508, SELV (EN 60950)
Degree of protection
Enclosures
IP20
Terminals
IP20
Protection class
according to EN 61140, Class 1
Mounting
DIN rail (IEC/EN 60715), snap fixing
Mounting position
Horizontal
Heat dissipation
W part no.
Technical data for design verification
Rated operational current for specified heat dissipation
In A 0
Heat dissipation per pole, current-dependent
Pvid W 0
Equipment heat dissipation, current-dependent
Pvid W 0
Static heat dissipation, non-current-dependent
Pvs W 15
Heat dissipation capacity
Pdiss W 0
Operating ambient temperature min.
°C -25
Operating ambient temperature max.
°C 70
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
Meets the product standard's requirements.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Technical data ETIM 6.0(Show features)(Hide features)
PLC's (EG000024) / PLC system power supply (EC000599)
Electric engineering, automation, process control engineering / Control / Programmable logic control (SPS) / SPS system power supply ([email protected] [AKE532011])
Input voltage at AC 50 Hz
V 85 - 264
Input voltage at AC 60 Hz
V 85 - 264
Input voltage at DC
V 100 - 350
Type of voltage (input voltage)
AC/DC
Max. input current AC 50 Hz
A 2.2
Max. input current AC 60 Hz
A 2.2
Max. input current DC
A 1.35
Type of output voltage
DC
Output voltage at AC 50 Hz
V 0 - 0
Output voltage at AC 60 Hz
V 0 - 0
Output voltage at DC
V 0 - 0
Max. output current AC 50 Hz
A 0
Max. output current AC 60 Hz
A 0
Max. output current DC
A 5
Redundancy
Yes
Suitable for safety functions
Yes
Width
mm 130
Height
mm 130
Depth
mm 57
Dimensions
IL05012004Z (IL05012004Z) Power supply unit
>>

ETIM for 100640 PLC's (EC000599)
Feature Name Feature Value
Input voltage AC 50 Hz (EF007118) 85 V
Input voltage AC 60 Hz (EF007119) 85 V
Input voltage DC (EF007120) 100 V
Type of voltage (input voltage) (EF003033) AC/DC
Max. input current AC 50 Hz (EF007360) 2.2 A
Max. input current AC 60 Hz (EF007361) 2.2 A
Max. input current DC (EF007362) 1.35 A
Type of output voltage (EF008222) AC/DC
Output voltage AC 50 Hz (EF006999) 0 V
Output voltage AC 60 Hz (EF007000) 0 V
Output voltage DC (EF007001) 0 V
Max. output current AC 50 Hz (EF007351) 0 A
Max. output current AC 60 Hz (EF007352) 0 A
Max. output current DC (EF007353) 5 A
Redundancy (EF003156) Yes
Suitable for safety functions (EF001597) Yes
Width (EF000008) 57 mm
Height (EF000040) 130 mm
Depth (EF000049) 130 mm

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.